background image

 

8 • 65-2340RK Toxic Gas Transmitter

produces an electrical output that corresponds to the detection range of the sensor.

Amplifier

The amplifier converts the electrical output from the detector to a 4 to 20 mA signal that 
corresponds to the detection range and transmits the signal to a gas monitoring controller. A 
foam gasket that orients the amplifier and keeps it from rotating is installed on the bottom of 
the amplifier. The amplifier includes the detector terminal strip, controller terminal strip, zero 
pot, span pot, and test points (see Figure 3).

Figure 3: Amplifier Component Location

Controller Terminal Strip

The controller terminal strip is a two position plug-in style terminal strip located at the top 
edge of the amplifier. Use the controller terminal strip to wire the transmitter to a controller.

Detector Terminal Strip

The detector terminal strip is a four position plug-in style terminal strip located below the 
controller terminal strip. Two of the positions are for use with an oxygen sensor and are not 
used in the toxic gas transmitter. Use the two detector terminal strip positions that are labelled 
“TOXIC” to connect the detector to the amplifier.

NOTE:

The detector is factory-wired to the detector terminal strip. See “Wiring the Toxic Gas 
Transmitter to a Controller” on page 11 for a
ll wiring procedures related to the 
transmitter.

Zero Pot

The zero pot is located in the upper left corner of the amplifier (see Figure 3). Use a small flat 
blade screwdriver to turn the zero pot’s adjustment screw and adjust the amplifier’s zero (fresh 
air) output during the start-up and calibration procedures. Turn the adjustment screw 
clockwise to increase the zero output and counterclockwise to decrease the zero output.

Controller Terminal Strip

Detector Terminal Strip

Mounting Screw

  

SI

G

/P

W

R

 

SP

A

N

Span Pot

Factory Adjust Pot

Zero Pot

ZE

R

O

Red + Test Point

Black - Test Point

S

 T

O

X

IC

    

   

    

O

X

Y

Содержание 65-2340RK

Страница 1: ...RKI Instruments Inc www rkiinstruments com 65 2340RK Toxic Gas Transmitter Operator s Manual Part Number 71 0143RK Revision G Released 6 12 20...

Страница 2: ...c calibration and maintenance of the detector is essential for proper operation and correct readings Please calibrate and maintain this detector regularly Frequency of calibration depends upon the typ...

Страница 3: ...ement costs local repair costs transportation costs or contingent expenses incurred without our prior approval THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTATIONS EX...

Страница 4: ...iring the Toxic Gas Transmitter 11 Startup 13 Introducing Incoming Power 13 Setting the Zero Signal 13 Maintenance 14 Preventive Maintenance 14 Troubleshooting 14 Replacing Components of the Toxic Gas...

Страница 5: ...en using the 65 2340RK you must follow the instructions and warnings in this manual to assure proper and safe operation of the 65 2340RK and to minimize the risk of personal injury Be sure to maintain...

Страница 6: ...components of the toxic gas transmitter The toxic gas transmitter is a 4 20 mA type detector head It consists of the toxic detector amplifier and junction box Figure 1 Toxic Transmitter Component Loca...

Страница 7: ...pre amplifier located between the connector and the two interconnect wires conditions the sensor s signal before the signal reaches the controller Each plug in sensor type Cl2 for example requires a...

Страница 8: ...terminal strip is a four position plug in style terminal strip located below the controller terminal strip Two of the positions are for use with an oxygen sensor and are not used in the toxic gas tra...

Страница 9: ...mitter at a mounting site that is remote from the controller The junction box protects the amplifier and wiring connections made to the amplifier Use the top 3 4 NPT conduit hub to connect wiring from...

Страница 10: ...e 4 Mounting the Toxic Gas Transmitter 2 At the monitoring site you select hang or mount the junction box with the detector facing down see Figure 4 3 65 Rubber Spacer 3X 3 4 NPT Conduit Hub 0 38 75 2...

Страница 11: ...ox 7 Pull out the controller terminal strip and connect the two wires to the terminal strip as follows see Figure 5 Connect the positive wire to the SIG PWR terminal Connect the signal wire to the SIG...

Страница 12: ...oller RKI controllers typically have a ground stud that can be used to ground the cable s drain wire Gas Type Table Gas Type W ire 0 10 ppm Cl2 0 3 ppm Cl2 S SIG P W R TO XIC OX Y Z E R O Controller D...

Страница 13: ...of toxic gas in the monitoring environment use the calibration kit and the zero air calibration cylinder to introduce fresh air to the detector and verify an accurate zero setting See Calibration on p...

Страница 14: ...s transmitter NOTE This troubleshooting guide describes transmitter problems only See the controller operator s manual for problems you may encounter with the controller Table 2 Troubleshooting the To...

Страница 15: ...al circumstances the transmitter requires calibration once every 3 months Some applications may require a more frequent calibration schedule The calibration cylinder is low out dated or defective The...

Страница 16: ...n sensor 1 Turn off the controller 2 Turn off or unplug power to the controller 3 Remove the junction box cover 4 Remove the detector terminal strip from its socket 5 Disconnect the detector leads fro...

Страница 17: ...plifier as shown in Figure 5 on page 12 If controller leads or detector leads were removed during this procedure refer to Figure 5 on page 12 for the detector and amplifier connections NOTE When a tra...

Страница 18: ...you dedicate a regulator for use with chlorine Cl2 gas and that you do not use that dedicated regulator for any other gases particularly hydrogen sulfide H2S WARNING Not using the recommended calibrat...

Страница 19: ...screwed onto the housing body 7 Push the calibration cup onto the plug in sensor that sticks through the housing cap The calibration cup seals to the sensor with an O ring Setting the Zero Fresh Air R...

Страница 20: ...u determined earlier If necessary use the span pot on the amplifier to adjust the reading to match the correct response reading 4 Turn the regulator knob clockwise to close the regulator 5 Unscrew the...

Страница 21: ...in sensor 65 2300RK SO2 Replacement detector assembly SO2 includes plug in sensor 71 0143RK 65 2340RK Operator s Manual this document 81 0076RK Zero air calibration cylinder 17 liter 81 0076RK 01 Zero...

Страница 22: ...cylinder 81 F503RK LV Calibration kit includes regulator calibration cup and a 34 liter 10 ppm NH3 in nitrogen aluminum calibration cylinder 81 F603RK Calibration kit includes regulator calibration cu...

Страница 23: ...Gas Transmitter 23 ESM K01 D CL2 ESM 01 plug in sensor 0 3 00 ppm chlorine diffusion type only ESM K01D CL2 10 ESM 01 plug in sensor 0 10 0 ppm chlorine diffusion type only Table 4 Parts List Part Num...

Отзывы: