background image

 

65-2301RKSS Toxic Detector • 7

Detector Housing Body

The detector housing body protects the electronic components within the housing. Use the mounting 
threads at the top of the housing to screw the toxic detector into a 3/4 NPT hub. Two wires extend 
from the top of the detector housing body. Use these wires to connect the toxic detector to a controller. 
One of the wires is black and one of the wires is color coded depending on the detector type. See 
Figure 4 on page 9 for the color code assignments.

The housing body includes a 12 position connector at the bottom of the housing body. The plug-in 
sensor mates to this connector. A pre-amplifier located between the connector and the two 
interconnect wires conditions the sensor’s signal before the signal reaches the controller.

Housing Cap, Cap Gasket, & Splashguard

The housing cap screws onto the detector housing. It retains the sensor and protects it from damage. A 
removable splashguard is screwed onto the detector cap to protect the sensor from impact damage, 
direct water spray, and splashing. Unscrew the detector cap to access the sensor for maintenance or 
replacement. A cap gasket seals the interface between the housing and cap.

Plug-in Sensor

The plug-in sensor is secured in the detector assembly by the housing cap. There is a different sensor 
for each target gas. Through a series of chemical and electrical reactions, the sensor produces an 
electrical output that corresponds to the detection range of the sensor.

Junction Box

The stainless steel, corrosion resistant junction box allows you to install the detector at a mounting site 
that is remote from a controller, and it protects the detector wiring connections. Two conduit hubs 
allow you to mount the detector to the junction box and connect the wiring from the detector to a 
controller. An O-ring seals the interface between the junction box cover and the junction box base.

The terminal block within the junction box facilitates the wiring process. A cover on the front of the 
junction box allows access to the interior of the junction box. A locking set screw on the junction box 
cover allows you to secure the junction box cover and prevent it from being removed.

Installation

This section describes procedures to mount the toxic detector in the monitoring environment and wire 
the detector to a controller.

Mounting the Toxic Detector

1.

Select a mounting site that is representative of the monitoring environment. Consider the 
following when you select the mounting site.

Select a site where the detector is not likely to be bumped or disturbed. Make sure there is 
sufficient room to perform start-up, maintenance, and calibration procedures.

Select a site where the target gas is likely to be found first.

NOTE:

If your application does not require a specific mounting site, mount the detector at 
approximately breathing level.

Содержание 65-2301RKSS Series

Страница 1: ...www rkiinstruments com 65 2301RKSS Toxic Detector Operator s Manual Part Number 71 0273RK Revision A Released 7 17 19...

Страница 2: ...alibration and maintenance of the detector is essential for proper operation and correct readings Please calibrate and maintain this detector regularly Frequency of calibration depends upon the type o...

Страница 3: ...t costs local repair costs transportation costs or contingent expenses incurred without our prior approval THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTATIONS EXPRES...

Страница 4: ...the Toxic Detector to a Controller 8 Startup 10 Introducing Incoming Power 10 Setting the Zero Fresh Air Signal 10 Maintenance 10 Preventive Maintenance 10 Troubleshooting 11 Replacing Components of...

Страница 5: ...2301RKSS toxic detectors WARNING When using the 65 2301RKSS you must follow the instructions and warnings in this manual to assure proper and safe operation of the 65 2301RKSS and to minimize the ris...

Страница 6: ...65 2300RK Toxic Detector The 65 2300RK toxic detector consists of the detector housing body detector housing cap splashguard cap gasket and the plug in sensor Figure 2 65 2300RK Toxic Detector Compone...

Страница 7: ...as Through a series of chemical and electrical reactions the sensor produces an electrical output that corresponds to the detection range of the sensor Junction Box The stainless steel corrosion resis...

Страница 8: ...g the Toxic Detector to a Controller WARNING Always verify that power to the controller is OFF before you make wiring connections 1 Turn off the controller 2 Turn off or unplug power to the controller...

Страница 9: ...rough the same conduit hub The power cable may disrupt the transmission of the detector signal to the controller 8 Connect the wires to the applicable controller terminal strip See the controller oper...

Страница 10: ...ccurate zero setting See Calibration on page 14 for instructions to introduce zero air to the detector 1 Verify that the detector is in a fresh air environment environment known to be free of toxic an...

Страница 11: ...r in this section If the fail condition continues contact RKI for further instruction Slow or No Response Difficult or Unable to Calibrate Symptoms Unable to accurately set the zero or response readin...

Страница 12: ...move the toxic sensor 5 Remove the black plug from the top of the replacement sensor 6 Carefully plug the replacement sensor into the connector that is located in the detector housing body WARNING You...

Страница 13: ...llow the replacement detector to warm up for 5 minutes before you continue with the next step 11 Calibrate the replacement detector as described in Calibration on page 14 Calibration Frequency Althoug...

Страница 14: ...ke sure to connect the sample tubing to the calibration cup port that results in the specified flow direction for the 81 1138RK calibration cup Preparing for Calibration 1 Unscrew the splashguard from...

Страница 15: ...nder and toxic gas cylinder If necessary to fit the calibration toxic gas cylinder change the regulator Setting the Response Reading Span 1 Screw the regulator into the calibration gas cylinder 2 Foll...

Страница 16: ...300RK SO2 Replacement detector assembly SO2 includes plug in sensor 71 0273RK 65 2301RKSS Operator s Manual this document 81 0076RK Zero air calibration cylinder 17 liter 81 0076RK 01 Zero air calibra...

Страница 17: ...on cup and a 34 liter 10 ppm NH3 in nitrogen aluminum calibration cylinder 81 F603RK Calibration kit includes regulator calibration cup and 58 liter 2 ppm CL2 in nitrogen aluminum calibration cylinder...

Страница 18: ...18 65 2301RKSS Toxic Detector ESM K01D CL2 10 ESM 01 plug in sensor 0 10 0 ppm chlorine diffusion type only Table 3 Parts List Part Number Description...

Отзывы: