6
•
Applications
61-1020/61-0230 Molecular Property Spectrometer
WARNING: When using the 61-1020/61-0230, you must follow the instructions and warnings
in this manual to assure proper and safe operation of the 61-1020/61-0230 and to
minimize the risk of personal injury. Be sure to maintain and periodically
calibrate the 61-1020/61-0230 as described in this manual.
Applications
The MPS combustible detector is most effective in the following applications:
• High concentrations of hydrogen sulfide (H
2
S) or silicones present where sensor
poisoning is a common problem
• High-humidity environments where catalytic or IR sensors may not hold up
• Environments more likely to have mixtures of hydrocarbons present
Table 2: Specifications
Target/Calibration Gas
With Junction Box
• 61-0230-CH4: Methane
• 61-0230-HC: General hydrocarbons (propane calibration standard)
Without Junction Box
• 61-1020-CH4: Methane
• 61-1020-HC: General hydrocarbons (propane calibration standard)
Area Classification
Explosion-proof for Class I, Groups B, C, and D
Operating
Temperature Range
-20ºC to +50ºC (-4ºF to +122ºF)
Humidity Range
0 - 100% RH (non-condensing)
Pressure Range
80 to 120 kPa
Sampling Method
Diffusion
Detection Range
0 to 100% LEL
Response Time
90% in 45 seconds
Dead Bands
• Methane (CH
4
): 3% LEL
• All other gases: 5% LEL