35-3010RK-03 Sample-Draw Detector • 1

Overview

This manual describes the 35-3010RK-03 sample draw detector. This manual also 
describes how to install, start up, maintain, and calibrate the sample draw detector when 
it is used with a gas monitoring controller. A parts list at the end of this manual lists 
replacement parts and accessories for the detector.

Specifications

Table 1 lists specifications for the 35-3010RK-03.

WARNING: When using the 35-3010RK-03, you must follow the instructions and 

warnings in this manual to assure proper and safe operation of the 
35-3010RK-03 and to minimize the risk of personal injury. Be sure to 
maintain and periodically calibrate the 35-3010RK-03 as described in this 
manual.

Table 1: Specifications

Target Gases & Detection Ranges

Combustible Gas: 0 - 100% LEL
Oxygen: 0-25% volume
Carbon Monoxide (CO): 0 - 300 ppm

Input Power

24 VDC

Current Draw

200 mA

Construction (housing)

Fiberglass/polyester (NEMA 4X)

Dimensions

15.44 in. H x 12.55 in. W x 8.31 in. D

Weight

14 lbs.

Sampling Method

Sample draw

Sample Flowrate to Sensors

1.2 SCFH (nominal)

Response Time

90% in 30 seconds

Accuracy

Combustible Gas:
± 5% of reading or ± 2% LEL (whichever is greater)
Oxygen:
± 0.5% O

2

Carbon Monoxide:
± 5% of reading or ± 5 ppm CO (whichever is greater)

Содержание 35-3010RK-03

Страница 1: ...rkiinstruments com 35 3010RK 03 Sample Draw Detector Part Number 71 0166RK Revision D Released 6 5 17...

Страница 2: ...c calibration and maintenance of the detector is essential for proper operation and correct readings Please calibrate and maintain this detector regularly Frequency of calibration depends upon the typ...

Страница 3: ...ement costs local repair costs transportation costs or contingent expenses incurred without our prior approval THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTATIONS EX...

Страница 4: ...Low Flow Alarm 13 Maintenance 13 Preventive Maintenance 13 Troubleshooting 14 Replacing Components of the Sample Draw Detector 16 Adjusting the Low Flow Setting 17 Calibration Frequency 18 Calibratio...

Страница 5: ...assure proper and safe operation of the 35 3010RK 03 and to minimize the risk of personal injury Be sure to maintain and periodically calibrate the 35 3010RK 03 as described in this manual Table 1 Sp...

Страница 6: ...d by two latches on the right side Four mounting feet are attached to the back of the housing one at each corner Use the mounting feet to install the housing to a vertical surface Use the two conduit...

Страница 7: ...ple Draw Detector Flow Diagram INLET fitting The INLET fitting on the bottom of the housing allows the gas sample to enter the sample draw detector The INLET fitting accepts 1 4 in rigid tubing See In...

Страница 8: ...a flow of 0 6 SCFH the optimum flow rate is 1 2 SCFH Bypass Valve The bypass valve is to the left of the flowmeter The bypass valve adjusts the flow rate to the sensors Use a flat blade screwdriver t...

Страница 9: ...e gas sample to enter the sensor assembly and contact the sensing element The flame arrestor also contains sparks within the sensor Connector The top of the sensor includes five pins that plug into th...

Страница 10: ...nsor signal and the one of the right is for the H2S sensor signal Since the H2S sensor is replaced with a dummy plug in the 35 3010RK 03 the H2S sensor signal cable carries no signal in this version o...

Страница 11: ...pot to make adjustments to the zero reading The test points are labeled CAL 1 and CAL 1 for the CO channel and CAL 2 and CAL 2 for the H2S channel A 100 mV 500 mV output is available at the CO test p...

Страница 12: ...ing connections at the right of the housing Make sure there is sufficient room to perform start up maintenance and calibration procedures Figure 4 Mounting the Sample Draw Detector 2 Close and latch t...

Страница 13: ...rce is OFF before you make wiring connections 1 Turn off the controller 2 Turn off or unplug incoming power to the controller 3 Unlatch and open the housing door of the sample draw detector 4 Guide a...

Страница 14: ...s typically have a ground stud that can be used to ground the cable s drain wire Figure 5 External Field Wiring Sample Draw Detector CO Controller Transmitter Terminals 24 VDC S 4 20 mA 24 VDC Interco...

Страница 15: ...Internal Factory Wiring Sample Draw Detector Green White White Green Black Oxygen Sensor Pump Factory Wired LEL Sensor Connector H2S Not Used CO Sensor Plugs Into Far Side of Preamp Circuit Board Pres...

Страница 16: ...is remote from the sample draw detector you will need two people to perform this test If the flowmeter ball drops to the bottom of the flowmeter the incoming sample line is not leaking 8 Remove your t...

Страница 17: ...le draw detector resulting in a failure indication for each channel at the controller If a low flow alarm occurs press the pump reset switch for about 2 seconds to restart the pump turn off the Fail L...

Страница 18: ...low regulator 1 Screw the regulator into the calibration cylinder 2 Connect the calibration tubing from the regulator to the inlet line at or near the INLET fitting Gas will begin to flow 3 After one...

Страница 19: ...ion The sensor or transmitter wiring to the controller is disconnected or misconnected Recommended Action 1 Check the sample draw detector and if it is in fail find the cause and correct it see above...

Страница 20: ...lift the plate connector and sensor out of the housing 4 Unplug the connector from the sensor 5 Verify that you are using the correct replacement sensor NC 6245 is printed on the sensor then plug the...

Страница 21: ...al clamp 4 Remove the rubber seals from each end of the hydrophobic filter and remove the filter 5 Place the new hydrophobic filter in the same orientation as the one that was removed 6 Place the new...

Страница 22: ...if the environment is not well controlled then more frequent calibration than every 3 months may be necessary for the sample draw detector Calibration LEL Detector This section describes how to calib...

Страница 23: ...meter leads from the test points 2 Reconnect the incoming sample line 3 Wait 1 to 2 minutes to allow the calibration gas to be drawn out and the reading to stabilize 4 Close the housing door 5 Store t...

Страница 24: ...normal oxygen content 20 9 it is necessary to use a zero air cylinder when setting the zero reading 1 Open the housing door 2 The fresh air reading for the oxygen channel is set at the controller See...

Страница 25: ...ple tubing to the regulator 3 Connect the sample tubing from the regulator to the inlet line at or near the INLET fitting 4 Allow the gas to flow for 1 minute 5 Verify a voltmeter reading of 100 mV 2...

Страница 26: ...e Parts List Table 2 lists replacement parts and accessories for the sample draw gas detector Table 2 Parts List Part Number Description 06 1248RK Sample tubing 3 16 x 5 16 specify length for calibrat...

Отзывы: