1. OUTLINE 

The temperature control module for Ethernet V-TIO-P/V-TIO-Q 
has one modular connector (RJ-45) for connection to Ethernet. 
This module conforms to Modbus/TCP (Modbus protocol) 
operating on TCP/IP of Ethernet. 
One this module enables temperature control corresponding to 
two channels. It has power supply terminals in addition to 
temperature control input and output terminals.   
In addition, one digital input (DI) point and two digital output (DO) 
points can be optionally added. 

 

 

Usable modules: 

• 

Temperature control (TIO) module
[Basic type]: V-TIO-A/V-TIO-C 

• 

Temperature control (TIO) module
[Extension type]: V-TIO-B/V-TIO-D

(Up to 30 modules) 

Ethernet

 

Network Hub 

Computer 

(Client) 

Ethernet

 

Temperature control   
module for Ethernet 
V-TIO-P/V-TIO-Q 

(Server) 

Control 

output

Measured 

input 

Power supply 
input (24 V DC) 

Event connector (option)

Digital input:  1 point 
Digital output: 2 points 

 

 

 

The data request side is called “client” (such as 
computer) and the data response (supply) side is called 
“server” (SRV). 

 

Basically, one client corresponds to one server (SRV) 
(i.e. one to one). However, one client can communicate 
with two or more servers depending on the program on 
the client side, but two or more clients cannot 
communicate with one server. 

 

All data are set by communication. For details, see the 

Module Type Controller SRV Ethernet [Modbus/TCP] 
Communication Instruction Manual (IMS01P09-E )

.

 

 
 

2. PRODUCT CHECK 

Before using this product, check each of the following: 

• 

Model code 

• 

Check that all of the accessories delivered are complete. 

• 

Check that there are no scratch or breakage in external 
appearance (case, front panel, or terminal, etc). 

V–TIO–     

 –     

     –     –  –   /Y 

(1) (2)  (3) 

(4) (5)  (6) (7) (8)  (9) (10) (11)  (12) 

(1) Type 

P:  Module for Ethernet, heat control 
Q: Module for Ethernet, heat/cool control 

(2) Control action 

(Each channel common code)

 

[For heat control]

 

F:  PID action with autotuning (AT) (reverse action) 
D:  PID action with autotuning (AT) (direct action) 
[For heat/cool control] 
B:  Heat/cool PID action with autotuning (AT) (air cooling) 
W: Heat/cool PID action with autotuning (AT) (water cooling) 

(3) Input range 

(Each channel common code)

 

[Thermocouple input] 

Type Code

Range 

Code 

Range 

K02

0 to 400 

°

KB9 

32 to 752 

°

 

K04

0 to 800 

°

KB8 

32 to 1472 

°

 K16

200 to 

+

1372 

°

C KB7 

328 to 

+

2501 

°

F

 

K09

0.0 to 400.0 

°

KC2 

32.0 to 752.0 

°

F

 K35

200.0 to 

+

400.0 

°

C KC1 

328.0 to 

+

752.0 

°

F

J02

0 to 400 

°

JC2 

32 to 752 

°

 

J04

0 to 800 

°

JC1 

32 to 1472 

°

 J15

200 to 

+

1200 

°

C JB9 

328 to 

+

2192 

°

F

 

J09

0.0 to 400.0 

°

JC4 

32.0 to 752.0 

°

F

 J27

200.0 to 

+

400.0 

°

C JC3 

328.0 to 

+

752.0 

°

F

T08

0 to 400 

°

TB9 

32 to 752 

°

 

T09

0 to 200 

°

TC1 

32 to 392 

°

 T16

200 to 

+

400 

°

C TB8 

328 to 

+

752 

°

 

T06

0.0 to 400.0 

°

TC3 

32.0 to 752.0 

°

F

 T19

200.0 to 

+

400.0 

°

C TC2 

328.0 to 

+

752.0 

°

F

E01

0 to 800 

°

EA8 

32 to 1472 

°

 

E02

0 to 1000 

°

EA7 

32 to 1832 

°

S05

0 to 1768 

°

SA6 

32 to 3214 

°

R06

0 to 1768 

°

RA6 

32 to 3214 

°

N02

0 to 1300 

°

NA6 

32 to 2372 

°

B03

0 to 1800 

°

BB1 

32 to 3272 

°

PL

A02

0 to 1390 

°

AA6 

32 to 2534 

°

W5Re/
W26Re

W03

0 to 2300 

°

WA9 

32 to 4172 

°

[RTD input] 

Type Code

Range 

Code 

Range 

Pt100

D17

0 to 400 

°

DC5 

32 to 752 

°

 

D33

0 to 850 

°

DC4 

32 to 1562 

°

 

D16

0.0 to 400.0 

°

C  DC7 

32.0 to 752.0 

°

F

 D28

200.0 to 

+

400.0 

°

C DC6 

328.0 to 

+

752.0 

°

F

JPt100

P17

0 to 400 

°

PC5 

32 to 752 

°

 

P23

0 to 600 

°

PC4 

32 to 1112 

°

 

P16

0.0 to 400.0 

°

PC7 

32.0 to 752.0 

°

F

 P28

200.0 to 

+

400.0 

°

C PC6 

328.0 to 

+

752.0 

°

F

[Voltage/current input] 

Type Code

Range

 

0 to 100 mV DC

201

 

0 to 5 V DC 

401

Programmable 

0 to 10 V DC 

501

2000 to 

+

10000 

1 to 5 V DC 

601

(Factory set value: 0.0 to 100.0 %) 

0 to 20 mA DC

701

Decimal point position can be changed

4 to 20 mA DC

801

 

 

 

 
 

Содержание V-TIO-P

Страница 1: ...nals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel All precautions described in this manual should be taken to avoid damage to the instrument or equipment All wiring must be in accordance with local codes and regulations All wiring must be completed before power is turned on to prevent electric shock instrument failure or incorrect action The power mu...

Страница 2: ...dule for Ethernet heat control Q Module for Ethernet heat cool control 2 Control action Each channel common code For heat control F PID action with autotuning AT reverse action D PID action with autotuning AT direct action For heat cool control B Heat cool PID action with autotuning AT air cooling W Heat cool PID action with autotuning AT water cooling 3 Input range Each channel common code Thermo...

Страница 3: ...office or the agent 3 PARTS DESCRIPTION Terminal cover Indication lamps 1 Address setting switch Terminal cover Indication lamps 2 Event connector Ethernet communication side Temperature control side FAIL RUN RX TX EVENT1 EVENT2 EVENT3 EVENT4 5 4 3 2 1 0 9 8 7 6 5 5 4 3 2 1 0 9 8 7 6 5 Modular connector for Ethernet RJ 45 Indication lamp 3 Indication lamp 4 FAIL RUN RX TX EVENT1 EVENT2 EVENT3 EVEN...

Страница 4: ...e this one The communication speed sets the same value as a temperature control side DIP switch 3 setting Temperature control side setting Set the communication speed and data bit configuration for internal communication by using the DIP switch 3 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 7 8 ON DIP switch 3 Right side ON OFF Terminal base Module mainframe 1 2 Communication speed OFF OFF Don t set this one ON...

Страница 5: ...with the event connector but the same also when not provided with the connector Depth in connector mounting Conduct installation in consideration of the sizes of the connector and cable when connector connected 110 Usage example of SRVP 01 Unit mm Approx 50 Connector plug SRVP 01 sold separately 5 3 DIN rail Mounting Mounting procedures 1 Pull down the mounting bracket at the bottom of the module ...

Страница 6: ... RTD input use low resistance lead wire with no difference in resistance between the three lead wires To avoid noise induction keep input signal wire away from instrument power line load lines and power lines of other electric equipment If there is electrical noise in the vicinity of the instrument that could affect operation use a noise filter Shorten the distance between the twisted power supply...

Страница 7: ...ptional This is a connector installed in the V TIO P V TIO Q module only when provided with the event input DI or the event output DO 1 6 Event connector socket Circuit configuration 24 V DC 1 2 3 DI 4 5 6 Load DO1 DO2 Load Attention in Connector plug Wiring Use the following connector plug as that connected to the event input output connector Connector plug is sold separately SRVP 01 Front screw ...

Страница 8: ...action is selectable Specify when ordering Heat cool control is selectable Specify when ordering Additional function Autotuning function Events Number of events 2 points channel Event type Temperature event Deviation high Deviation low Deviation high low Band Process high Process low Heater break alarm Control loop break alarm Burnout Temperature rise completion Option Event input DI Number of inp...

Отзывы: