RKC INSTRUMENT THW-3 Series Скачать руководство пользователя страница 3

100

0

100

80

60

40

20

0

100

80

60

40

20

0

25

50

75

Standard Functions 

Optional Functions 

 This function limits the highest output for the period of a 
preset time after power-ON and control mode change from 
Stop to Run. It makes the THW Series suitable for heaters 
which cause rush current flow, such as Halogen lamp, 
Tungsten, Platinum, and Molybdenum heaters. 

Output limiter High at start-up

100

80

60

40

20

0

High limiter at 
the time of start

100

0

100

80

60

40

20

0

25

50

75

The contact input can be configured to Run/Stop, 
Auto/Manual or alarm interlock reset. The alarm types 
are reverse phase detection, power frequency 
abnormal, and FAIL. Alarm output will go on, when any 
of them goes in alarm status. Optional heater break 
alarm and over-current alarm can be also configured as 
an output (alarm logic selection).

16mA

20mA

8mA

12mA

Input signal

100

80

60

40

50

20

0

100

80

60

40

20

0

Input signal

Input signal

100

80

60

40

20

0

Output current (%)

Output current (%)

16mA

12mA

8mA

20mA

This function maintains the output current constant when a 
load or a power supply fluctuates.  It makes the THW 
Series suitable for heaters of which resistance greatly 
changes by temperature change, such as Platinum, 
Molybdenum, Tungsten, and Tantalum heaters.

This function controls the output to make its effective value 
power proportional to the input. It makes the THW Series 
suitable for heaters of which resistance gradually 
increases by temperature or time, such as silicon carbide 
type heater.
This function controls its effective value power at 50% of 
the rating shown in the diagram below.

100

25

50

75

0

Load

(%)

100

80

60

40

20

0

Limiter set value

30%

60%

100%

Constant current control

Constant power control

Constant voltage control

0

20

40 50 60

80

100

20mA

16mA
12mA

8mA
5mA

300%

200%

100%

0

60%

Soft start

Soft start

100

25

50

75

0

 The relation between the setting input and the output 
voltage can be set. Gradient setting is possible via front 
keys or an external setter. Control characteristics may 
vary with the setting as follows.

Gradient setting output characteristic diagram

 Gradient setting

Input signal (%)

1. Auto setting input X Internal gradient setting X External gradient setting
2. Auto setting input X Internal gradient setting
3. Manual setting X Internal gradient setting X External gradient setting

Output
voltage
  (%)

Gradient

setting

 Even if setting input changes abruptly, output changes 
slowly to suppress inrush current. Ramp-up (Start-up) and 
ramp down (Start-Down) time can be set in the range of 0.1 
to 99.9 sec via front keys.

Time

Soft-start
time

Soft-down
time

100%

Time

Ramp function (Soft-start & Soft-down) 

Output
voltage
  (%)

Input 
signal

Soft-start & Soft-down action diagram

When phase control is selected for linear load (R: resistor), 
output mode can be selected among Proportional phase 
angle to input, proportional voltage to input, and 
proportional square voltage (electric power) to input.

Three types of output modes

100

50

0

4

12

20

4

12

20

4

12

20

100

50

0

100

50

0

Input signal (mA)

Input signal (mA)

Input signal (mA)

Proportional phase 

angle to input

Proportional 

voltage to input

Proportional square

voltage (electric power)

to input

* Default setting is proportional square voltage to input.

Phase 

angle

(%)

(%)

(%)

Effective

voltage

Electric

power

Output highest and lowest values can be set via front 
keys.

Output limiter (High & Low)

100

0

100

80

60

40

20

0

80%

80%

25

50

75

High limiter

High limiter

10%

Low limiter

Input signal (%)

Output
voltage
  (%)

Output
voltage
  (%)

High & Low limiter characteristic diagram

Output bias can be set via front keys.
(Base-up setting is valid when output limiter low is set to 
0.0)

Input signal (%)

 Base-up setting (Output bias)

Base-up 
setting : 20%

Output

voltage

  (%)

Output
voltage
  (%)

Output
voltage
  (%)

Output
voltage
  (%)

Base-up output characteristic diagram

 This function measures load current and compares it with 
a heater break alarm set value. Alarm will be activated if 
the load current goes into alarm ranges.  UP to two alarm 
set points can be set for the heater break alarm, which 
could be used for heater-deterioration alarm and heater-
break alarm.

Heater break alarm

Fuse break alarm

Over-current alarm

(Note) For phase control alarm does not work when the load
           current is less than 15% of maximum load current.

 This function limits the load current value to the heater. 
The setting range is 30 to 100% of the rated current.

Load current limiter

(Note) If the load has a large inrush current, use soft-start function
          along with this function to suppress the inrush current. 
          This function alone can not prevent the inrush current. 

(For phase control
 only)

(For phase control
 only)

(For phase control
 only)

Current limiter characteristic diagram

Output

current

 The alarm goes on when the load current exceeds 120%
of the rated current.

High limiter output
at the time of start

 Event input and alarm function

Constant current control characteristic diagram

Constant power control characteristic diagram

Output current (%)

Constant voltage control characteristic diagram

 This function maintains the output voltage constant when 
a load or a power supply fluctuates.

(For phase control
 only)

The alarm goes on when a fast blown fuse is blown. The 
fuse with alarm output function must be used for this 
function.

Содержание THW-3 Series

Страница 1: ...Three Phase Thyristor Unit Power Controller R THW 3SERIES...

Страница 2: ...when the supply voltage is at 0V This system suppresses high frequency noise inherent to phase control Supply voltage is switched on and off according to the voltage pulse or contact signals from a c...

Страница 3: ...of 0 1 to 99 9 sec via front keys Time Soft start time Soft down time 100 Time Ramp function Soft start Soft down Output voltage Input signal Soft start Soft down action diagram When phase control is...

Страница 4: ...ont key Manual setting 0 0 to 100 Front key or external setting unit Output setting range Output mode When phase control is selected for linearity load R resistor output mode can be selected from Prop...

Страница 5: ...100A AC 0 to 5V DC 0 to 10V DC 1 to 5V DC 0 to 20mA DC 4 to 20mA DC Standard Proportional phase angle Proportional voltage Proportional square voltage Standard Constant voltage control Standard Const...

Страница 6: ...g pitch 314 200 183 Mounting pitch 203 When multiple units are installed space between units must satisfy the rules shown in the drawing below 100 or more ELECTRIC HAZARD HIGH TEMPERATURE INDICATION L...

Страница 7: ...T2 6 T3 U V W NFB L1 L2 L3 3 2 1 7 1 8 2 9 3 Step down transformer 400V type only Power supply terminal Only 400V Type 400V type only 7 1 8 2 9 3 The phases of the power supply wirings R S T must mat...

Страница 8: ...is supplied Please refer to the following codes to order accessories Model code Name Setter Model Code Name Model Code Name Model Code Name Model Code Connector plug Voltage down transformer Terminal...

Отзывы: