2.3  Connection to Ethernet 

 

Pin layout of connector 

 

Pin layout 

Modular connector

for Ethernet

RJ-45

1

 

8

 

 

 

Pin No. 

Signal name 

Symbol 

1 Send 

data 

 TX

 

2 Send 

data 

 TX

 

3 Receive 

data 

 RX

 

4 Unused 

 

5 Unused 

 

6 Receive 

data 

 RX

 

7 Unused 

 

8 Unused 

 

 

The cable must be provided by the customer. 
Used cable: 

The cable is based on the 10BASE-T or the 
100BASE-TX standard of Ethernet. 

Used connector:  RJ-45 type

 

 

 
 

 

Wiring example 

 

When directly connected to client 

Use a cross cable when directly connected to the client (such as computer). 

 

TX

TX

RX

RX

TX

 

TX

 

 

RX

 

RX

 

Computer 

COM-JL 

Cross cable 

 

 

 

When use network hub 

Use straight cables when connected to the network hub. 

 

Network hub 

TX

TX

RX

RX

TX

 

TX

 

 

RX

 

RX

 

TX

TX

RX

RX

TX

 

TX

 

 

RX

 

RX

 

Computer 

COM-JL 

Straight cable 

Straight cable 

 

 

Cross cables may be used depending on the connecting device used. 
Therefore, follow the instructions for the respective device. 

 

 

2.4  Connection to the Controllers 

Conduct wiring between the COM-JL and controller (SRZ) as shown in the following.

 

 

 

Connection diagram 

 

RS-485 

Paired 

wire 

Shielded twisted 

pair wire

 

Controller (SRZ) 

Up to 16 Z-TIO modules can be connected.

R2 

R2: Termination resistor for external   
 connection 

(120 

 1/2 

W) 

3

4

5 SG 

COM-JL 

SG

R1 

Terminal block 

T/R (A)

T/R (B)

3

4

5 SG 

T/R (B)

T/R (A)

T/R (B)

T/R (A)

Z-TIO module

Z-TIO module 

The maximum number of SRZ modules (including other function modules) on the same 
communication line is 31. 

Connected by   
the internal 
communication 
line 

R1: Internal termination resistor   
 (Example: 

120 

 1/2 

W) 

 

 

  The cable must be provided by the customer. 

 

The termination resistor existing within the COM-JL can be connected or 
disconnected by the switch. (Factory set value: Termination resistor connected) 

 

 

2.5 System Configuration Example 

 

When directly connected to client 

 

Power supply (24 V DC) 

Ethernet 

Computer 

(Client) 

Ethernet 

[Modbus/TCP] 

communication 

converter COM-JL 

(Server) 

Controller 

communication 

(RS-485: Modbus) 

SRZ unit 

16 17

30 31

Internal communication line (RS-485)

Z-DIO module 

Module 
(Controller) 
address 

Z-TIO module 

 

 

 

When use network hub 

 

Ethernet 

Network hub 

Ethernet 

Power supply (24 V DC) 

Computer 

(Client) 

Ethernet 

[Modbus/TCP] 

communication 

converter COM-JL 

(Server) 

Controller 

communication 

(RS-485: Modbus) 

SRZ unit 

16 17

30 31

Internal communication line (RS-485)

Z-DIO module 

Module 
(Controller) 
address 

Z-TIO module 

 

The data request side (such as computer) is called “client” and the data 
response (supply) side (COM-JL) is called “server.” 

 

Basically, one client corresponds to one server (COM-JL) (i.e. one to one). 
However, one client can communicate with two or more servers depending 
on the program on the client side, but two or more clients cannot 
communicate with one server. 

3. SPECIFICATIONS 

 

Ethernet communication 

Physical layer: 

Ethernet 

 

10BASE-T/100BASE-TX automatic recognition 

Application layer: 

Modbus/TCP 

Communication data: 

Based on Modbus message format 

Connector type: 

RJ-45 

 

 

Controller communication 

Interface: 

Based on RS-485, EIA standard 

Protocol: Modbus-RTU 
Communication speed:  9600 bps, 19200 bps, 38400 bps 
Data bit configuration: 

Data 8-bit, Without parity, Stop 1-bit 

Maximum connections:  31 controllers * (SRZ modules) 

*  A combined total of up to 31 Z-TIO and Z-DIO modules can be 

connected in the SRZ. 
However, the maximum joinable number of functional modules of the 
same type is 16. 

 

 

General specifications 

Power supply voltage: 

24 V DC 

Power supply voltage range: 
 

21.6 to 26.4 V DC 

Current consumption: 

110 mA max. 

Allowable ambient temperature: 

10 to 

50 

Allowable ambient humidity: 

5 to 95 %RH 
(Absolute humidity: MAX.W.C 29.3 g/m

3

 dry air at 101.3 kPa) 

Installation environment conditions: 

Indoor use   
Altitude up to 2000 m 

Weight: 

Approx. 180 g 

 

 

Standard 

Safety standard: 

UL: 

UL61010-1 

cUL: CAN/CSA-C22.2 

No.61010-1 

CE marking: 

LVD:  EN61010-1 
EMC: EN61326-1 

RCM:  

EN55011 

 
 

4. MODEL CODE 

 

COM- JL - 1    02 

(1) (2) 

 

(1) Communication type 

1: Modbus/TCP 

(2) Corresponding to the RKC controller 

02: SRZ 

 

 

 

*

 

 

 