Personnel:
n
Qualified electrician
Protective equipment:
n
Protective clothing
n
Safety shoes
Prerequisite:
n
The mains cable is disconnected from the voltage supply.
1.
Connect the exposed wires of the control BUS cable to the
terminals (Fig. 27/ ) of the IO interface module in accord-
ance with the following table:
Terminal Wire
colour
Function
9
Yellow
Control BUS RS485 A
10
Green
Control BUS RS485 B
11
Pink
Logic V+ voltage supply
9
-
15 VDC, max. 40 mA
12
Brown
Logic GND voltage supply
2.
Connect the control BUS cable (Fig. 28/1) to the hand switch
interface HS.
ð
The IO interface module has been connected.
Connecting the IO interface module
Fig. 27: Connecting the control BUS
cable (terminals)
Fig. 28: Connecting the control BUS
cable (control unit)
Assembly
Connecting the accessories > Connecting the IO interface module