background image

 

7

WATER CONSIDERATION 

 

WATER CONDITIONING - 

Every new system will have certain harmful substances which remain in the boiler and piping 

after construction. It is com to find oils, weld slag, and other contaminates within the system. If the foreign materials 
remain, the boiler could be affected by loss of heat transfer on heat exchanger surfaces and/or an acidic water condition. 
Boiler life may be reduced as a result of an unclean system.

 

 
A water treatment company will be able to recommend a chemical cleaning or boil-out procedure. 
 

CHEMICAL TREATMENT - 

It is recommended that chemical treatment be provided for initial fill of the system. 

Generally, chemicals will be required to prevent scale formation, promote elimination of dissolved gases and control pH.

 

 
Most hot water boilers operate in a closed system and are considered to require little attention for water treatment. 
Experience has shown, however, few systems can be considered completely closed. Loss of water can occur from 
pump packing, glands, air venting devices, and threaded or flanged pipe connections. A means must be provided to 
chemically treat the raw water make-up. This is generally accomplished through the use of a shot-type chemical feeder. 
Consult a water treatment company for details. 
 

MAKE-UP WATER - 

It is generally accepted in system design that hat water boilers are in a closed system and, 

therefore, no make-up water is needed. This is not always the case. Untreated make-up water is a leading cause for 
failures of hat water boilers.  Provisions must be made for properly introducing, metering, and treating make-up water. 
Below are some considerations.

 

 

Provision should be made for removal of air from the make-up water. 

 

It is recommended that make-up water be tempered so as not to introduce cold water to the system. 

  A raw water meter should be used to identify the amount of water used by the system. This may indicate a 

potential problem with the system. 

 

ETHYLENE GLYCOL AS HEAT TRANSFER MEDIUM - 

On application requiring freeze protection, a mixture of 

ethylene glycol and water is commonly used.

 

 
When using ethylene glycol certain design limitations are important, due to the characteristics of the fluid verses water. 
These characteristics are: Elevated saturation temperature, and increased viscosity and density. In addition, ethylene 
glycol degrades when it is heated above the manufacturer’s specified maximum film temperature. 
 
The following design parameters must be followed when operating EMBLEM

®

 

with ethylene glycol:  

 

The maximum concentration should be 50%. 

 

Maximum temperature 200°F. 

 

Minimum operating pressure 50 psig. 

 

A means of monitoring the condition of the system fluid should be provided. Frequent analysis of the system 
should be conducted in the first few month of operation. Simi-annual checks thereafter are recommended. 

  Excessive use of inhibitors can create precipitation of solids causing reduce circulation and reduced heat 

transfer. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

 

Riverside Hydronics

®

, LLC  -  990 Haltom Road  -  Fort Worth, Texas  76117  -  Tel 1-800-990-5918

 

LEAD/LAG SYSTEMS 

Содержание Emblem

Страница 1: ...structions must be given to the equipment user or left near the appliance Refer to I M documents 34 50 34 501 and 34 502 for additional important information SPECIAL INSTRUCTIONS TO THE OWNER Retain t...

Страница 2: ...res are high the EMBLEM system engages a non condensing boiler to supplement heat output Although non condensing the secondary boiler in the EMBLEM system still operates at relatively high efficiency...

Страница 3: ...n from the system water to be heated to the Inlet of the EPV boiler Connect the Outlet to the supply side of the system hot water out of the unit FILLING THE UNIT 1 Fill the system with water To be su...

Страница 4: ...1 St1 parameter is the first to be displayed Press the Set key again and adjustment is enabled Use the arrow keys to adjust the set point 1 to the desired system temperature and press the set key agai...

Страница 5: ...the inherent flexibility of the EMBLEM system The Primary Only System is generally not applied with modern PRIMERA boiler systems due to the need to maintain a constant flow rate through the boiler Th...

Страница 6: ...6 Riverside Hydronics LLC 990 Haltom Road Fort Worth Texas 76117 Tel 1 800 990 5918...

Страница 7: ...t always the case Untreated make up water is a leading cause for failures of hat water boilers Provisions must be made for properly introducing metering and treating make up water Below are some consi...

Страница 8: ...he E series parameters are divided into 10 minute increments The E1 parameter is Sunday The S series parameters are the ending point for the programmed shift in set point The S series parameters are d...

Страница 9: ...1 160 E2 0 0 S2 6 0 Sb2 25 LEAD LAG CONTROL OPTION 2 The lead lag and outdoor reset function is managed by a third party Boiler Management System BMS or building Energy Management System EMS This mann...

Страница 10: ...ata Function Code Code of the desired function 0X06 Register Address The address of the first register to be read Set point 1 St1 has a register address of 768 Data The data to write CRC Defines the C...

Отзывы: