heated during defrosting time by means of a silicon heater (optional) of about 100W placed inside it .
Drawing 3
(*) Note: Only for RS….B and RS….BED models
7.
ELECTRICAL INSTALLATION
The wiring must be carried out by qualified personnel having the necessary technical requirements
asked for by the country where the machine is to be installed.
•
Provide for proper protection systems on the power supply line and check that the voltage
corresponds to that quoted on the label placed on the unit ( allowed tolerance ± 10% of the
rated tension).
•
The law requires that the unit is earthed: therefore it is necessary to connect it to an efficient
earthing equipment. No liability whatsoever can be accepted if the above instruction requirement
is not complied with or if the electrical plant to which the unit is to be connected is not made by
following the law in force.
•
For evaporators equipped with defrosting heaters, it is necessary to install a mechanical thermostat
(set to 40°C), which will disable the heaters in the event of excess temperature. The thermostat
bulb should be positioned in the fin coil, in the highest point of the evaporator.
Casing
Conveyor
Coil
Drip tray (*)
Defrosting
heaters only
for BED
model
E
E
C
B
F
C
B
A
A
G
G