Mod:

 

AN203T-2F

Production code:

 

FAL016G012-DI

0

6

/

2022

Содержание RIVC000001

Страница 1: ...Mod AN203T 2F Production code FAL016G012 DI 06 2022 ...

Страница 2: ...RIVC000001 REV 00 11 10 10 UK RIVC000001 USE AND MAINTENANCE HANDBOOK ...

Страница 3: ... is in progress LIT A serious alarm is in progress and alarm relay activated BLINKING A non serious alarm is in progress or a serious alarm has been silenced alarm relay deactivated SETPOINT key SETPOINT REDUCED SET green LED LIT The setpoint is displayed BLINKING The reduced set is activated ENTER key This is used to set the setpoint to access the programming menu and to view the machine status i...

Страница 4: ...ations are only to be carried out by qualified staff Parameters are not only divided by function they are also divided according to their security accessibility levels Level 0 Setpoint parameters direct access see paragraph 7 3 Level 1 frequently used parameters access without password see paragraph 7 5 Level 2 configuration parameters access with password see paragraph 7 7 Parameters can be varie...

Страница 5: ...time The time starting from the moment of deactivation for which it is not possible to restart the compressor 0 60 min dbi 1 Delay between switch on times The time starting from the moment of previous activation for which the compressor cannot be restarted 0 60 min OdO 1 Outputs delay at power on compressor fans defrosting This is used to delay the enabling of adjustments after the instrument has ...

Страница 6: ...fter a high or low temperature alarm condition 1 0 90 0 C F HAL 1 Maximum alarm threshold Above this value absolute or referred to the setpoint an alarm is triggered If the reference is relative the unmarked value is added to the setpoint 50 0 199 0 C F LAL 1 Minimum alarm threshold Below this value absolute or referred to the setpoint an alarm is triggered If the reference is relative the unmarke...

Страница 7: ...mperature above which defrosting is ended If at the start of a defrosting cycle the temperature is greater than that set no defrosting will be carried out In the event of a probe 2 malfunction the defrosting cycle will in any case terminate after reaching a time limit 50 0 199 0 C F Note To release the keypad hold down SET and ON OFF together for at least 5 seconds Note The LAn network parameter o...

Страница 8: ...ng element Application 5 5 C 25 15 C 2 10 C 5 5 C 25 15 C Menu Code no CPP 1 CPP 2 CPP 3 CPP 4 CPP 5 REG SEt 2 0 18 0 5 0 2 0 18 0 REG diF 2 0 2 0 2 0 2 0 2 0 REG HSE 5 0 15 0 10 0 5 0 15 0 REG LSE 5 0 25 0 2 0 5 0 25 0 DEF dtY 1 1 0 0 0 DEF dEt 15 15 15 30 30 DEF dSt 10 0 15 0 10 0 15 0 15 0 Fan FSt 8 0 5 0 50 0 8 0 5 0 Fan Fdt 1 2 0 1 2 Fan dt 2 2 0 2 2 Fan dFd 1 1 0 1 1 Follow the instructions ...

Страница 9: ...tch alarm adjustment is disabled permanently yes yes at switch on LO low temperature alarm yes yes automatic when the condition ceases HI high temperature alarm yes yes automatic when the condition ceases EE data saving alarm default parameters are loaded yes yes at power on or after the parameter has been stored to memory Ec condenser cleaning alarm blink no automatic when the condition ceases Er...

Страница 10: ...ly there is an EMERGENCY SYSTEM that can be used to maintain the unit in operation until it can be replaced To use this system proceed as follows 1 Cut off power to the Blocksystem 2 Remove all jumpers between the L terminals and the common contacts of the card relays terminals 25 28 33 36 38 3 As shown in the diagram connect a thermostat between the L terminal the NO terminals terminals 32 37 and...