INSTALLATION
Installation Instructions for SIS Bus Bar Systems A2MS001EN revision R05
52 / 130
Fig. 28: Preparing the indoor connection
sleeve
3.
Position the threads as the desired earthing
conductor requires it (possible in 60° steps) (Fig. 27).
4.
When positioning, make sure that the large
bevels on the inner radius of the flanges (Fig. 28/1 and
2) each face the O-ring (Fig. 28/3)
The connection sleeve will be secured and sealed off
later by squeezing the O-ring (Fig. 28/3) by a defined
amount.
4.7.1.1.2
PREPARING THE
CONNECTION SLEEVE
Personnel:
Installation staff
Protective Equipment:
Occupational safety clothing
Industrial safety helmet
Protective gloves
Safety footwear
Safety goggles
Materials:
Acetone
Lint-free rag or paper towel
NOTICE!
Risk of Material Damage due to Improper
Cleaning!
Dust or metal particles in the connection sleeves can
cause flashovers. This can compromise safe operation
of the overall system.
The lettering on the rating plates is not resistant to sol-
vents. Contact with acetone or similar substances can
cause the lettering to smear.
– Clean all components properly before
installation.
– Do not clean the rating plates on the
connection sleeve with acetone or similar
substances. Only use a lint-free rag for
cleaning the rating plates.