4
GB
Notes
Enclosure heaters with fans
Model No. SK 110 V
3105.210
3105.220
3105.230
Model No. SK 230 V
3105.180
3105.190
3105.200
Dimensions mm
W
H
D
142
170
101
142
170
101
142
170
101
Rated operating voltage Volt, Hz
110 or 240 V AC/DC, 3-pole
Continuous thermal output
at T
u
= 10°C
250 W
1)
400
W
1)
800
W
1)
Pre-fuse gG for 110 V
4 A
6 A
10 A
Pre-fuse gG for 230 V
4 A
6 A
6 A
1)
Output with fan.
Special voltages available on request. We reserve the right to make technical modifications.
Enclosure heaters without fans
Model No. SK
3105.110
3106.120
3115.130
3116.140
3107.150
3107.160
3102.170
Dimensions mm
W
H
D
81
123
49
81
164
49
102
150
60
102
225
60
102
260
60
140
205
80
140
250
80
Rated operating voltage
Volt, Hz
110 – 240 V AC/DC, 2-pole
Continuous thermal
output at T
u
= 10°C
10 W
20 W
30 W
50 W
75 W
100 W
150 W
Pre-fuse T
2 A
4 A
1. Technical Data
2. Mounting
The panel heater is fitted vertically, i.e. with
the connection terminal or fan facing down-
wards. To permit the required convection, a
gap of at least 100 mm must be left above
and below the heater. In the case of heaters
with fans, a safety clearance of min. 300 mm
to any component installed above must be
observed (thermal safety clearance to adja-
cent components at least 35 mm). If these
clearances are observed, the ambient tem-
perature does not rise above 65°C.
2.1 Screw fastening onto the mounting plate
(Fig. 2.4).
2.2 Snap-type fastening onto a 35 mm
support rail DIN EN 50 022
(Fig. 2.3/Fig. 2.5).
It is furthermore to be ensured that the heater
and connection cables are mounted firmly
and securely.
Electric cables must not touch the body of the
heater fan and must not be routed directly
past the hot air outlet. The heater must
not be mounted in the vicinity of flammable
materials.
Rittal enclosure heater assembly instructions