By removing the suction pipe, damage (e.g. a crack) to the suction pipe is simulated.
The message
“Failure (too high) air flow”
should now appear in the display.
Remount the suction pipe after checking the air flow. The message
“Failure (too
high) air flow”
is reset automatically.
6.2.8.2
Door contact switch
By opening a door to the protected cabinet which is equipped with a door contact
switch, the message
“Blocking by door cont.”
is generated and the yellow LEDs
By removing the door contact plug on the
rear side of the system, the door contact
switch is deactivated. The message
“Failure door contact”
is also shown in the
display.
Remount the door contact switch and acti-
vate the system using the upper
[Reset]
The check must be performed for each of the door contact switches that are
installed.
NOTICE
Faulty release due to removal of the blocking!
Premature removal of the blocking can result in a faulty release and thereby cause
property damage.
● Do not stop blocking the system until there are no red LEDs lit up and there is
no fire alarm shown in the display.
6.2.8.3
Manual call point
L
CAUTION
Danger of injury from faulty release!
Checking the manual call point when the system is not blocked can result in a faulty
release. A faulty release may cause injuries and significant property damage.
● Block the system prior to checking the manual call point. To this end, switch the
blocking switch on the back of the system to the
Ⅱ
"Agent disconnect [blocked]"
position.
Ⅰ
Agent connect [not blocked]
Ⅱ
Agent disconnect [blocked]
Fig. 40: LEDs and [Reset] button
Fig. 41: Blocking switch
Assembly and installation
Operating Instructions / DET-AC III Master / 916005 / 11-2022 / en_US
49