11.3.2
Removal
Required tools:
● Slotted screwdriver (size 3.0) for wire reed contact under terminal
● Torx screwdriver (size 10) for cover screws
● Socket wrench 5.5 mm
● 8 mm (flat) spanner for the earthing screws
● Stable storage area
INFORMATION
Only use suitable tools when changing the tank.
1.
L
WARNING! Danger of a faulty release!
To block the system: Switch the blocking switch (Fig. 86/arrow) to "Agent dis-
Ⅱ
).
2.
L
WARNING! Danger due to high voltage!
Remove the mains lead.
3.
Disconnect all connection lines from the system.
4.
Actuate the battery button "Battery OFF" (Fig. 87/1).
5.
Disconnect the suction pipe from the system (Fig. 88).
Fig. 86: Blocking switch (on the rear of
the system)
Fig. 87: Battery button
Fig. 88: Suction pipe