Technical Specifications
UPS-Manual
29
EN
Protection
(AC Mode )
<105% continuous
>106% ~ 120% for 30 seconds transfer to bypass
>121% ~ 150% for 10 seconds transfer to bypass
>150% for immediately transfer to bypass
Buzzer continuously alarms.
(Battery Mode)
<105% continuous
>106% ~ 120% for 30 seconds shuts down
>121% ~ 150% for 10 seconds shuts down
>150% for immediately shuts down
Buzzer continuously alarms.
Overload
(Bypass Mode)
<105% continuous
>106% ~ 120% for 250 seconds shuts down
>121% ~ 130% for 125 seconds shuts down
>131% ~ 135% for 50 seconds shuts down
>136% ~ 145% for 20 seconds shuts down
>146% ~ 148% for 5 seconds shuts down
>149% ~ 157% for 2 seconds shuts down
>158% ~ 176% for 1 seconds shuts down
>177% ~ 187% for 0,32 seconds shuts down
>188% for 0,16 seconds shuts down
Buzzer continuously alarms.
Short Circuit
Bypass mode : Input Fuse/Input Breaker
Normal Mode: Output Breaker/Electronic Circuit
Battery Mode: Output Breaker/Electronic Circuit
Battery ABDM
EPO
UPS shuts down immediately
Normal Mode
Transfer to Bypass Mode
Over
Temperature
Battery Mode
UPS shuts down immediately
Audible Alarm
Battery Mode
Sounding once every 1,5 seconds
Low Battery
Sounding once every 0,2 seconds
Overload
Sounding once every 3 second
Fault
Continuously Sounding (or Sounding once every 3 second)
Physical
Dimensions mm (HxWxD)
PMC12 Standard Design
88(2U)x440x 650
88.8(2U)x440x 650
Dimensions mm (HxWxD)
PMC12 compact Design
88(2U)x440x405
176(4U)x440x420
176(4U)x440x420
Weights
15,7kg (34,5Ib)
29,4kg (64,7Ib) 29,7kg
(65,3Ib)
Input Connection
10A, IEC 320-C14
10A, IEC 320-C14
16A, IEC 320-C20
Output Connection
230V
(6) 10A,IEC 320-C13
(4) 10A,IEC 320-C13
(1) 16A,IEC 320-C19