12
Rittal EC fan-and-filter unit assembly and operating instructions
Technical specifications
EN
Unit
Model No.
Fan-and-filter unit
RAL 7035
3244.500
3245.500
3245.510
3245.600*
Rated operating voltage
V
Hz
200 - 240, 1~,
50/60
200 - 240, 1~,
50/60
100 - 130, 1~,
50/60
200 - 240, 1~,
50/60
Rated current max.
A
0.7
1.33
2.1
1.33
Rated operating voltage
(active power)
W
80
165
165
165
Pre-fuse T
A
6
4
6
4
Dimensions
Width (B1) x height (H1)
mm
323 x 323
323 x 323
323 x 323
323 x 323
Required mounting cut-
out (B2 x H2)
mm
292 x 292
292 x 292
292 x 292
292 x 292
Depth (T1)
mm
25
25
25
25
Max. installation depth
(T2)
mm
130.5
130.5
130.5
130.5
Air throughput, unimped-
ed airflow with standard
chopped-fibre filter mat
m³/h
700
890
890
890
Air throughput, unimped-
ed airflow with pleated
filter
m³/h
855
1125
1125
1125
Air throughput with outlet
filter, including standard
chopped-fibre filter mat
m³/h
1 x 3243.200: 485
1 x 3243.200: 630
1 x 3243.200: 630
1 x 3243.200: 630
2 x 3243.200: 570
2 x 3243.200: 770
2 x 3243.200: 770
2 x 3243.200: 770
Air throughput with outlet
filter including pleated filter m³/h
1 x 3243.200: 700
1 x 3243.200: 930
1 x 3243.200: 930
1 x 3243.200: 930
2 x 3243.200: 800
2 x 3243.200:
1060
2 x 3243.200:
1060
2 x 3243.200:
1060
Control interface
(0 – 10 V/PWM input and
tacho signal output)
◾
◾
◾
◾
Fan
Diagonal/EC motor
Noise pressure level
dB (A)
64
72
72
72
Operating temperature
°C
-25…+55
-25…+55
-25…+55
-25…+55
Storage temperature
°C
-25…+70
-25…+70
-25…+70
-25…+70
Protection category (to
IEC 60 529)
IP54 standard
IP55 with pleated
filter
IP56 with hose-
proof hood
IP51 standard
IP52 with pleated filter
IP56 with hose-proof hood
Tab. 4:
Technical specifications
Technical modifications reserved.
* EMC version