Rittal fan-and-filter unit assembly and operating instructions
15
Cut-out/drilling dimensions
EN
11 Cut-out/drilling dimensions
H2
B2
H1
B1
T2
T1
Fig. 10: Cut-out dimensions
B = width; T= Depth
Fig. 11: Drilling pattern
Note:
The cut-out must be increased by 1 mm
each side for wall thickness above 2.5 mm
(see accompanying drilling template).
Model No.
B2 x H2 mm
T2 mm
3237.xxx
92 x 92
43
3238.xxx
124 x 124
58.5
3239.xxx
177 x 177
90
3240.xxx
224 x 224
107
3241.xxx
224 x 224
107
3243.xxx
292 x 292
118.5
3244.xxx
292 x 292
130.5
3245.xxx
292 x 292
130.5
Tab. 7:
Cut-out dimensions
Model No.
Ø mm
F mm
Nm
3237.xxx
3.5
100.5
1
3238.xxx
3.5
132.5
1
3239.xxx
4.5
185
1
3240.xxx
4.5
234
2
3241.xxx
4.5
234
2
3243.xxx
4.5
302
3
3244.xxx
4.5
302
3
3245.xxx
4.5
302
3
Tab. 8:
Drilling dimensions
12 EMC fan/outlet filter
To achieve EMC protection, the EMC fans and EMC
outlet filters should be snapped into the mounting
cut-out and screw-fastened using the screws supplied.
Next, the four contact foils should be stuck on all-
round between the fan-and-filter unit and the inside of
the enclosure as shown in the following illustration.