background image

Mounting 

 

 

5  Mounting 

 
Mounting, electrical connection and commissioning 
are only to be performed by trained service 
personnel. Adhere to all machinery-related 
requirements and specifications supplied by the 
system manufacturer or machine builder. Wear 
safety shoes and gloves for handling! 

 

The following applies for all cross flow fans: 

Do not install distorted. 

Housing or mounting bracket must be fixed 
flat on a level surface. 

Do not apply force (levering, bending). 

Standard horizontal installation. 

Depending on installation circumstances 
and application, the open motor (IP 10) will 
require protection against water spray and 
objects falling into it. 

If the motor installation is insulated (version 
with structure- borne noise decoupling 
using rubber elements), the fan housing 
must also be earthed where components 
under voltage are connected to it. 

The fan discharge must not be adversely 
affected with respect to flow engineering by 
installation of or attachments to the fan 
(e.g. shifting of housing edges, protruding 
seals). 

Connect fan only to electrical circuits that 
can be disconnected with an all-pole 
isolating switch. 

Electrical connection corresponding to 
wiring diagram on housing. 

Connect the temperature monitor to the 
tripping device and/or motor cut-out switch.

 

6  Electrical connection 

 

 

Must only be carried out by trained personnel 
(DIN EN 50 110, IEC 364). 

 

Connect fan only to electrical circuits that can 
be disconnected with an all-pole isolating 
switch. 

 

The motors have partly metal terminal box or 
partly screened connecting line (connection to 
EC-controller). 

 

Only use lines which can guarantee a 
permanent seal around the cable  glands 
(pressure-resistant, dimensionally-stable, 
round-centred jacket; e.g. by means of gusset 
filling)! 

 

Thermal contacts have to be connected. 

 

Attention

: Connection directly to the mains 

supply results in a damage of the motor. 
Electrical connections must not be short-

circuited since there is danger of de-
magnetization. 

 

Do not touch the connection ends of the 
motor when it has been switched off and is 
coming to a stop –  Electrical shock due to 
the effect of the generator.

 

7  Operating conditions 

 

 

Do not operate the fan in an explosive 
atmosphere. 

 

Switching frequency: 

The fan is rated for S1 continuous 
operation. 

Controls must not allow extreme switching 
operation. 

 

Ziehl-Abegg cross flow fans with integrated 
external rotor motor are, without restriction, 
suitable for operation with frequency inverters 
when the following points are observed: 

Between the inverter and the motor, 
sinusoidal  filters should be incorporated 
which are 

effective for all

 

phases 

(sinusoidal output voltage, phase against 
phase, phase against protective conductor) 
as offered by manufacturers. Please ask 
for our technical information L-TI-0510. 

du/dt  filters (also called motor or 
suppression  filters) cannot be used in 
place of sinusoidal filters. 

When using sinusoidal filters, screened 
motor leads, metal terminal boxes and a 
second earth connection to the motor can, 
if necessary, be omitted. Check-back by 
the supplier of the sinusoidal filter. 

 

If the operational leakage current exceeds 3.5 
mA, earthing in compliance with DIN EN 50 
178, art. 5.2.11.1 must be provided. 

 

Noise problems can be eliminated by using a 
sound attentuator. 

 

A-rated sound power levels of over 80 dB(A) 
are possible, see product catalogue. 

 

Corrosion is possible at the cutting edges on 
sendzimir galvanised parts. 

8  Start-up 

 

 

Before first-time start-up, check the following: 

Have installation and electrical connection 
been properly completed? 

Safety equipment is in place (

→  Contact 

protection). 

All leftover installation materials and other 
foreign materials have been removed from 
the fan cavity. 

Is the protective earth connected? 

Temperature monitor/motor protection 
switch are 

Содержание 3144.000

Страница 1: ...Tangential fans for 482 6 mm 19 Assembly and operating instructions 3144 000 3145 000 ...

Страница 2: ...cation 3 2 Safety instructions 3 3 Note on the ErP directive 3 4 Transport storage 3 5 Mounting 4 6 Electrical connection 4 7 Operating conditions 4 8 Start up 4 9 Maintenance repair 5 10 Cleaning 5 11 Disposal recycling 6 12 Dimensions 7 ...

Страница 3: ... motor circuit wiring diagram a tripping device is required For motors without a temperature monitor a motor cut out switch is to be used for P1 750 W P2 500 W Blocking or braking the fan by say pushing objects into it is forbidden This leads to heated surfaces and damage to the impeller It is not possible to exclude a residual risk due to incorrect use malfunction or force majeure The designer or...

Страница 4: ...d Attention Connection directly to the mains supply results in a damage of the motor Electrical connections must not be short circuited since there is danger of de magnetization Do not touch the connection ends of the motor when it has been switched off and is coming to a stop Electrical shock due to the effect of the generator 7 Operating conditions Do not operate the fan in an explosive atmosphe...

Страница 5: ...t of any other damage e g motor damage or damage to the fan cylinder please contact our Repair Department On 1 motors condenser rating can decrease with time Life expectancy approx 30 000 hrs per DIN EN 60252 Outdoor fans If a fan is stationary for long periods in a humid atmosphere it should be switched ON for minimum of two hours every month to remove any moisture that may have condensed within ...

Страница 6: ...e ventilator is running If water enters the motor Dry off the motor winding before using it again Replace motor ball bearings Wet cleaning under voltage may lead to an electric hock danger to life 11 Disposal recycling Our products are manufactured in compliance with valid international standards and regulations If you have any questions about how to use our products or if you are planning special...

Страница 7: ...Dimensions 12 Dimensions ...

Страница 8: ......

Отзывы: