Step 4. - CONNECTING THE GateGuard DECODER/RELAY BOARD TO YOUR DEVICE

1. Consult the manufacturer of the device you are attempting to control for the recommended wire gauge.

2. Confirm that your application will 

not

 exceed the maximum rating of the internal relay 

125 VAC @ 10 amps.

3. Make sure all equipment power is 

turned off or disconnected

.

4. Route all wires through the provided strain relief at the bottom of the Callbox enclosure and any additional strain

relief or conduit. If the XT Model is being used, also route the wires through the drilled or punched hole and any

additional strain relief or conduit.

5. Connect the wire pair between the 

GateGuard

 normally open relay contact outputs (refer to FIG.2) and the

contact closure inputs on the device you wish to control.

6. Tighten all strain reliefs and any conduit junctions to ensure moisture/vandal resistance.

Step 5. - CALLBOX RE-ASSEMBLE

 – 

Basic 

and

 XT

 Models RQX-150/156/450/456/454

Standard Model: RQX-150/156/450/456/454

1. Make sure power connectors between front and rear enclosures are connected.

2. Place front and rear enclosures together.

3. Tighten (4) large plastic screws.  NOTE:  

DO NOT

 

over-tighten, damage to screws may result.

4.

Basic

 model - Attach message placard to front enclosure by lining up the push-button in the hole in the

placard and matching up the (4) Velcro pads on the back of the placard.

4.

XT

 

model – Place metal plate on outer enclosure.

5.

XT

 model – Tighten (4) metal screws with 

Torx T-25

 Tamper-proof screw bit.

Basic Operation - Model GGT-1/1F DTMF DECODER

The RITRON OUTPOST Radio Callbox with 

GateGuard

 installed will operate as such;

After a call has been initiated by the OutPost radio callbox, a two-way conversation can be established between

the callbox and a portable two-way radio.  Likewise, personnel with a radio (portable, mobile or base station)

equipped with a DTMF keypad can transmit the access command code back to the OutPost callbox equipped

with a 

GateGuard

 decoder.  By transmitting the correct 

GateGuard

 access command code via the radio’s keypad,

the user can now achieve long range, wireless remote control to activate motors, gates, locks, lights and/or pumps.

When the 

GateGuard

 decodes the correct access command code, the relay contacts will close momentarily  (a

1/2-second) to control what has been connected to the relay contacts.  The OutPost radio callbox will then

automatically transmit a short  (1 second) “acknowledgement” tone back to the portable radio.  This  tone

acknowledgement in-turn alerts radio-equipped personnel that the OutPost callbox received and successfully

decoded the 

GateGuard

 access command code.

Note:

Acknowledgement Tone and Trunking Operation 

If 

GateGuard

 is used with a RITRON Model RQX-454/-XT

programmed for trunking mode through a repeater, the 1 second tone may be partially or entirely missed due to

Home  Channel  availability.

Ritron Quick Talk Wireless Voice Alarm Reporter Offers Wireless Remote Monitoring

If you would like to know that the desired “command” was 

actually performed

 e.g. “is the gate really moving?”,

then Ritron has the perfect wireless solution for you.  We recommend the Quick Talk Wireless Voice Alarm

Reporter.  The Quick Talk RQT-150/450/454 can be programmed to the radio system frequency and connected

to any switch i.e. a flex switch, magnetic reed switch, pressure plate etc.. in-turn this switch will be activated by

the actual opening/closing of the gate.  A corresponding voice message is then transmitted via radio to all radio-

equipped personnel, providing confirmation on the status of the gate. This useful wireless device can be used in

conjunction with existing two-way radios – conventional, repeaters and UHF trunking system and a wide variety

of available switches or sensors.

The 1-second “acknowledgement” tone generated by the GGT-1 equipped Outpost indicates that a correct

access command code has been received and properly decoded.  It does not confirm that the gate is actually

opening or closing; i.e.,  a damaged gate motor may not be operational.  Even though a 

GateGuard

 equipped

OutPost callbox receives and decodes the signal, and the relay output closes, the attached device (e.g., a gate

opener) may not be operational. A Quick Talk Voice Alarm Reporter along with a flex switch mounted in the path

of the gate will confirm via radio that the gate is actually moving. This added monitoring capability will also alert

radio-equipped personnel of “unauthorized” movement of the gate. Visit the Ritron web site at 

www.ritron.com

 or

call your dealer or Ritron at 

800-USA-1-USA

 (

800-872-1-872

) for more information on the Quick Talk Voice Alarm

Reporter.

Отзывы: