DATAFLOW RTU
11.1.4
CONNECTIONS
CONNECTOR
PIN
NAME
DESCRIPTION
Ext. Power/ Serial:
1
A
Serial Pair A
Jl 05 (X3_8 Y0-2)
2
B
Serial Pair B
3
GND
Loader Ground
4
LDR
Loader Connected/ Program Enable
5
GND
Power Ground
6
VI
Power In to Controller and Radio
7
B+
From Internal Battery
User Input/ Output:
1
Rll
Relay 1 Contact 1
JJO! (Xl.8 Y0.3)
2
Rl2
Relay 2 Contact 1
3
R21
Relay 1 Contact 2
4
R22
Relay 2 Contact 2
5
PWR
Power Out
6
GND
Power Out Ground
7
Sl
Input 1
8
GND
input 1 Ground
9
S2
Input 2
10
GND
Input 2 Ground
11
S3
Input 3
12
GND
Input 3 Ground
13
S4
Input 4
14
GND
Input 4 Ground
15
S5
Input 5/ Output 1
16
GND
Input 5/ Output l Ground
17
S6
Input 6/ Output 2
18
GND
Input 6/ Output 2 Ground
12. HARDWARE CONFIGURATION
12.1
The
DATAFLOW RTU
has six hardware configurable jumpers_ Jumper functions are described in the following
paragraphs 12. Ll to 12. 1.6. See Figure A2, page A-6, for location references_
12_1.l P.Tl0l (Y 2_8 - X 2-0): This jumper setting determines whether configurable I/0 1 is an input or an analog
output The jumper across pins 1 and 2 configures the pin to be an input_ The jumper across pins 2 and 3
configures the pin to be an output, the default setting. At the time of printing this manual, the
DATAFWW
RTU
firmware supports this pin to be used only as an output.
12.1.2 P,T102 (Y 2.8 - X 1.8): This jumper setting determines if configurable I/0 2 is an input or an analog output. The
jumper across pins l and 2 configures the pin to be an input. The jumper across pins 2 and 3 configures the pin
to be an output, the default setting. At the time of printing this manual, the
DATAFLOW RTU
firmware
supports this pin to be used only as an output.
12.1.3
PJ103
(Y 2.8 - X 1.6): This jumper setting determines how the configurable analog outputs 1 and 2 are
powered. The jumper setting is valid only if PJ!0l or PJ102 is set for output. The jumper across pins 2 and 3
configures the output to be powered by system power. The jumper across pins 1 and 2 configures the output to
be powered by regulated radio power, the default setting.
12_ 1.4
P.T104
(Y 2.9 - X 1.2): This jumper setting determines if configurable I/0 1 is set for voltage or current loop
analog output. This jumper setting is valid only if PJ!0l is set for output. With one jumper across pins 1 and 2
and another jumper across pins 3 and 4, the output is confi
gur
ed for voltage, the default setting. Only one
jumper across pins 2 and 3 configures the output for current loop.
( A-11 )
www.TwoWayRadioEquipment.com | (800) 878-7829 | [email protected]