Service Manual  23

Troubleshooting Guide 

Room Air Conditioner Voltage Limits

NAME PLATE RATING 

MINIMUM 

MAXIMUM 

115V ± 10%

103.5V 

126.5V 

COMPLAINT CAUSE 

REMEDY 

Fan motor will not run. 

No power 

Check voltage at outlet. Correct if none. 

Power supply cord 

Check voltage to rotary switch. If none, check 

power supply cord. Replace cord if circuit is 

open.

Rocker switch 

Check switch continuity. Refer to wiring diagram 

for terminal identification. Replace switch if 

defective. 

Wire disconnected or 

Connect wire. Refer to wiring diagram for 

connection loose

terminal identification. Repair or replace loose 

terminal.

Capacitor (Discharge 

Test capacitor. 

capacitor before testing.) 

Replace if not within ±10% of manufacturer's 

rating. Replace if shorted, open, or damaged. 

Will not rotate 

Fan blade hitting shroud or blower wheel hitting 

scroll. Re-align assembly. 

Units using slinger ring condenser fans must 

have 0.22~0.25 inch clearance to the base. 

If necessary, shim up the bottom of the fan motor 

with mounting screw(s). 

Check fan motor bearings; if motor shaft will not 

rotate, replace the motor. 

Fan motor runs. 

Revolves on overload

Check voltage. See limits on this page. 

If not within limits, call an electrician. 

Test capacitor. 

Check bearings. Does the fan blade rotate 

freely? 

If not, replace fan motor. 

Pay attention to any change from high speed to 

low speed. If the speed does not change, 

replace the motor. 

Содержание HW500CMY8

Страница 1: ...Room Air Conditioner SERVICE MANUAL MODELS HW500CMY8 CAUTION website http www lgservice com BEFORE SERVICING THE UNIT READ THE SAFETY PRECAUTIONS IN THIS MANUAL ONLY FOR AUTHORIZED SERVICE PERSONNEL ...

Страница 2: ...t Some Models 10 How to Secure the Drain Pipe 11 Operation 12 Features 12 Insulation Resistance Test 12 About the Controls on the Air conditioner 12 Disassembly 13 Mechanical Parts 13 Air Handling Parts 14 Electrical Parts 15 Refrigerating Cycle 16 Schematic Diagram 19 Wiring Diagram 19 Troubleshooting Guide 20 Piping System 20 Troubleshooting Guide 21 Room Air Conditioner Voltage Limits 23 Explod...

Страница 3: ...death or serious injury This symbol indicates the possibility of injury or damage to property only Be sure not to do Be sure to follow the instruction Gasolin WARNING Installation Always install the expansion panel s Improper assembly or installation may cause incorrect operation including injury fire and electric shock hazards Do not place the power cord near a heater It may cause fire and electr...

Страница 4: ...d length It will cause electric shock or fire Use the air conditioner on a single outlet circuit See page 7 Do not share the outlet with other appliances It will cause electric shock or fire Always plug into a grounded outlet No grounding may cause electric shock Unplug the unit if strange sounds odors or smoke come from it Otherwise it will cause fire and electric shock accident Do not use the so...

Страница 5: ...out of the window creating a safety hazard Close all doors windows and other outside openings to the room The air conditioner must be operated in a enclosed area to be most effective Ventilate before operating air conditioner when gas goes out It may cause explosion fire and burn Installation CAUTION Do not clean the air conditioner with water It will cause electric shock or failure of machine If ...

Страница 6: ...Operation without filters will cause failure Use a soft cloth to clean Do not use wax thinner or a strong detergent The appearance of the air conditioner may deteriorate change color or develop surface flaws Do not drink water drained from air conditioner Do not direct airflow at room occupants only It is not sanitary and could cause illness or personal injury hazard Be cautious not to touch the s...

Страница 7: ...83 11 1 8 D mm inch 326 12 13 16 Model Dimension All Model Outside Dimensions This symbol alerts you to the risk of electric shock This symbol alerts you to hazards that could cause harm to the air conditioner This symbol indicates special notes NOTICE Symbols Used in this Manual ...

Страница 8: ...ATING CURRENT AMP 4 8 REFRIGERANT CONTROL CAPILLARY TUBE REFRIGERANT CHARGE R 22 200g 7 0 Oz INSIDE FAN TURBO OUTSIDE FAN ROPELLER FAN WITH SLINGER RING AIR DISCHARGE 2 WAY RIGHT AND LEFT CHASSIS TOP DOWN PROTECTOR TEMPERATURE CONTROL THERMOSTAT ROCKER SWITCH 1 2 POSITIONS POWER ON POWER OFF ROCKER SWITCH 2 2 POSITIONS HI FAN LOW FAN FAN MOTOR 6 POLES OVERLOAD PROTECTOR FOR COMPRESSOR INTERNAL PRO...

Страница 9: ...IP MOUNTED ON TOP OF INNER SILL is more than 1 two of wood strip are not necessary NOTICE Installation Installation Select the Best Location How to Install This air conditioner is designed with a button down chassis so it can be easily installed in a window 1 To prevent vibration and noise make sure the unit is installed securely and firmly 2 Install the unit where the sun does not shine directly ...

Страница 10: ... with pencil on the center of the inner sill as shown in Figure 6 2 Attach L Bracket a Install the L brackets behind the inner window sill with the short side of bracket as shown Use the 2 screws TYPE A provided b The bracket helps to hold unit securely in place Be sure to place bracket edge flush against back of inner sill See Figure 7 HARDWARE TYPE F 1EA SASH SEAL Not adhesive backed TYPE E 1EA ...

Страница 11: ...ng 2 screws TYPE B 2 screws TYPE C to secure them as shown in Figure 10 5 Install the Sash Seal and Sash Lock a Cut the sash seal TYPE F to the window width Stuff the sash seal between the glass and the window to prevent air and insects from getting into the room as shown in Figure 10 b Fasten the L bracket using a TYPE A screw as shown in Figure 10 6 Window installation of room air conditioner is...

Страница 12: ... operation with cooling or not Normal Fan 1 Turn the FAN speed mode switch to the HI or the LOW setting 2 Set the thermostat control to the temperature mark Fan Only Normal cooling 1 Turn the FAN speed mode switch to the HI or the LOW setting 2 Set the thermostat control to the desire temperature the mid point is a good starting position If the room temperature is not satisfactory after a reasonab...

Страница 13: ...re 15 4 Lift the cabinet from the unit 5 Re install by referring to the procedures above 3 CONTROL PANEL 1 Disconnect the unit from the power source 2 Remove the front grille Refer to Section 1 3 Remove the cabinet Refer to Section 2 4 Remove 2 screws that secure the control panel to control box and base pan See Figure 16 5 Pull the control board toward yourself Controls wires and capacitor are no...

Страница 14: ... the control panel Refer to Section 3 5 Remove the air guide upper Refer to Section 4 6 Remove 2 screws that secure the condenser to the base pan 7 Remove the screw that secures the shroud to channel of condenser 8 Press the snap area of shroud with your thumbs This allows you to remove it from the condenser 9 Remove 1 screw that secure the evaporator to the base pan See Figure 19 10 Remove the or...

Страница 15: ...r Refer to Section 6 8 Remove 2 screws that secure the shroud to the base pan See Figure 23 9 Lift air guide lower and shroud upward See Figure 23 10 Re install by referring to the procedures above 8 OVERLOAD PROTECTOR 1 Remove the front grille and cabinet Refer to Section 1 2 2 Remove the nut which fastens the terminal cover 3 Remove the terminal cover 4 Remove all the leads from the overload pro...

Страница 16: ...ontrol board Refer to Section 3 3 Remove all the leads of the rotary switch terminals 4 Remove the rocker switch See Figure 28 5 Re install the components by referring to the removal procedure above 13 POWER CORD 1 Disconnect the unit from source of power 2 Remove the front grille Refer to Section 1 3 Remove the cabinet Refer to Section 2 4 Remove a screw that secures control panel to control box ...

Страница 17: ... few minutes then open slowly with the two full turns counter clockwise This will keep oil from foaming and being drawn into the vacuum pump 6 3 Operate the vacuum pump for 20 to 30 minutes until 600 micron vacuum is obtained Close valves A and B and observe vacuum gauge for a few minutes A rise in pressure would indicate a possible leak or moisture remaining in the system With valves A and B clos...

Страница 18: ...f making a vapor proof seal leak detector tubing cutter hand tools to remove components and service valve B A B A B A COMPOUND GAUGE SEE INSETS BELOW CAPILLARY TUBE EVAPORATOR LOW PRESSURE SIDE COMPRESSOR CONDENSER HIGH PRESSURE SIDE EXTERNAL VACUUM PUMP LO HI CHARGING CYLINDER MANIFOLD GAUGE C Figure 31A Pulling Vacuum Figure 31B Charging ...

Страница 19: ...L LO BK RD BK BK GN YL GL GN YL GL RD OR BR OR BR BK RD BL YL CAPACITOR F C H MOTOR COMP OLP THERMOSTAR YL 2 2 3 R S C 1 1 Ribbed MODEL HBLG5004 HBLG5004T4 DESCRIPTION NAME POWER CORD ASSY FAN MOTOR COMPRESSOR ROCKER SWITCH 1 ROCKER SWITCH 2 THERMOSTAT CAPACITOR OVERLOAD PROTECTOR Q TY 1 1 1 1 1 1 1 1 REF NO 1 2 3 4 5 6 7 8 ...

Страница 20: ...cycle COOLED AIR HOT DISCHARGED AIR MOTOR COMPRESSOR ROOM AIR HEAT LOAD CAPILLARY TUBE LIQUID REFRIGERANT LIQUID OUTLET VAPOR INLET COMPLETE LIQUID BOIL OFF POINT SUCTION LINE COOL LOW PRESSURE VAPOR LIQUID PRESSURE DROP DISCHARGE LINE NOT HIGH PRESSURE VAPOR OUTSIDE COOLING AIR FOR REFRIGERANT PASS THROUGH EVAPORATOR COILS CONDENSER COILS ROOM AIR CONDITIONER CYCLE OF REFRIGERATION HIGH PRESSURE ...

Страница 21: ...perature difference of inlet outlet air 44 50 F 7 10 C Replacement of unit if the unit is beyond repair Check outdoor coil heat exchanger and fan operation Check heat load increase Check cold air circulation for smooth flow Check gas leakage Clean condenser Not on separate circuit Check inside gas pressure Adjust refrigerant charge Malfunction of compressor Replacement of compressor Check clogging...

Страница 22: ... start Defect of compressor capacitor Replacement of compressor Motor damaged Irregular motor insulation Ω Irregular motor resistance Ω Check of circuit breaker and fuse Gas leakage of feeler bulb of thermostat Check control switch Fan only fails to start Improper wiring Defect of fan motor capacitor Replacement of fan motor Regular but fails to start Replacement of compressor Locking of piston me...

Страница 23: ...e terminal Capacitor Discharge Test capacitor capacitor before testing Replace if not within 10 of manufacturer s rating Replace if shorted open or damaged Will not rotate Fan blade hitting shroud or blower wheel hitting scroll Re align assembly Units using slinger ring condenser fans must have 0 22 0 25 inch clearance to the base If necessary shim up the bottom of the fan motor with mounting scre...

Страница 24: ...h Check for continuity refer to the wiring diagram for terminal identification Replace the switch if the circuit is open Thermostat Check the position of knob If not at the coldest setting advance the knob to this setting and restart the unit Check the continuity of the thermostat Replace the thermostat if the circuit is open Capacitor discharge Check the capacitor capacitor before Replace if not ...

Страница 25: ...res will increase causing the compressor to cycle Straighten the fins or replace the coil Capacitor Test the capacitor Wiring Check the terminals If loose repair or replace Refrigeration system Check the system for a restriction Insufficient cooling Air filter If restricted clean or replace Unit undersized Determine if the unit is properly sized for the area to be cooled Excessive noise Turbo Fan ...

Страница 26: ... 2 266002 1 149410 352115 349480 352113 35211A 567502 554160 550140 137215 W0CZZ 264110 354210 130410 W48602 148000 130910 359011 554030 159830 147582 1 147582 2 352380 1 352380 2 135312 249950 359012 149980 346811 731273 W48602 269310 552113 35211A 238310 749740 145200 ...

Страница 27: ...P No 3828A29003D February 2005 Printed in China ...

Отзывы: