Common Faults
&
Solutions
1
2
3
4
5
6
7
No.
Common Faults
Solutions
Acid leakage
Please contact the supplier for solutions.
Crack
Low floating voltage of single cell
High temperature on battery pole and
cell
Abnormal Appearance
Grounding Fault
Abnormal connect & inner
resistance
Please contact the supplier for solutions.
After 24-48hrs equalization charger, still low, please contact the supplier for
solutions.
Check whether the connection is good, inspect charger, ventilation and charging
current.
Clean dust, and check leakage or ground faulty. The battery bank shall be
insulated from the ground.
Please contact the supplier for solutions.
Check whether the connection is good, inspect charger, ventilation and
charging current.
3. Battery cleaning
Use cloth soaked in water or carbonic acid water to clear battery and cover.
4. Capacity test
If batteries work properly, no need to check capacity. Check capacity only when battery capacity is in doubt.
When battery is in discharge, the cut-off voltage should not be lower than the requirement in the technical
manual.
Before capacity testing, make sure battery get fully charged for more than 48 hours under float charge, if not,
make a equalization charge for 24 hours. Let batteries rest and cool down for 8-24 hours and then conduct
capacity test.