Engineer Programming
Page 68
System: Controls: Advanced
Quick Keys
Parameter
Default
Range
Advanced
Yes
Yes/No
This section refers to the advanced controls in the system.
Double Verification
of Fire Alarms
No
Yes/No
YES
: Implemented on detection of smoke or fire for verification. Power
to the smoke detector(s) in the affected zone is cut off and restored after
the time defined in the
Switch Aux Break
delay (page 62). If a
subsequent detection occurs in the same zone within one minute of the
first detection, the system emits a fire alarm.
NO
: No fire alarm verification takes place.
Alarm ZE Cut
No
Yes/No
YES
: Produces an alarm if the communication between the main panel
and any expander is lost. A report is transmitted to the ARC.
NO
: No alarm occurs. The system, however, produces a local fault
indication.
Code Grand Master
No
Yes/No
YES
: Only a user with the grand master authority level can change all
user codes, along with the time and date.
NO
: Users with the grand master and master authority levels can change
their own user codes, all codes with a lower authority level, and the time
and date.
Area
No
Yes/No
Changes the system operation to area instead of partition, which then
changes only the operation of a common zone.
YES
: When selected, the following points are relevant:
A common zone will be set after any partition is set.
A common zone will be unset only when all partitions are unset.
NO
: When selected, the following points are relevant:
A common zone will be set only when all partitions are set.
A common zone will be unset when any partition is unset.