background image

Engineer Programming 

Page 62 

Quick Keys 

Parameter 

Default 

Range 



 

Exit Delay 2 

 45 seconds

 

01-255 seconds

 

Duration of exit delay 2. 



 

Bell Timeout 
 

 15 minutes

 

01-90 minutes 

Duration of the external sounder(s) during alarm. 



 

Bell Delay 
 

 00 minutes/seconds

 

 00-90 minutes/seconds 

The time delay before the keypad sounder and the external sounder 
operate after the onset of an alarm. 



 

Switch Aux Break 
 

 10 seconds

 

00-90 seconds 

The time that the power supplied to the system's smoke detectors through 
the programmable output is interrupted during a user-initiated smoke 
detector reset, typically performed after a fire alarm or automatically 
when a fire verification is defined in the system control. (Refer to Double 
Verification of Fire Alarms, page 68, for additional details.) 

Note 

This feature is supported through any programmable output that is 
defined as Switch AUX . 



 

Wireless 

 

 

Specifies the time intervals relating to the operation of the wireless 
module 



 

Jamming Time

  

None 

None, 10, 20 or  
30 seconds

 

Specifies the period of time that the LightSYS's wireless module tolerates 
unwanted radio frequencies capable of blocking (jamming) signals 
produced by the system's transmitters. Once the specified time is reached, 
the main panel sends a report code to the alarm receiving center. (Refer to 

Jamming Fault

, page 199.) 

NONE 

10 SEC  

 20 SEC 

 30 SEC  

NONE:

 No jamming will be detected or reported. 

Note: 

Different sounds will be produced when jamming is detected, depending 
on the defined Audible Jamming time 

Содержание LightSYS

Страница 1: ...Installation and Programming Manual ...

Страница 2: ...O Group The information contained herein is for the purpose of illustration and reference only Information in this document is subject to change without notice Corporate and individual names and data used in examples herein belong to their respective owners Compliance Statement Hereby RISCO Group declares that the LightSYS series of central units and accessories are designed to comply with EN50131...

Страница 3: ... Auxiliary Devices 23 Wiring Internal Bell 24 Wiring Bell Tamper 24 Wiring Programmable outputs 25 Back Tamper Optional 26 Connecting a telephone line to the LightSYS 26 Placing the Communication Modules 27 GSM GPRS 27 Plug in IP 28 Plug in Fast Modem 2400 29 Plugs 29 Jumpers 30 DIP switches 31 Connecting Backup Battery 31 Chapter 3 Installing Bus Devices 32 Bus connection 32 Setting Bus Accessory...

Страница 4: ... 55 Step 1 Allocate a wireless receiver 55 Step 2 Calibrate the Receiver 55 Step 3 Allocating Wireless Device 56 Bus Detectors Programming Workflow 56 Programming bus detectors on the main bus 57 Step 1 Adding Bus Detector to the Main Unit 57 Step 2 Set Bus Zone Basic Attributes 57 Step 3 Programming the Bus Detectors Advanced Parameters 57 Programming bus detectors on a bus expander 57 Step 1 Add...

Страница 5: ...7 Label 87 Partition 87 Type 87 Sound 94 Termination 95 Loop Response 95 Advanced 96 Bus Zones Configuration 97 Testing 105 Cross Zones 107 Alarm confirm 109 3 Outputs 110 Nothing 110 Follow System 111 Follow Partition 114 Follow Zone 118 Follow Code 119 4 Codes 121 User 122 Grand Master 124 Engineer 124 Sub Engineer 125 Code Length 125 5 Communication 126 Method 126 PSTN 126 GSM 128 Timers 128 Co...

Страница 6: ...rt Split 145 Report Codes 147 Configuration SW 147 Follow Me 150 Define FM 150 Report Type 150 Partition 152 Events 152 Restore Events 154 Remote Control 155 Controls 155 Parameters 156 6 Audio 156 Messages 157 Local Announcements 158 7 Install 160 Bus Device 160 Bus Devices Automatic Setting 160 Bus Devices Manual Setting 161 Bus Devices Testing 171 Wireless Devices 173 8 Devices 176 Keyfob 177 S...

Страница 7: ... 187 Stand Alone Keyfobs 187 Appendix A Technical Specifications 188 Appendix B LightSYS Accessories 192 Appendix C Wiring 195 Appendix D Library Voice Messages 198 Appendix E Report Codes 199 Appendix F Engineer Event Log Messages 204 Appendix G Engineer Programming Maps 213 Appendix H EN 50131 and EN 50136 Compliance 222 Appendix I Remote Software Upgrade 225 ...

Страница 8: ...e 2 11 Placing the IP modem 28 Figure 2 12 Placing the Fast communication modem 29 Figure 2 13 Placing the battery and attaching the plug 29 Figure 3 1 Terminal block bus connectors 32 Figure 3 2 Zone Expander board and mounting diagrams 35 Figure 3 3 Zone Expander mounting location inside the LightSYS box 36 Figure 3 4 Programmable Output Module PO4 Showing an Example of PO4 Wiring 36 Figure 3 5 ...

Страница 9: ...ll in one box and an IP GSM receiver package for alarm receiving centres ARC LightSYS provides a new level of remote service and installation convenience with unique remote diagnostic capabilities Auto Install technology and bus test which checks communication quality of the bus and enables pinpointing intermittent wiring faults LightSYS can be programmed and or controlled through the remote confi...

Страница 10: ...mable outputs 4 onboard expandable to 14 User codes 16 Event log 500 Keypads 4 wired wireless one way Wireless keyfobs 16 multi functional 200 stand alone Proximity key readers 8 Follow me numbers 16 Communication PSTN onboard Plug on IP module or fast modem Plug on GSM GPRS or integrated KP long range radio Long range radio Account Numbers 4 Additional inputs Bell tamper box tamper Max Current 1 ...

Страница 11: ...ounders bells or loudspeakers respectively Supports more than 25 zone types 4 zone terminations including closed circuit NC open circuit NO end of line EOL resistors and double end of line DEOL resistors Configurable zone resistance 500 Event log on board Zone Expansion Support for additional 24 wired wireless zones Zones expansion using 8 Zone wired expander Max 3 expanders or Bus Zones expander ...

Страница 12: ...different wireless detectors such as o Smoke detectors o Door contacts Door magnet universal transmitter door contact universal o Up to 16 rolling code 4 button keyfobs o Double key panic keyfob o Flood detector o Shock detectors o CO detectors o Gas detectors o Glassbreak detectors o Internal and External PIR PET and WatchOUT detectors Partitions Areas Up to 4 independent partitions areas Any zon...

Страница 13: ... tamper protection Internal buzzer Audible feedback for keypad operations Easy to use hot key sequences for simple zone omitting A one key quick set feature for both Part set and Full Set In partitioned systems keypads can be selectively assigned to specific partitions Four function keys A B C D can be programmed to carry a sequence of commands User Codes and Authority Levels 1 engineer code 1 sub...

Страница 14: ...merous transmission formats to ARC including ADEMCO Contact ID and SIA Account number for each alarm receiving centre with additional backup accounts 3 ARC link up options using o PSTN report o GSM report o IP report o GPRS report o SMS report o Long Range Radio report Flexible split reporting for backup Call Save mode from which non urgent reports can be collected over a designated time period an...

Страница 15: ...ring auxiliary devices and triggering bells electronic sounders or loudspeakers during an alarm Each power supply expansion module also supports its own standby battery and is supervised for the loss of AC a low battery condition tamper input the failure of its auxiliary output power and the loss of sounder loop integrity Scheduling Through the use of the system s built in clock it is possible to ...

Страница 16: ... every minute and automatically performs a comprehensive self test and reports when operating faults are found o A maintenance mode which when selected performs an active self check on many of its components o One man walk testing capabilities enabling an engineer or technician to check the operation of each contact and detector which when tripped produce audible feedback and are visibly logged at...

Страница 17: ...various expanders 9 Connect backup battery and AC power 10 Perform automatic setting and complete system programming Choosing the mounting location Before you mount the LightSYS study the premises carefully in order to choose the exact location of the unit for the best possible coverage and yet easily accessible to expanders and accessories and prospective users of the alarm system Among the mount...

Страница 18: ...ub assemblies by pressing the circular locking plastic brackets on either side to release the front cover Figure 2 1 Box clip release 2 Hold the mounting bracket against the wall as a template and mark the locations for the mounting holes 4 mounting holes and an additional optional hole for securing the tamper protection bracket item Figure 2 2 Mounting screw template 3 Drill the desired mounting ...

Страница 19: ...ure 2 3 Placing the AC adapter with mains fuse Caution When the main panel is powered on mains voltage is present on the main PCB To prevent risk of electric shock disconnect all power AC transformer and battery and phone cords before servicing Under no circumstances should mains power be connected to the PCB other than to the main terminal block A readily accessible disconnect device shall be inc...

Страница 20: ...Mounting and Wiring Page 20 Figure 2 4 Placing the main panel 3 Wire all require expansion modules as described in Chapter 3 Installing Bus Devices ...

Страница 21: ...re 2 5 Main board wiring diagram Main Board Bus Connection Figure 2 6 Main board terminal block The set of four terminals on the left of the terminal block represent the expansion bus These terminals support the connection of keypads and expansion modules The connections are terminal to terminal with color coded wires as follows AUX RED 12V DC power BUS YEL Yellow data COM BLK 0V common BUS GRN Gr...

Страница 22: ... 5 For long cable runs please use the correct cable as stated in Appendix A Technical Specifications Zone Inputs Wiring The following diagrams illustrate the various zone connections to the main unit or to the 8 wired zones expander and possible 4 wire smoke detector END OF LINE ZONE N O CONTACT zone com ALARM 2 2 K DETECTOR NORMALLY OPEN ZONE CONFIGURATION ALARM zone com DETECTOR NORMALLY CLOSED ...

Страница 23: ...s and or any device that requires a 12V DC power supply The total power from the AUX terminals should not exceed 800 mA Notes If the auxiliary outputs are overloaded exceed 800mA and are shut down you must disconnect all loads from the outputs for a period of at least 10 seconds before you reconnect any load to the auxiliary outputs LightSYS supports 4 wire smoke detectors To connect a 4 wire smok...

Страница 24: ...provides power to the internal sounder When connecting an internal sounding device pay attention to the polarity It is important to position the BELL LS DIP switch SW1 see p 31 correctly The position varies depending on the type of internal sounder A maximum of 800mA may be drawn from this terminal Note To avoid bell loop fault if no connections are made to an internal sounder use a 2 2K resistor ...

Страница 25: ...ice activation whether resulting from time dependency external input or device sensor As detailed in Chapter 4 3 Outputs you can program customized device activation powerfully and granularly For additional details see page 36 To wire Programmable output 1 Utility output 1 can be used to activate a self powered sounder or any other self powered device Figure 2 8 Wiring U01 for self powered device ...

Страница 26: ... page 18 3 Attach the tamper wires to PCB main board PLUG2 p 29 The back tamper switch is located on the rear side of the back panel and is constantly depressed by the section shown in Figure 2 9 Note If the installation does not include the tamper mechanism set DIP switch 4 to ON see page 31 Figure 2 9 Perforated Back Tamper Release Connecting a telephone line to the LightSYS 1 Connect the incomi...

Страница 27: ...ee wrong attempts recognized by the SIM card to enter a PIN number the SIM card will lock You will have to contact your local cellular provider to unlock the SIM card Important Do not install SIM card while power is applied to the LightSYS Do not touch SIM Card connectors If doing so you may release an electrical discharge that could damage the SIM card Once the SIM card is placed it is recommende...

Страница 28: ...vate the Plug in IP Module 1 Place the optional IP communication modem mounted on its cylindrical placement struts as illustrated in Figure 2 11 2 Connect the incoming LAN cable in order to enable IP Communication Make sure that the cable is connected to the network Figure 2 11 Placing the IP modem ...

Страница 29: ...plug for easy connection to the bus PLUG 2 Back Tamper Used for the connection of the optional back tamper PLUG 3 Telephone Used for a local telephone connection same as the PHONE SET terminal PLUG 4 Voice Used to connect the Advanced Digital Voice Module RP432EV to the LightSYS Connect the Voice module to the VOICE connector PLUG 4 on the main panel via the supplied cable This connector transmits...

Страница 30: ...discharge protection Use the following table to set the jumper Position Function Default Battery Discharge Protection is disabled The battery may be totally discharged during continuous AC failure thus battery replacement may be required no deep discharge protection Note In this position the LightSYS will start to operate from a battery power supply whether it is connected to the Mains or not Batt...

Страница 31: ...nect the leads to the main panel battery PLUG7 p 30 Notes The main panel is designed to work with an approved 12 VDC 7 Amp hour sealed lead battery as a backup for the primary power supply in time of main power failure The main panel is designed with reverse polarity protection on the battery charging circuit However prolonged improper connection of the battery to the main panel will result in dam...

Страница 32: ...s AUX RED 12V DC power BUS YEL Yellow data COM BLK 0V common BUS GRN Green data Connect each bus device necessary for the installation using the bus connections Figure 3 1 Terminal block bus connectors Notes 1 The parallel wiring system supports parallel connections from any point along the wiring 2 The maximum wire run permitted is 300 meters 1000 feet for all legs of the bus 3 In case of bus com...

Страница 33: ... ON OFF ON ON OFF 30 ON OFF ON ON ON 15 OFF ON ON ON OFF 31 OFF ON ON ON ON 16 ON ON ON ON OFF 32 ON ON ON ON ON Notes Most accessories have four DIP switches while bus detectors have five DIP switches IDs 9 32 are only available for bus detectors If a DIP switch is changed on any device it is necessary to shut down the device s power and then re power it The first module in each category is defin...

Страница 34: ...P128KP To install LightSYS bus keypads 1 Open the keypad cover 2 Set ID DIP switches 3 Connect the keypad to the bus 4 Set the back tamper switch Only in model RP128KP 5 Adjust the brightness and contrast of the LCD keypad using a trimmer located next to the dipswitches Model RP128KCL In models RP128KP and RP432KP it is done by pressing and holding OK 6 Close the keypad 8 Zone Expander The LightSY...

Страница 35: ... to the appropriate Zone Z terminal and its related COM terminal Each pair of zones shares a COM terminal For example Z1 and Z2 share a COM terminal as do Z3 and Z4 and so on END OF LINE ZONE N O CONTACT zone com ALARM 2 2 K DETECTOR NORMALLY OPEN ZONE CONFIGURATION ALARM zone com DETECTOR NORMALLY CLOSED ZONE CONFIGURATION ALARM zone com DETECTOR END OF LINE ZONE N C CONTACT 2 2 K zone com ALARM ...

Страница 36: ...htSYS box Programmable Outputs The LightSYS programmable outputs support a variety of device activation based on periodicity or system event As detailed in Chapter 4 Using the Engineer Programming Menus Outputs you can program customized device activation powerfully and granularly Figure 3 4 Programmable Output Module PO4 Showing an Example of PO4 Wiring ...

Страница 37: ...ansmitter ii Plug the X 10 transmitter into the AC power iii Plug the X 10 receiver into the AC power close to the device that will be operated iv Connect the X 10 receiver to the device 4 Mount the Programmable Output Expansion Modules in the main panel cabinet depending on space availability or in a separate cabinet see Figure 3 3 5 If the Programmable Output expansion module is mounted in a sep...

Страница 38: ...rminal block Figure 3 7 Wireless Receiver To install the wireless receiver 1 Separate the mounting bracket from the main unit 2 Use the mounting bracket as a marking template 3 Tear off screw caps as needed for covering front screw hole 4 Mount the bracket to the wall 5 Open the wireless receiver front cover 6 Set DIP switches as follows Switch Description SW1 SW3 3 switches to set ID of the wirel...

Страница 39: ...ide Note For additional programming and configuration instructions see 5IN1424 Wireless Receiver 432 Installation instructions 3A Switching Mode Power Supply Figure 3 8 SMPS General View To mount the 3A Switching Mode Power Supply SMPS 1 Mount the SMPS and the backup battery inside a metal box Important The SMPS should be serviced by qualified personnel only Unless serviced the SMPS box must be cl...

Страница 40: ...to the wall it is recommended to use Ø4 2mm 32mm length screws DIN 7981 4 2X32 ZP 5 Connect the incoming mains cable to the main fuse terminal block 6 Wire the SMPS terminals as follows a Connect the bus Terminals Connect only three of the first four terminals at the left of the Power Supply expansion module to the main panel s 4 wire bus as follows Expansion Bus Terminals COM BUS BUS Color BLK Bl...

Страница 41: ...into account when selecting a wire gauge see Appendix C page 195 3 Any internal sounder s connected to the power supply expansion module will operate exactly like the sounder s connected to the main panel d AUX RED Used together with the COM terminal to apply power to Aux devices e g PIRs smoke glass break detectors and any other devices that require 12VDC power supply Total current consumption fr...

Страница 42: ...r Supply LightSYS communication On up Communication enabled Off down Communication disabled Progra mmabl e Output PO SW1 SW3 Used to set a unique bus ID number for the PO module located on the SMPS board PO SW4 Enables disables PO module LightSYS communication On up communication enabled Off down communication disabled Note When PS SW4 or PO SW4 is Off the ID number defined by SW1 SW3 is not recog...

Страница 43: ...LL LS terminals Note The sounder s connected to the SMPS operates identically to the main panel s sounder s Bell For a bell electronic sounder with a built in sounder driver position jumper on one pin 12VDC is produced at the sounder s terminals during burglary panic alarms Slow pulsing voltage is produced during fire alarm LS Speaker For a loudspeaker without a built in sounder driver position ju...

Страница 44: ... block 2 OPT Not in use 3 Test Connected in parallel to all output channels and enables to listen to all played messages using a speaker at least 32 Ohm connected between the Test Spkr and COM terminals 4 Intern Mic Select an external or internal microphone for recording messages On Recording messages from the microphone located on the Voice module board Off Recording messages from a microphone lo...

Страница 45: ... as illustrated in the diagram above c Connect the Voice module to the VOICE connector on the LightSYS main panel PLUG 4 via the supplied cable as illustrated below This connector transmits signals from the Voice module to the telephone line during remote communication and is essential for normal operation of the Voice module 3 Mount the Voice module inside the plastic enclosure with the LightSYS ...

Страница 46: ... 1 SW1 3 Set ID Bus Number Up to 4 sounders can be connected to the LightSYS d DIP switch DIP 2 SW2 Set different sounder sound Notes The sounder will not operate when a battery is not connected or no power supply is connected to the PS terminals After powering up the sounder it will not operate for a period of 20 seconds sound and strobe in order to avoid accidental activation during installation...

Страница 47: ...atchOUT LuNAR and WatchIN set the switch that defines the detector operation mode to bus mode 2 Wire the bus terminals AUX RED COM BLK BUS YEL and BUS GRN to the LightSYS bus Note For maximum operation stability it is best NOT to exceed a total 300 meters 1000 feet of wiring from the bus detector to the LightSYS panel To connect bus detectors using a Bus Zone Expander BZE Important Note Connecting...

Страница 48: ...n ease your installation by connecting any detector in parallel connections from any point along the wiring route In addition you can define any detector with one of the following zone terminations supported by the panel NO NC EOL DEOL To connect the RP128EZ01 to the LightSYS bus Note Up to 32 Single Zone Expanders can be installed on the LightSYS 1 Set the RP128EZ01 ID number 1 32 using DIP switc...

Страница 49: ...s The Black and White wires are equivalent to zone input terminals in the LightSYS Completing the Installation To complete the installation 1 Mount the back panel to the wall using affixing screws 2 Connect the system to the mains power Note If no back tamper is connected set SW1 4 to ON position to avoid tamper alarm 3 Close the front cover and close the locking screw 4 Upon completion of LightSY...

Страница 50: ...e manual PTM Data Storing Device The PTM is a tiny circuit board into which the LightSYS panel can transmit a copy of the system s configuration The PTM stores this copy and can also transmit the configuration information back to the LightSYS panel To copy from a programmed main panel into the PTM 1 Position the PTM on PLUG 1 connector on the main panel with the red LED facing the row of terminals...

Страница 51: ...LED on the Program Transfer module flashes rapidly indicating that the information is being copied from the PTM to the main panel The LCD keypad displays the following Please wait 5 When the LED stops flashing rapidly the keypad beeps once and its display returns to the normal initial display 6 Remove the PTM from the bus connector PLUG 1 7 Position the default DIP switch 2 to the OFF position 8 F...

Страница 52: ...either one of these keys to move back and forth through the programming level functions These keys also change the position of the flashing cursor When editing a selection the cursor moves to the left or right respectively or Used to toggle displayed menu options from N to Y and vice versa Used to increase or decrease selected screen digital values If you do not know where you are in the menu stru...

Страница 53: ...ineer Programming menu you must key in your Engineer code again and press Accessing Engineer Programming Menu First Time Power Up To power up LightSYS for the first time 1 Disconnect all power from the main panel 2 Set SW1 2 Default to ON position see page 31 3 Set SW1 4 Omit Tamper to ON position see page 31 4 Connect power to the assembled mounted unit 5 Press the key 6 Select language Scroll th...

Страница 54: ...s Automatic 2 Press to begin the automatic BUS SCANNING the Auto Settings process in which it identifies all the devices on the bus 3 Verify that the keypad displays all the devices you have connected If a device does not appear ensure that you have given it a unique ID within its family 4 Press to accept what is being displayed to progress through configuration screens and to advance on to the ne...

Страница 55: ... box tamper Press and move to step 2 Step 2 Calibrate the Receiver For successful communication strength of the signal should be higher than the noise threshold level measured in a process termed calibration 1 From the Engineer menu select Install WL Device RX Calibration 2 Select the wireless receiver and press 3 Using the key choose Y Yes to Re Calibrate the Wireless Receiver and press to confir...

Страница 56: ...your wireless device as shown in the table below Wireless Device Sending Write Message Detector Contacts Flood Shock Press and hold the tamper switch for 3 seconds Smoke Detector Insert battery Write message is sent automatically within 10 seconds Gas CO detectors Press and hold the test button for 3 seconds 2 Panic Button Key fob Press and hold both buttons for at least 7 seconds 4 Button Key fob...

Страница 57: ...arrow keys move to the Type field Use the key to select the detector s type 5 Repeat steps 2 4 for other bus detectors Step 2 Set Bus Zone Basic Attributes 1 From the main Engineer menu select 1 Zones 1 Parameters 1 One by One 2 Select the zone number that the bus zone was assigned to and press 3 Configure the parameters for the relevant bus detector Step 3 Programming the Bus Detectors Advanced P...

Страница 58: ...ssign Bus Detectors to a Zone ID and set basic parameters 1 From the main engineer menu press to enter the Bus Expander menu 2 Using the arrow and numeric keys select a bus zone expander ID 3 Using the arrow keys move to TYPE Use the key to select a BZE32 and press Step 2 Adding Bus Detector Refer to section Step 1 Adding Bus Detector to the Main Unit to assign a bus detector to the system Note Wh...

Страница 59: ... OFF position 2 Close the main box in order to prevent Front Tamper Alarm 3 Press repeatedly to return to Main Menu 4 Press to Exit and SAVE your settings Note The system will not allow exit from the Engineer mode if a Tamper or System Troubel condition exists Correct any tamper and or system fault conditions before attempting to exit the Engineer mode Restoring Manufacturer s Programming Defaults...

Страница 60: ...zed modules your menu option numerical display listing will be non successive The engineer menu consists of the following options System page 61 Zones page 84 Outputs page 110 Codes page 121 Communication page 126 Audio page 156 Install page 160 Devices page 176 Exit page The column headings appear as follows Column Heading Description Quick Keys A shortcut to program an option The shortcuts are l...

Страница 61: ...ounds page 80 Settings page 81 Auto Clock page Service Info page 83 Firmware update page 84 Timers The Timers menu contains parameters that specify the duration of an action Access and configure the parameters in the System Timers menu as follows System Timers Quick Keys Parameter Default Range Exit Entry Delay 1 Exit Entry delays Group 1 Entry Delay 1 30 seconds 01 255 seconds Duration of entranc...

Страница 62: ...e verification is defined in the system control Refer to Double Verification of Fire Alarms page 68 for additional details Note This feature is supported through any programmable output that is defined as Switch AUX Wireless Specifies the time intervals relating to the operation of the wireless module Jamming Time None None 10 20 or 30 seconds Specifies the period of time that the LightSYS s wirel...

Страница 63: ... Guard Delay 30 01 99 minutes Specifies the time period that the system will be unset after an authorized user enters a Guard code Swinger Limit 00 00 15 times A swinger is a repeated violation of the same zone often resulting in a nuisance alarm and usually due to a malfunction an environmental problem or the incorrect installation of a detector or sensor This parameter specifies the number of vi...

Страница 64: ...this time is other than 0 the panel will count down the time When the time expires a service message will be displayed on all LCD keypads whenever the keypad is on Unset display To clear the message the engineer needs to reset the time enter a code from the Anti Code menu or perform a remote reset to the panel Payment Timer 000 0 255 weeks Use this timer as a reminder for the user payment due When...

Страница 65: ...ecific system operations Access and configure the parameters in the system control menu as follows System Controls Basic Quick Keys Parameter Default Range Basic Programming This section refers to the most common controls in the system Quick Set Yes Yes No YES Eliminates the need for a user code when arming Full or partial NO A valid user code is required for arming Full or partial Quick PO Yes Ye...

Страница 66: ...em is unset after an alarm NO No chirp is produced 3 Minute Omit No Yes No YES Omits all zones automatically for three minutes when power is restored to an unpowered system to allow for the stabilization of motion and or smoke detectors NO No omitting occurs Audible Panic No Yes No YES The sounders operate when a Police Alarm is initiated at the keypad if defined the remote control or when a panic...

Страница 67: ... partition is then force set and all intact zones are capable of producing an alarm NO The partition cannot be set until all violated not ready zones are secured Set Pre Warning Yes Yes No Related to auto set unset operation YES For any partition s set up for auto arming an audible exit delay warning countdown will commence 4 25 minutes prior to the automatic arming During this period exit delay b...

Страница 68: ...expander is lost A report is transmitted to the ARC NO No alarm occurs The system however produces a local fault indication Code Grand Master No Yes No YES Only a user with the grand master authority level can change all user codes along with the time and date NO Users with the grand master and master authority levels can change their own user codes all codes with a lower authority level and the t...

Страница 69: ...is made 24 Hour Omit No Yes No YES It is possible for the user to omit a 24 hour zone NO It is not possible for the user to omit a 24 hour zone Technician Tamper No Yes No YES It is necessary to enter the engineer code to reset a tamper alarm Therefore resetting a tamper alarm requires the intervention of the alarm company However the system can still be set although the tamper indication is on NO...

Страница 70: ... low battery condition is detected also in the Power Supply expansion module NO Arming the system is disabled when a low battery condition is detected Bell 30 10 No Yes No YES Any internal sounders cease to sound for 10 seconds after each 30 seconds of operation NO Any internal sounders operate without interruption Fire Temporal Pattern No Yes No YES During a fire alarm the sounders produce a patt...

Страница 71: ...zone is closed NO Causes the following parameters to function as follows Auto Set Omit If the Auto Set programming arms the system and there is an open zone during the auto set the system will omit the open zones and set the system A programmable output defined as Auto Set Alarm is deactivated A programmable output defined as Zone Loss Alarm is deactivated Guard User If a Guard user disarms a part...

Страница 72: ...ll be silent during the bell delay time NO The keypad buzzer will be audible immediately when a system alarm occurs Speaker Buzzer Yes Yes No YES The internal sounder will follow the operation of any keypad s buzzer NO The internal sounder will follow the external sounder operation and not the keypad s buzzer Confirmation Speaker No Yes No YES A confirmed alarm triggers the internal sounder Note A...

Страница 73: ...re report to the ARC is always reported regardless of the TAMPER REP definition AC Fault Set Yes Yes No YES The system can be set with an AC fault detected in the main panel power supply module or the bus sounder NO The system cannot be set with an AC fault Strobe Set No Yes No This option allows the strobe internal or external activated by a programmable output Utility output Follow Partition Str...

Страница 74: ...s to the normal operation mode Select this option for keypads that can be viewed from outside the protected area to disguise the system status NO The keypad display operates normally System Controls Communication Quick Keys Parameter Default Range Communication This section refers to controls of the systems communication capabilities Monitoring Station Enable Yes Yes No YES Enables communication w...

Страница 75: ...e programming mode for one hour NO The engineer does not need an authorization code Override Fault Yes Yes No Specifies if the system partition can be set when there is a fault in the system YES The system will set even if there is a fault in the system NO When the user starts the arming process and there is a system fault the user must confirm that he is aware of all faults before continuing with...

Страница 76: ...t at the end of a successful arming procedure Entry Delayed Alarm No Yes No This feature is used to reduce false alarm reports to the ARC YES The report to the ARC and the sounder alarm will be delayed for 30 seconds or until the end of the predefined entry delay the shorter time of the two following a violation of a zone outside the entry route NO A violated zone outside the entry route will gene...

Страница 77: ...EN followers and Final Exit from participating in the alarm confirmation process when the entry time starts Note Sequential confirmation can still be established from two confirmed zones located off the entry route NO The entry route zones will participate in the alarm confirmation process when the entry time starts Engineer Reset Confirmation No Yes No YES An engineer reset confirmation is requir...

Страница 78: ... a remote control can unset the system during the entry time Note The system cannot be unset with a remote control while the system is set NO The system can be unset during any time using any disarming device System Controls CP 01 Quick Keys Parameter Default Range CP 01 This section refers to controls that apply to comply with SIA CP 01 Exit Restart No Yes No This parameter is used to define if a...

Страница 79: ...olation will activate tamper alarm NO Anti mask violation will be regarded as fault event Proximity Anti Mask Tamper No Yes No Used to determine the operation of the proximity anti masking detection indicated by the MW channel in the WatchOUT DT detector YES Proximity anti mask detection will activate the tamper alarm NO Proximity anti mask detection will be regarded as a fault event Note that Pro...

Страница 80: ...stem Labels Quick Keys Parameter Default Range System Security System Any 16 Characters Edits the global system label to Partitions 1 through 4 Partition 1 through Partition 4 Any 16 Characters Sounds The Sounds menu contains parameters that enable you to set the sound s that will be produced after the following system events Tamper Sound Sets the sound s produced by a Tamper violation of a keypad...

Страница 81: ...nal sounder beeps while there is fault in the system Chime 9 0 9 Determines the volume of internal sounder chime sound The Chime sound is used as an audible indication to a zone violation while the system is Unset Exit Entry 9 0 9 Determines the volume of the beeps sounded from the internal sounder during the Exit Entry times Alarm 9 0 9 Wireless Lost Sound Sets the behavior of the sound when a wi...

Страница 82: ...es programming options to factory defaults The panel default option will be followed by questions regarding the defaults of the labels and erasing wireless devices Use to select your option See page 59 Erase Wireless Erase wireless devices without changing the system current programmed parameters Select the receiver to be erased Note This entry appears only if a wireless device is registered in th...

Страница 83: ...tomatic time update NTP or Daytime through the IP network or GPRS System Automatic Clock Quick Keys Parameter Default Range Server Daytime Select the internet time protocol NTP Network Time Protocol DAYTIME Host 99 150 184 201 The IP address or server name Port 00013 The NTP server port Time Zone GMT Scroll through the available selections GMT 12 00 GMT 13 00 Service Information The Service Inform...

Страница 84: ...are Update Quick Keys Parameter Default Range Server IP firmware riscogroup com Enter the IP address of the router gateway where the upgrade file is located Server Port 80 Enter the port on the router gateway where the upgrade file is located File Name CMD TXT Enter the upgrade file name for example LightSYS 0UK cpcp bin Please contact Customer Support services for the file name parameters Downloa...

Страница 85: ...2 7 Zones Parameters One By One Important When using the One by One method the listing of each zone s parameters is sequential Once Zone 1 s parameters have been programmed they are followed by Zone 2 s then Zone 3 s and so forth To program one or more of the system s zones using the One by One method changes made to any or all of the Zone parameters will NOT be recorded without going through the ...

Страница 86: ...to create and or edit up to 15 characters to describe each of the system s zones see page 80 6 Press to confirm and proceed to the partitions category The Partitions menu contains parameters that enable you to program the partition assignment for each zone The following display appears P 1234 Z XX Y Note The XX in the Z XX designation is for the zone number In a multi partition system a zone can b...

Страница 87: ...he Zone Type menu contains parameters that enable you to program the zone type for any zone Setting the zone type is partly determined by the arming levels Three arming levels exist as follows Unset The system reacts only to those zones defined as 24 HR Fire Panic and Fault Set The system reacts to all zones Part Set The system does not react to zones defined as internal home This setting allows f...

Страница 88: ...xit Delay period ZZ Exit OP Entry 2 Same as above except that the Exit Op Entry 2 time period applies ZZ Entry Follower Usually assigned to motion detectors and to interior doors protecting the area between the entry door and the keypad This zone s causes an immediate intrusion alarm when violated unless an Exit Entry zone was violated first In this case Entry Follower zone s will remain omitted u...

Страница 89: ...I Exit OP Entry 1 Interior Exit OP Entry 1 Used for an exit entry door that for convenience may be kept open when the system is being set as follows In FULL SET mode behaves as an Exit Op Entry 1 zone see ZZ above In PART SET SET mode the zone will be omitted ZZ I Exit OP Entry 2 Interior Exit OP Entry 2 Used for an exit entry door that for convenience may be kept open when the system is being set...

Страница 90: ... night as follows With the system set either FULL SET or PART SET the zone acts as an intruder zone A violation of this zone after the system is set or during the exit delay time period causes an immediate intrusion alarm With the system unset a violation of this zone attempts to alert the user by causing the POWER LEDs on all keypads to flash rapidly This directs the user to view the system s fau...

Страница 91: ...te ZZ Special For external auxiliary emergency alert buttons and wireless auxiliary emergency transmitters If violated an immediate auxiliary emergency alarm is sounded regardless of the system s state and a report is sent to the alarm receiving centre ZZ Pulsed Key Switch Used to set Unset the system Connects an external momentary action keyswitch to any zone terminals given this designation ZZ F...

Страница 92: ...cting the area between the entry door and the keypad as follows In PART SET SET mode a zone s given this designation behaves like an Exit Entry zone and is subject to the Entry and Exit Delay time periods specified under Exit Entry Delay 1 Refer to Exit Entry Delay 1 page 85 In FULL SET mode a zone s given this designation behaves like an Entry Follower Zone and causes an immediate intrusion alarm...

Страница 93: ...operates the same as 24 hours zone but it has a special CO report code ZZ Exit Term This type of zone is used to avoid a false alarm by acting like an Exit OP Entry zone When triggered after arming the system and closing the door or opening the door arming the system and closing the door the systemʹs Exit Delay time period will be shortened to 3 seconds When you re open the door the entry time res...

Страница 94: ... systems zone triggers and alarm Reports to the alarm receiving centre are not affected by the option of this menu The following sound can be selected Silent Produces no sound Bell Only Activates the bell sounders for the duration of the Bell Timeout period or until a User Code is entered Buzzer Only Activates each keypad s internal piezo buzzer Bell Buzzer Activates the bell sounders and the keyp...

Страница 95: ...rminating End of Line Resistor EOL Uses normally closed NC and or normally open NO contacts in a zone terminated by End of Line Resistor DEOL Uses normally closed NC contacts in a zone using End of Line Resistors to distinguish between alarms and tamper conditions N O Uses normally open contacts and no terminating End of Line Resistor Loop Response The Loop Response menu enables you to set the dif...

Страница 96: ...eriod it will no longer be omitted and will be included among the system s set zones ZZ Pulsed Counter 01 01 15 Specifies that the zone will count the number of open and close pulses received If the zone exceeds the predefined number of pulses the zone will be tripped and act according to its type definition After a 25 second timeout the pulse counter is restarted The pulse length is the currently...

Страница 97: ...wo Microwave MW channels WatchOUT PIR An outdoor detector with signal processing based on two Passive Infrared PIR correlated channels WatchIN DT Grade 3 A dual technology Grade 3 industrial detector with signal processing based on two Passive Infrared PIR channels and two Microwave MW channels iWISE QUAD Grade 2 A motion detector incorporating Quad PIR technology iWISE DT Grade 3 A motion detecto...

Страница 98: ...hly recommended to avoid the possibility that an intruder will Learn the detector behavior 3 LEDS All 3 LEDs will operate ZZ PIR Sensitivity Normal Defines the PIR sensitivity of the detector LOW MEDIUM NORMAL HIGH ZZ Lens Type Wide Angle Defines the actual lens of the detector WIDE ANGLE BARRIER LONG RANGE ZZ Auxiliary Relay Mode Off Defines the operation of the auxiliary relay of the detector OF...

Страница 99: ...is not omitted Alarm condition cannot be established until the MW channel is fixed YES Switches the detector to operate only in PIR mode in case of MW fault ZZ Green Line Yes A feature that follows environmental guidelines by avoiding surplus emission This feature defines the activation of the microwave channel while the system is unset NO Green Line feature is disabled MW is constantly activated ...

Страница 100: ...he MW channel will be omitted or not while the detector identifies fault in the MW channel NO While detecting a problem in the MW channel it is not omitted Alarm condition cannot be established until the MW channel is fixed YES Switches the detector to operate only in PIR mode in case of MW fault ZZ Green Line Yes A feature that follows environmental guidelines by avoiding surplus emission This fe...

Страница 101: ...the Maintenance menu via the LightSYS User Functions menu LOCAL automatic Once an hour the detector automatically checks that the detector s channels are functioning properly Bus Zone iWISE QUAD Grade 2 Quick Keys Parameter Default Range ZZ LEDS On Defines the LEDS operation mode OFF Disables the LEDS operation ON Enables the LEDS operation ZZ PIR Sensitivity High Defines the PIR sensitivity of th...

Страница 102: ...detection while the detector is set or unset NO While set or unset anti mask behaves according to the setting defined in quick keys ZZ above YES While set anti mask is disabled When detector is unset Anti mask behaves according to the settings defined in quick keys ZZ ZZ Self Test Remote Used to test the detection technologies In the event of a failed test a Self Test Fault is created REMOTE Manua...

Страница 103: ...20 40 60 80 MAXIMUM TRIMMER MW is defined by the trimmer setting on the PCB ZZ Anti Mask Sensitivity Defines the sensitivity of the active IR AM LOW HIGH ZZ Lens Type Wide Angle Defines the actual lens of the detector WIDE ANGLE BARRIER LONG RANGE ZZ Anti Mask Enable Defines the operation of Anti Masking detection DISABLE Enable ZZ Set Unset No Defines the operation of the LEDs and Anti masking de...

Страница 104: ...ined by the trimmer setting on the PCB ZZ Alarm Logic PIR and Microwave Determine the detector s logic of defining an alarm PIR MW and Microwave An alarm is activated when both PIR and MW channels detect an alarm AND Logic PIR MW or Microwave An alarm is activated when either PIR or MW channels detect an alarm OR Logic ZZ Lens Type Wide Angle Defines the actual lens of the detector WIDE ANGLE BARR...

Страница 105: ...ters Supervision Choose which zone will be supervised by the system receiver according to the time defined under the timer RX Supervision See Resistance In the LightSYS you have the ability to define separately the end of line resistance of the zones on the main unit Selection is done by the software with the following available options Specify here the optional circuit resistance configuration Cu...

Страница 106: ...for the first test and sets the times for repeated tests over a 24 hour period A message is sent to the Central Station if all the related sensors are triggered during the test if a Report Code has been defined With successful completion of the self test an entry is also placed in the system s Event Log If one or more of the sensors fails to trip during the test period a self test failure message ...

Страница 107: ...s to confirm and display the initial menu 5 To add a second zone for Soak Test press and repeat the procedure above OR Press the key to return to the previous menu Cross Zones Default No cross zoning The Zone Crossing menu is used for additional protection from false alarms and contains parameters that enable you to link together two related zones Both must be violated within a designated time per...

Страница 108: ...d with themselves are valid pairs They need to register a violation twice to trigger the alarm This process is known as Double Knock 4 Press to display the correlation type screen PAIR 01 02 1 NONE Determine how the LightSYS will process violations of the paired zones 1 NONE Not correlated Temporarily disables any associated zone pairings 2 ORDERED Correlated Effects an alarm so the first listed z...

Страница 109: ... Time Window A confirmed intruder alarm will be reported if two separate alarm conditions are detected in the same confirmed partition during the confirmation time Cycle through the four partitions and press to toggle Y N Confirm zones Define which zones are to be defined for alarm sequential confirmation When the first zone goes into alarm the system transmits the first zone alarm When the second...

Страница 110: ...ogrammable output menu 1 From the main Engineer Programming menu press or press the keys until you find the number 3 UTILITY OUTPUT option and then press 2 Enter a two digit number for the Programmable output that you want to program using a leading zero for numbers between 1 and 9 for example 01 02 and so on and then press You can now program the selected Programmable output Use the information s...

Страница 111: ...ful call is established with the ARC Fault Follow Activates when a system fault condition is detected Deactivates after the fault has been corrected Main Low Battery Follow Activates when the LightSYS rechargeable standby battery has insufficient reserve capacity and the voltage decreases to 11 V or following an accessory low battery indication AC Loss Follow Activates when the source of the main ...

Страница 112: ...output activation For additional details refer to the LightSYS User s Manual Switched Aux Activates the programmable output when a fire zone is activated for fire detection according to the time defined in double verification of fire alarms page 68 This programmable output will not have the option to choose pulse or latch in the Programmable output Code The pulse time is defined in switched auxili...

Страница 113: ...ulsed only following any panic activation in the system The maximum number of times an output can be activated from the same zone is defined according to the Swinger Limit Timer Quick key Fire Activates the output Pulsed only following any fire activation in the system The maximum number of times an output can be activated from the same zone is defined according to the Swinger Limit Timer Quick ke...

Страница 114: ...ollow Activates the output when all the selected partition s are in the READY state Alarm Follow Activates the output when an alarm occurs in the selected partition s Set Follow Activates the programmable output when the selected partition s is set in either the FULL SET or PART SET mode The programmable output will be activated immediately regardless of the exit delay time period Burglary Follow ...

Страница 115: ... when the selected partition s initiates an Exit Entry delay period Fire Fault Follow Activates the output when a FIRE FAULT is detected in the selected partition s Day Zone Fault Activates when a day zone fault is detected in the selected partition s General Fault Follow Activates the output when a fault condition is detected in the selected partition Part Set Follow Activates the programmable ou...

Страница 116: ...ill not be activated Notes If an alarm occurs in a zone that shares more than one partition and one of the partitions is in Set mode while the other is in Part Set mode the output will be activated as described above In Part Set mode a 24 hour zone will not activate this output Zone Omit Activates the output when the relevant partitions are in Full Set or Part Set mode and any zone in the relevant...

Страница 117: ...d output that is used to trigger a strobe The output is activated when one of the defined partitions is in alarm mode or during squawks The output will be activated until the alarm is unset The output is also activated in test mode Note A tamper alarm will not activate the output if all the partitions are unset Fail To Set Activates when one of the defined partitions fails to set and deactivates a...

Страница 118: ... activated by a group of up to five zones To access the Zone sub menus 1 Access the outputs menu as described on page 110 2 From the Programmable output menu press 3 The following display appears PO 01 FOLLOWS 3 ZONE 3 Press to access the Zones menu The following display appears ZONE EVENT PO 01 1 ZONE FOLLOW 4 Select the zone event type to be followed from the following list Programmable output Z...

Страница 119: ...code and presses The engineer designates the user code s for triggering the selected PO Refer to the LightSYS User s Manual for additional details about triggering programmable output s via user codes Note The programmable output is activated by entering a user code only if the Quick PO parameter under System Control is defined as Disabled When the Quick PO is defined as Enabled no user code is re...

Страница 120: ...s always Activated N C before it is triggered pulled down to negative When triggered it deactivates and remains deactivated latched until the operation is restored 1 Press and then press 2 Using the key select ALL or ANY to set the activation and press 3 Using the key select ALL or ANY to set the deactivation and press 4 Define the output label and press Pulse N O 05 seconds 01 90 seconds The prog...

Страница 121: ...f the Pattern of Operation is defined as Latch N O or Latch N C the Engineer can choose the activation and deactivation logic of the PO to follow either after all the Partitions Zones or after any of the Partitions Zones If the Pattern of Operation is defined as Pulse N O or Pulse N C the Engineer can choose only the activation logic of the programmable output to follow either after all the Partit...

Страница 122: ...24 Engineer page 124 Sub Engineer page 125 Code length page 125 To access the Codes menu 1 From the main Engineer Programming menu press 4 or press the keys until you find the number 4 Codes and then press The first submenu 1 User appears 2 You are now in the Codes menu and can access the required submenus as described in the following sections User User rights can be defined by allocating each us...

Страница 123: ...ng and Unsetting o Omitting zones o Accessing designated partitions o Viewing system status fault and alarm memory o Resetting the switched auxiliary output o Activating designated programmable outputs o Changing his her own user code Set Only There are no restrictions in the number of Set Only codes as long as they don t exceed the number of codes remaining in the system Set Only codes are useful...

Страница 124: ...uthority level PO Control Typically used to enable the operation of a device controlled by a programmable output meaning a door and so on These codes are used only to operate a programmable output Grand Master Default 1234 The Grand Master Code is used by the system s owner and is the highest Authority Level The owner can set change the Grand Master Code Note The grand master code can also be chan...

Страница 125: ... All the other codes User Set Only and Maid use from one digit up to a maximum of six digits Note When you change the code length parameter all user codes are deleted and must be re programmed or downloaded For a 6 digit Code Length system 4 digit default codes like 1 2 3 4 Grand Master 1 1 1 1 Engineer and 2 2 2 2 Sub Engineer become 1 2 3 4 0 0 1 1 1 1 0 0 and 2 2 2 2 0 0 respectively If you cha...

Страница 126: ...ds channels of the LightSYS with three available communication types PSTN GSM IP Radio Long Range radio PSTN Quick Keys Parameter Default Range PSTN The PSTN screens contains parameters for the communication of the LightSYS over the PSTN network Timers Timers related to communication through the PSTN channel PSTN Lost Delay 4 minutes 0 20 minutes The time after which the system will regard the PST...

Страница 127: ...tor 3 Within one minute the software calls again 4 The LightSYS is programmed to pick up this second call on the first ring thus omitting any interaction with the answering machine Note This feature is used to prevent interference from an answering machine with remote configuration software operations NO The answering machine override is disabled and communication takes place in the standard manne...

Страница 128: ...ving centre as defined by your local telephone provider for example 70 This string will only appear during the first attempt to send a report to an ARC number PSTN or GSM Note Do Not use the Call Waiting cancel features inappropriately Using this feature on a line with no call waiting will prevent successfully reporting to the alarm receiving centre GSM Quick Keys Parameter Default Range GSM The G...

Страница 129: ...to check the connection 3 polling times can be defined Primary Secondary and Backup For each time period define the number of units between 1 65535 Each unit represents a time frame of 10 seconds Note When using the polling feature through GPRS the ARC channel parameter must be defined as GPRS only The report code for ARC polling is 999 Contact ID or ZZ SIA When the GPRS Primary polling time is de...

Страница 130: ...ackup ARC Polling example When selecting ARC 1 GPRS ARC 2 GPRS and split report option 1st Backup 2nd using the default primary secondary and backup time intervals the report process will be as follows In a normal state Polling through the GPRS network using the GSM module will occur every 90 seconds according to the primary time interval to ARC 1 and every 3600 seconds 1 hour according to the sec...

Страница 131: ...red The user name is provided by your provider The LightSYS supports a user name field of up to 20 alphanumeric characters and symbols etc APN Password The password to the GPRS network as provided by your provider if required The LightSYS supports a user name field of up to 20 alphanumeric characters and symbols Email The following programming parameters are used to enable sending Follow Me event ...

Страница 132: ...ned Follow Me phone numbers If the incoming number is recognized as one of the Follow Me numbers the operation will be executed Parameters Allows to program timers related to the operation with the GSM module PIN Code The PIN Personal Identity Number code is a 4 to 8 digit number giving you access to the GSM network provider Note You can cancel the PIN code request function by inserting the SIM ca...

Страница 133: ...ge Enter the message command as defined by the provider and the provider s phone number to which the credit level SMS message request will be sent Voice Credit Enter the provider s phone number to which a call will be established Service Command Enter the service command message as defined by the provider Phone To Send The provider s phone number to which the credit level SMS message request will ...

Страница 134: ...ystem refers to a static IP Address Panel Port The LightSYS Port address Panel IP Only for Static IP The LightSYS static IP address Subnet Mask Only for Static IP The subnet mask is used to determine where the network number in an IP address ends Gateway Only for Static IP The IP address of the local Gateway which enables communication settings to other LAN segments This address is the IP address ...

Страница 135: ...eric characters and symbols etc Host Name Up to 32 Characters IP address or a text name used to identify the LightSYS over the network Default Security System ARC Keep alive Polling The time period that the system will establish automatic communication polling with the ARC over the IP network in order to check the connection Three polling times can be defined primary secondary and backup For each ...

Страница 136: ...ARC 1 Fails Backup N A 1st Backup 2nd3rd Primary If ARC 1 is OK Secondary else ARC 1 Fails Backup If ARC 2 is OK Secondary else ARC 2 Fails Backup 1st Backup 3rd Call 2nd Primary Primary If ARC 1 is OK Secondary else ARC 1 Fails Backup 2nd Backup 3rd Call 1st Primary Primary If ARC 2 is OK Secondary else ARC 2 Fails Backup ARC Polling example When selecting ARC 1 IP Only ARC 2 IP only and split re...

Страница 137: ...LINE protocol to facilitate detailed event transmission to alarm receiving centres Account 0 0 00FFFF The number that recognizes the customer at the alarm receiving centre You can define an account number for each alarm receiving centre These account numbers are the 6 digit numbers assigned by the alarm receiving centre Notes Account Number Communication Format The account number will always be re...

Страница 138: ...gers an event report to the alarm receiving centre Control 060 0 255 Disable Low Battery Y Yes No YES For use when LRT is housed in the main LightSYS box LRT low battery fault condition will not be regarded NO For use when LRT is housed remotely in its own box LRT low battery fault condition will be regarded Alarm Receiving Centre The Alarm Receiving Centre menu contains parameters that enable the...

Страница 139: ...ine 3 PSTN Only The outgoing calls are executed through the PSTN audio channel only Use this option for installations where no GSM line is available 4 GSM Only The outgoing calls are executed through the GSM audio channel only Use this option for installations where no PSTN line is available Enter the alarm receiving centre telephone number including area code and special letters if required If ca...

Страница 140: ...report is executed through the GPRS network Enter the relevant IP and Port numbers for the ARC that will receive reports from the system See IP and Port SMS Events are sent to the alarm receiving centre using encrypted SMS messages 128 BIT AES encryption Each event message contains information including the account number report code communication format time of event and more The event messages a...

Страница 141: ... C20B Notes for Account Number in SIA Communication Format Account number for SIA should be defined as a decimal number Only digits 0 9 Account number can be reported as 1 to 6 digits To send an account number with less than 6 digits use the 0 digit for example For account number 1234 enter 001234 In this case the system will not send the 0 digit to the alarm receiving centre In order to send the ...

Страница 142: ...en the dialer receives the kissoff signal from the ARC s receiver NO The keypad does not indicate on receipt of the kissoff signal Show Handshake No Yes No YES The keypad indicates when the dialer receives the handshake signal from the ARC s receiver NO No indication for establishing communication with the central station s receiver Audible Kissoff No Yes No YES There is an audible sound emitted f...

Страница 143: ... Restoral is reported This option informs the ARC of a change in the specified condition s during an alarm restore These reports need a valid Report Code ON BTO Bell Time Out Reports the restoral after the audible alarm times out FOLLOW ZONE Reports the restoral when the zone in which the alarm occurs returns to its non violated secured state AT UNSET Reports the restoral when the system or the pa...

Страница 144: ...C to receive a cancel alarm code sent subsequently to the initial alarm code This happens if a valid user code is entered to reset the alarm in the cancel delay time window that starts after the defined abort alarm time is over Note Ensure that Cancel Alarm report code is defined Listen In 120 sec 1 255 seconds The time duration for the alarm receiving centre to listen in and perform voice alarm v...

Страница 145: ...s triggered before the end of the confirmation time window the system will send a confirmed alarm to the alarm receiving centre Report Split The Report Split menu contains parameters that enable the routing of specified events to up to three ARC receivers ARC Set Unset 1st backup 2nd Reports Setting Unsetting meaning Closings Openings events to the ARC Do not call no report Send 1st Reports Openin...

Страница 146: ...Closings to ARC 1 If communication is not established calls ARC 2 1st Backup 2nd3rd Reports to ARC 1 If communication is not established calls ARC 2 If communication is not established again calls the ARC 1st Backup 3rd Call 2nd Reports ARC 1 If communication is not established calls to ARC 3 In addition it will also call ARC 2 2nd Backup 3rd Call 1st Reports to ARC 2 If communication is not estab...

Страница 147: ...e a function of the central station s own policies Before programming any codes it is important to check the central station protocols Reporting codes are assigned by default according to the selected communication format SIA or contact ID Assigns a specified report code for each event based on the reporting format to the alarm receiving centre An event that is not assigned with a report code will...

Страница 148: ...e along with the access code must match between the Configuration Software and the main panel Dealers often use the customer s alarm receiving centre account number for the ID code but you can use any 4 digit code unique to the installation ARC Lock 000000 ARC Lock is a security function used in conjunction with the configuration software It provides greater proprietary security when viewing alarm...

Страница 149: ...M and PSTN Communication menu in the Configuration Software If the panel identifies one of the numbers as one of the numbers predefined in the panel the call will hang up and the panel will call back to that same number Control Call Back Yes Yes No The call back feature requires the system to call back to a pre programmed telephone number to which the alarm company s configuration software compute...

Страница 150: ...iguration software under Communication Configuration GPRS you should enter the IP address of the PC that the software is installed in Follow Me In addition to reporting to the alarm receiving centre the LightSYS has a Follow Me feature which enables reporting system events to predefined follow me destinations using a voice message SMS message or Email Up to 16 Follow Me destinations can be defined...

Страница 151: ...GSM line the line is routed to the PSTN line PSTN Only The outgoing calls are executed through the PSTN audio channel only Use this option for installations where no GSM line is available GSM Only The outgoing calls are executed through the GSM audio channel only Use this option for installations where no PSTN line is available EMAIL Report to Follow Me will be done by e mail thorough IP or GPRS E...

Страница 152: ...t Description Default Alarms Intruder Intruder alarm in the system Yes Fire Fire alarm in the system Yes Emergency Emergency alarm in the system Yes Panic S O S A panic alarm in the system Yes Tamper Any tamper alarm in the system No Duress Alarm Duress alarm in the system from user xx Yes Confirmed alarm Confirmed alarm indication No No Movement No movement report indication No Set Unset Set Sett...

Страница 153: ...the system PSTN Fault PSTN lost event If PSTN Loss Delay time period is defined the message will be sent after the delay time No IP Network Communication fault with the IP network No GSM GSM Fault General GSM fault Network availability Network Quality PIN code error Module communication GPRS password GPRS IP fault GPRS Connection PUK code fault No SIM Fault Any fault with the SIM card No SIM Expir...

Страница 154: ...he time defined in the Periodic Test parameter under the ARC parameters No Remote programming System is in remote installation mode No Quick Keys Parameter Default Range Restore Events Choose the restore events that will be reported to each Follow Me destination Event Description Default Alarms Intruder Alarm Intruder alarm in the system restored Yes Tamper Tamper alarm in the system restored No F...

Страница 155: ...ood Alert restored No CO Alert CO Alert restored No High Temperature High Temperature Alert restored No Low Temperature Low Temperature Alert restored No Technical Technical Alert restored No Quick Keys Parameter Default Range Remote Control Yes No Remote Listen No Yes No Enables the user of the Follow Me phone to perform remote listen and talk operation with the premises Remote program No Yes No ...

Страница 156: ...Retries 03 01 15 The number of times the Follow Me phone number is redialed Voice Message Recurrence 01 01 05 This number of times a voice message repeats itself when establishing a call to a Follow Me number Follow Me Periodic Test 01 05 The Periodic Test enables you to set the time period that the system will automatically establish communication to a Follow Me destination defined with the Perio...

Страница 157: ...prised of up to 4 words Each word has been pre recorded and assigned a number When comprising a message the engineer will enter the number of each word into the message sequence The system recognizes the numbers and sounds the words assigned to those numbers For example For the system to sound Top Floor Guest Bedroom you should enter the following sequence 119 050 061 019 The table in Appendix D L...

Страница 158: ... such as Heating for each Programmable output Macro Assigning a voice messages to a Macro simplifies the meaning of the macro operation for the user Library Message User defined messages for the customer needs Each messages is self recorded and can be up to 2 seconds long Local Announcements Local Announcement Upon event occurrence the system can announce the security situation to occupants of the...

Страница 159: ...ystem Partition set in Part Set Yes Unset System Partition unset Yes Audible Status Status heard when pressing the status button on the keypad remote control Yes Entry Exit System in exit or entry delay Yes Auto set System in auto set process Yes Output On Off Output activated or deactivated No Walk test Walk test The LightSYS will sound the zone number and description Yes ...

Страница 160: ...to verify the full operational functionality of installed hardware Automatic Manual Testing Bus Devices Automatic Setting Quick Keys Parameter Default Range Automatic The Auto Settings menu enables you to perform automatic setting of the accessories connected to the system by using the BUS scanning feature Note By default when entering Engineer mode with the default DIP Switch 2 in ON position the...

Страница 161: ...oose modify a keypad type 1 Through the menu selection the following display appears KEYPADS ID 01 TYPE 2 Use the or keys to position the cursor over the keypad ID number for which you want to assign or delete a keypad The first keypad must be assigned to the first ID number which is 01 Note Make sure that the keypad s physical ID number has been dip switch programmed as described in Setting Bus A...

Страница 162: ...ontrolled by the specified keypad Information about the selected partitions can also be viewed on the specific keypad 6 After pressing to store your partition choice The following display appears P 1234 KP xx YYYY MASK 7 For each partition 1 to 4 use the key to toggle between Y YES and N NO Note The xx represents the ID number of the keypad 8 Press Define the keypad controls Emergency keys multi v...

Страница 163: ...ors you intend to connect to the expander By default the resistance is set to 2 2K for EOL and DEOL termination See Zones resistance table page 105 4 Press to confirm and store your choice 5 Repeat the process for other Zone Expanders in the system Programmable output To choose modify a programmable output 1 Through the menu selection the following display appears UTIL OUTPUT ID 01 TYPE 2 Use the ...

Страница 164: ...has been selected the following display appears DELETE ARE YOU SURE N Press to return to the prior display OR 7 Press to select Y YES and press to confirm the delete Power Supply To choose modify a power supply 1 Through the menu selection the following display appears POWER SUPPLY ID 01 TYPE 2 Use the or keys to position the cursor over the power supply ID number for which you want to assign or d...

Страница 165: ...ess for any other power supply modules in the system up to the system s maximum of four depending on your installed model 8 If a power supply module is found and NONE has been selected the following display appears DELETE ARE YOU SURE N 9 Press to select Y YES and press to confirm Wireless Expander The LightSYS can support up to two wireless modules Each module can support up to 32wireless zones a...

Страница 166: ...s that you set when you installed the module 3 With the cursor positioned at the TYPE field use the key to toggle and choose the PKR option 4 Press The following display appears P 1234 KR01 Y MASK 5 Use the or keys and the key to assign the partitions that will be affected by the instant set function 6 Press The following display appears Controls PKR 1 Use the or keys to scroll the list and the ke...

Страница 167: ...ers 1 Through the menu selection the following display appears VOICE MODULE TYPE VOICE 2 With the cursor positioned at the TYPE field use the key to toggle and choose the VOICE option 3 Press The following display appears ENTER R PHONE CODE 00 4 Enter a remote phone code and press The remote code is used when calling the system from a remote phone Sounder To specify and configure a sounder sounder...

Страница 168: ...D Y 9 Use the key to toggle Y Yes or N No If yes the sounder will sound one squawk to indicate the set status 10 Press The following display appears SOUNDER 1 SQUAWK STROBE Y 11 Use the key to toggle Y Yes or N No If yes the sounder will flash to indicate the set status 12 Repeat above steps for other sounders if needed BUS Zones Up to 32 addressable bus detectors can be assigned to the LightSYS B...

Страница 169: ... the Type field Use the key to toggle and select the detector s type OPR12 WatchOUT PIR ODT15 WatchOUT DT WatIN WatchIN ILun3 Industrial Lunar Grade 3 iDTG3 iWISE DT Grade 3 iQUG3 iWISE QUAD Grade 3 iDTG2 iWISE DT Grade 3 iQUG2 iWISE QUAD Grade 2 BZ1 Single BUS zone expander 4 Press to confirm Repeat the process for the other bus detectors Note The iWISE BUS detectors have additional input on boar...

Страница 170: ...th the cursor positioned at the TYPE field use the key to toggle and choose the IPC option 3 Press to store your choice Note If IP module is found and NONE has been selected press to return to the prior display OR press to display a confirm delete screen Modem The Fast PSTN Modem enables PSTN communication at 2400 Bps between a remote PC and the LightSYS security panel when programming the system ...

Страница 171: ... in case a certain BUS detector is sabotaged To specify and configure Bus expander 1 Through the menu selection the following display appears BUS Expander TYPE NONE 2 With the cursor positioned at the TYPE field use the key to toggle and choose the BZE32 option 3 Press to store your choice LRT Long Range Transmitter To specify and configure LRT 1 Through the menu selection the following display ap...

Страница 172: ...TY LCDPI 01 99 A result of less than 100 means that there are bus connection problems for example bad wiring or cabling located in a harsh electrical environment or two modules in the same family have been given the same ID number Bus Scan The Bus Scanning menu scans the bus and reports all modules found To verify the bus expander connections 1 Through the menu selection the bus scanning begins an...

Страница 173: ...scertain that all keypads and expansion modules in the installation have been identified correctly VERIFY MODULE LCPDI 01 LCPDI VERIFY MODULE WM 01 WM The system displays each programmed device its address and whether or not it s found on the bus This helps you to identify programming mistakes Wireless Devices The Wireless Devices menu provides access to sub menus that are used for allocating and ...

Страница 174: ...Through the menu selection the following display appears Choose Receiver 1 ID 1 TYP WM 2 Select the wireless zone expander for which you want to establish the threshold level and press The following display appears showing the current threshold level THOLD XX WM1 RE CALIBRATE N 3 To perform a new automatic calibration use the key to select Y Yes After the calibration process is finished the new re...

Страница 175: ...f wireless expanders present affects only the total possible set of keypads two keypads per each expander for a maximum of four The maximum 32 zones and 16 keyfobs are irrespective of the presence or absence of a second expander By RF To allocate a wireless device 1 Select 1 By RF and press 2 Select the receiver to be used for the registration mode 3 Select category 1 Zone 2 Keyfob 3 Keypad and pr...

Страница 176: ... each BUS keypad Label A label identifying the keypad in the system Partition This partition specifies the location of the keypad and is mainly used for quick arming Masking Specifies the partitions that are controlled by the specified keypad Controls Advance through the parameters to be controlled Emergency The keypad s emergency keys can be enabled or disabled per keypad Yes Enable the operation...

Страница 177: ... Unset The button is used for disarming its assigned partitions Part Set The button is used for part set home arming of the assigned partitions Group The button is used for Group arming Partial arming within a partition area of the assigned partitions PO The button is used to operate a single programmable output Panic The button is used to send a panic alarm Note Full Set or PART SET arming can be...

Страница 178: ...ppropriate rename the sounder s label as per the key definitions on page 80 Strobe Use this menu to define parameters relating to the sounder strobe Control Follow Bell Defines the strobe operation mode ALWAYS OFF The strobe is deactivated FOLLOW BELL The strobe is activated when the sounder bell is triggered FOLLOW ALARM The strobe is activated when an alarm occurs in the selected sounder s parti...

Страница 179: ... ALTERNATE Only for Lumin8 The status LEDs will constantly alternate FLASH Only for Lumin8 The status LEDs will constantly flash Battery Load Test Every 24 Hours Enables to set the time period that the LightSYS will automatically generate a Load test on NEVER The system will not set a battery load test EVERY 24 HOURS Proximity Level Response 3 0 9 seconds Only for ProSound Defines the time seconds...

Страница 180: ...xternal lamp Power Source SAB SAB SCB Only for Lumin 8 Used to define the SAB or SCB power source mode of the LuMIN8 SAB Power supply for the sounder will be drawn from the control panel SCB Power supply for the sounder will be drawn from the sounder s rechargeable battery Sounder Current Standard Standard Low Only for Lumin 8 Set the sounder current mode LOW The sounder output will be reduced to ...

Страница 181: ... to this sub menu requires that a Proximity Key reader device is installed on your site Quick Keys Parameter Default Range Masking Specifies the partitions that are controlled by the specified PKR Press to display the partition application screen P 1234 KR 1 Y MASK Use the key to toggle Y N to set the partitions Control Use this menu to define controls of the PKR Scroll the list and use the key to...

Страница 182: ...Range Masking Specifies the partitions that the power supply is assigned to Press to display the partition application screen P 1234 PS 1 YYYY Use the key to toggle Y N to set the partitions Control Use this menu to define controls of the power supply Use the key to toggle Y N for each option BELL L SPEAK ...

Страница 183: ... for any function involving the Chime feature Partition Chime Allows user control turning ON and OFF of all keypad s buzzers in the partition for any function involving the Chime feature Buzzer On Off Used to control the Turning ON and OFF the current keypad s internal buzzer during both Entry and Exit Delay time periods and all fire and intruder alarms Follow Me Follow Me Define Destination Used ...

Страница 184: ...atus of the partition to which the keypad is assigned Pressing the sequence CODE from the normal operation mode will display the status of all the partitions assigned to the user code Zone Status Allows the display of all system zones and their current status Service Information Allows the display of any previously entered service information and the system version IP Address Use this option to vi...

Страница 185: ... events memory cannot be erased To skip 10 events at a time backward or forward use the consecutively Maintenance Maintenance Walk Test Enables to easily test and evaluate the operation of selected zones in your system Walk test is set for up to 60 minutes During the last 5 minutes of walk test mode the keypad used to perform the walk test will indicate that the walk test is about to end Full walk...

Страница 186: ...splays the signal level measured by the GSM module 0 No signal 5 Very high signal Version Displays information regarding the GSM module version IMEI View the IMEI number of the GSM module This number is used for identification of the LightSYS at the RISCO IP receiver when using GSM or GPRS communication IP Performs a diagnostic test for the following parameters of the plug in IP module IP Address ...

Страница 187: ...n number and momentarily tests the keypad indicators Voice Displays the voice module software version number and creation date LRT Displays the Log Range Radio module software version and its active protocol Macro Macro LightSYS enables the engineer or Grand Master record a series of commands and assign them to a macro For more information refer to LightSYS User Manual Stand Alone Keyfobs Stand Al...

Страница 188: ...max Main panel connection 4 wire BUS up to 300 m 1000 ft from Main Panel Dimensions 153 x 84 x 28 mm 6 02 x 3 3 x 1 1 inch Operating temperature 0 C to 49 C 32 F to 120 F Storage temperature 20 C to 60 C 4 F to 140 F Prox RF frequency 13 56MHz Touchscreen Keypad RP128KP01 RP128KPP1 Voltage 13 8V 10 Current Consumption RP128KP01 30 mA typical 180 mA Max RP128KPP1 with prox 30 mA typical 280 mA max ...

Страница 189: ... 10 Current 25 mA typical 160 mA maximum Contacts Open Collector Active Pull Down 70 mA maximum Main Panel Connection 4 wire BUS up to 300 m 1000 ft from Main Panel Dimensions 4 13 x 2 6 x 0 7 10 5 cm x 6 6 cm x 1 8 cm X 10 Transmitter Module Voltage 13 8VDC 10 Current 30 mA maximum Main Panel Connection 4 wire BUS up to 300 m 1000 ft from Main Panel Dimensions 10 5 cm x 6 6 cm x 1 8 cm 3A Power S...

Страница 190: ...A typical 180 mA max Main Panel Connection 4 wire BUS up to 300 m 1000 ft from Main Panel Dimensions 40 mm x 43 6 mm x 22 mm 1 57 x 1 7 x 0 86 Voice Module RP432EV Voltage 13 8VDC 10 Current 30 mA typical 70 mA maximum Operating temperature 0 70 C Main Panel Connection 4 wire BUS up to 300 m 1000 ft from Main Panel Sounders ProSound RS200WA RS200WAP Input DC Power Regulated 13 5 14 2V 200 mA maxim...

Страница 191: ...in Panel Connection 4 wire BUS up to 300 m 1000 ft from Main Panel Plug In GSM RP432GSM Voltage 13 8VDC 10 Current During Communication 300mA During Standby 30mA Dimensions 80 mm x 50 mm x 25 mm Plug In IP RW132IP Voltage 13 8VDC 10 Current 90mA maximum Dimensions 70 mm x 60 mm Plug In Modem 2400 RP432MD24 Voltage 13 8VDC 10 Current 20 mA typical 60 mA maximum Dimensions 70 mm x 25 mm BUS Expander...

Страница 192: ...xpanders Description RP432EW8 Wireless Receiver 868 MHz RP432EW4 Wireless Receiver 433 MHz Wireless Transmitters 868MHz Wireless Transmitters 433MHz Description RWT920868 RWT920433 Wireless PIR detector RWT92P868 RWT92P433 Wireless PIR detector with pet immunity RWT33S868 RWT33S433 Wireless smoke detector RWT72C868 RWT72C433 Wireless door contact RWT72M868 RWT72M433 Wireless door contact magnet RW...

Страница 193: ...er Supply Expansion Module in tamper box Medium UK RP128PSPSEUA 3A Switched Power Supply inside large metal box Tamper transformer RP128PSPSUSA 3A Switched Power Supply inside large metal box Tamper No transformer Programmable Output Devices Description RP296E04 4 Relay Output Expansion Module RP296E08 8 Open Collector Output Expansion Module Voice Unit Description RP432EV LightSYS Voice module RP...

Страница 194: ... from panel to PC USB RP132CB RS232 PC to Panel Cable Bus Detectors Description RK315DT WatchOUT DT swivel RK325DT WatchIN DT swivel RK312PR WatchOUT PIR swivel RK200DTG3 Industrial LuNAR DT AM Grade 3 RK815DTB iWISE DT AM Grade 3 15m RK825DTB000A iWISE DT AM Grade 3 25m RK800Q0B000A iWISE Quad 15m 50 ft AM Grade 3 RK815DTB200A iWISE DT AM Grade 2 15m RK825DTB200A iWISE DT AM Grade 2 25m RK800Q0B2...

Страница 195: ...ers Resistance Feet Millime ters Inches Ω Per Meter Ω Per 100 Meters Ω Per Foot Ω Per 1000 Feet 24 0 50 0 020 0 085 8 5 0 026 26 0 22 0 64 0 025 0 052 5 2 0 016 16 0 20 0 80 0 031 0 032 3 2 0 010 10 0 19 0 90 0 035 0 026 2 6 0 008 8 0 18 1 00 0 040 0 020 2 0 0 006 6 0 16 1 27 0 050 0 013 1 3 0 004 4 0 14 1 63 0 064 0 008 0 82 0 0025 2 5 Table A 1 Wire Facts One Way Wire Distance Between LightSYS a...

Страница 196: ... Branch 32 02 mm 18 AWG 28 02 mm 19 AWG 24 02 mm 20 AWG 16 02 mm 22 AWG 7 02 mm 24 AWG Max Run Max Run Max Run Max Run Max Run Meters Feet Meters Feet Meters Feet Meters Feet Meters Feet 20mA 1195 3920 945 3100 750 2460 472 1550 296 970 30mA 793 2600 628 2060 500 1640 314 1030 197 646 40mA 597 1960 472 1550 375 1230 236 775 148 485 50mA 478 1568 378 1240 300 984 189 620 118 388 60mA 296 1300 314 1...

Страница 197: ... s Feet Meter s Feet Meters Feet 100mA 238 780 191 625 151 495 94 310 200mA 229 390 95 313 76 248 47 155 300mA 79 260 63 208 50 165 31 103 400mA 59 195 48 157 38 124 24 78 500mA 48 156 38 125 30 99 19 62 650mA 37 120 29 96 23 76 15 48 Table A 5 Maximum External Sounder Current Note The wire lengths indicated represent the one way distance between the LightSYS and the external sounder in the branch...

Страница 198: ...G P 145 Washroom 019 Bathroom 063 Game 103 Panic 146 West 020 Bedroom 064 Garage 104 Partition 147 Window 021 Before 065 Garden 105 Passage Y 022 Behind 066 Gas 106 Patio 148 Yard 023 Bottom 067 Gate 107 Perimeter Z 024 Boy s room 068 Girl s room 108 Pool 149 Zone 025 By 069 Glass R Numbers C 070 Guest 109 Rear 150 0 026 Camera H 110 Reception 151 1 027 Ceiling 071 Hallway 111 Refrigerator 152 2 0...

Страница 199: ...nt Confirmed alarm 139 BV Urgent Confirmed alarm restore 139 Urgent Recent Close 459 Non urgent Main Faults Low battery 302 YT Non urgent Low battery restore 302 YR Non urgent AC loss 301 AT Non urgent AC restore 301 AR Non urgent Clock not set 626 Non urgent Clock set 625 Non urgent False code 421 JA Non urgent False code restore 421 Non urgent Main phone fault 351 LT Non urgent Main phone fault ...

Страница 200: ...7 OP Set Unset Forced Set 574 CF Set Unset Quick Set 408 CL Set Unset No Set 654 CD Set Unset Auto Set fail 455 CI Set Unset Detectors Zones Burglary alarm 130 BA Urgent Burglary alarm restore 130 BH Urgent Fire alarm 110 FA Urgent Fire alarm restore 110 FH Urgent Foil alarm 155 BA Urgent Foil alarm restore 155 BH Urgent Panic alarm 120 PA Urgent Panic alarm restore 120 PH Urgent Medical alarm 100...

Страница 201: ...estore 158 KH Urgent Zone fault 380 UT Urgent Zone fault restore 380 UJ Urgent Burglary fault 380 BT Urgent Burglary fault restore 380 BJ Urgent Zone omit 570 UB Urgent Zone omit restore 570 UU Urgent Burglary omit 573 BB Urgent Burglary omit restore 573 BU Urgent Zone supervision loss 381 UT Urgent Zone supervision restore 381 UJ Urgent Tamper 144 TA Urgent Tamper restore 144 TR Urgent Zone lost ...

Страница 202: ...S Set Unset Unset 409 OS Set Unset Low battery 384 XT Non urgent Low battery restore 384 XR Non urgent Wireless Sounder Tamper 145 TA Urgent Tamper restore 145 TR Urgent Low battery 384 XT Non urgent Low battery restore 384 XR Non urgent Sounder lost 355 BZ Urgent Sounder lost restore 355 Urgent Wireless I O Expander Low battery 384 XT Non urgent Low battery restore 384 XR Non urgent I O Expander ...

Страница 203: ... Local 628 LS LX Set Unset Enter programming Remote 627 RB Set Unset Exit programming Remote 628 RS Set Unset ARC periodic test 602 RP Non urgent ARC keep alive polling 999 ZZ Urgent Call back 411 RB Non urgent System reset 305 RR Urgent Listen in begin 606 LF Urgent Cancel Report 406 OC Urgent Walk Test 607 BC Non urgent Walk Test restore 607 Non urgent Exit Error 374 Non urgent ...

Страница 204: ... on partition Y is set by user ZZ SET C P y KF zz Group C on partition Y is set by wireless keyfob ZZ SET D P y C zz Group D on partition Y is set by user ZZ SET D P y KF zz Group D on partition Y is set by wireless keyfob ZZ SET FAIL P y Fail to Set Partition X by Guard due to not ready zones SET P y C zz Partition Y set by user ZZ SET P y KF zz Partition Y set by wireless keyfob ZZ Aut tst fail ...

Страница 205: ... Proximity Key Reader Y Comm OK VOICE Bus communication OK with Advanced Voice module Comm OK WME y Bus communication OK with wireless module expander ID Y Comm OK BZE y Bus communication OK with Bus Zone Expander ID Y Comm OK PS y Bus communication restore with power supply expander ID Y Comm OK Sounder y Communication OK between the LightSYS and Sounder Y Comm OK PO y Bus communication restore w...

Страница 206: ...ng engineer programming from keypad or configuration software Exit program Exiting engineer programming from keypad or configuration software F Tr OK Z xx Fault restore in fire zone no XX F Trbl Z xx Fault in fire zone no XX Fire Zone xx Fire alarm in zone no XX False code kp y False code due to 3 incorrect keypad attempts False code kr y False code due to 3 incorrect Access Control attempts False...

Страница 207: ...is low GSM PIN cod err PIN code entered is incorrect GSM PIN code OK PIN code is correct GSM PUK Cod err PUK code required GSM PUK Code OK PUK Code entered is correct GSM SIM OK SIM Card in place GSM SIM fault SIM card missing or not properly sited H Temp rst Z xx High temperature alert restored from zone XX defined as a temperature detector High Temp Z xx High temperature alert from zone XX defin...

Страница 208: ...Zone XX of type key box is open KeyBox Rst Z xx Zone XX of type key box is restored KSW A Z xx P Y Group A in partition Y is set by keyswitch zone XX KSW SET Z xxP Y Partition Y is set by keyswitch zone XX KSW B Z xx P Y Group B in partition Y is set by keyswitch zone XX KSW C Z xx P Y Group C in partition Y is set by keyswitch zone XX KSW D Z xx P Y Group D in partition Y is set by keyswitch zone...

Страница 209: ...store in Main Panel Main AC Rstr AC power restore on main panel Main Aux Rst Restore of Aux power on Main Panel Main Bat Rst Low battery fault restore from the main panel Main Low AC Loss of AC power from the main panel Main Low Bat Low battery fault from the main panel Main No aux Failure in the Aux power on Main Panel Main No bell Bell fault in Main Panel Masked Z XX Anti mask fault from zone XX...

Страница 210: ...r ID Y No comm GSM No communication between the GSM GPRS Module and the LightSYS No comm LRT No communication between the long range transmitter and the LightSYS No fault z xx Fault restore in zone XX TEOL zone or Bus zone input TEOL No jam wme y Jamming restore on wireless module expander ID Y No mask z xx Anti mask fault restore from zone XX Nxt hom p y Partition Y is set in Next Part Set mode O...

Страница 211: ... in Bus zone XX has been restored Soak fail Z xx Zone XX has failed in the soak test Spec KP y Special alarm from the from wireless keypad Y Spk Trbl RS S y Speaker low battery restore from sounder Y Spkr Trbl Sir y Speaker low battery fault from sounder Y Start exit P y Exit time started in partition Y Tamper BZE y Tamper alarm from bus zone expander ID Y Tamper Kp y Tamper alarm from keypad ID Y...

Страница 212: ...store from wireless sounder Y Unbyp Box Bell Box Bell reinstated from omit Unbyps Zn xx Zone no XX is reinstated from omit Unknown evnt Unknown event alert PO REST ZN xx A zone defined as PO Trigger has been deactivated PO TRIG ZN xx A zone defined as PO Trigger has been activated VOC COMM OK Bus communication OK with Voice Module VOC NO COMM Bus communication failure with the Voice Module Water A...

Страница 213: ...nd Chime Buzzer On Off Follow Me View Fault Alarm Memory Partition Status Zone Status Service Information Engineer System Version Clock Time and Date Scheduler Vacation Event Log Maintenance Walk Test Resistance Sounder Test Strobe Test Diagnostics Main Panel Bus Zones Zone Expander Power Supply Sounder GSM IP Wireless Voice Module Keypad LRT ...

Страница 214: ...t 14 IMQ Install 03 Code Grand Master 15 Disable Incoming Calls 04 Area 16 Disable Keypad at Auto Unset 05 Global Follower 17 Buzzer Delay 06 Summer Winter 18 Speaker Buzzer 07 24 Hour Omit 19 Confirm Speaker 08 Technician Tamper 20 Bell Confirmation 09 Technician Reset 21 Error Speaker Time Out 10 Engineer Tamper 22 Tamper Report 11 Low battery Arming 23 AC Fault Set 12 Bell 30 10 24 Strobe Set 3...

Страница 215: ...3 Buzzer main 3 Buzzer main 4 Bell Buzzer 4 Bell Buzzer 2 Speaker Volume 1 Fault 3 Exit Entry 2 Chime 4 Alarm 3 Wireless Lost Sound 1 As fault 2 As tamper 5 Settings 1 DIP 2 Enable Disable 3 Erase Wireless 5 Customer 2 Default Panel 4 Standard 6 Language 6 Automatic Clock 1 Server 1 NTP 2 DAYTIME 2 Host 3 Port 4 Time Zone GMT 7 Service Info 1 Name 2 Phone 8 Firmware Update 1 Server IP 2 Server por...

Страница 216: ...y 2 26 Technical 09 I Exit OP Entry1 27 Water 10 I Exit OP Entry2 28 Gas 11 I Entry Follow 29 CO 12 I Instant 30 Exit Term 13 PO Trigger 31 High Temperature 14 Day Zone 32 Low Temperature 15 24 Hours 33 Key Box 16 Fire 34 Keyswitch Set 17 Panic 35 Keyswitch Delayed Set 4 Sound 1 At Set 2 At Part Set 3 At Unset 5 Termination 01 N C 03 DEOL 02 EOL 04 N O 6 Loop Response 7 Advanced 1 Forced Arming 2 ...

Страница 217: ...tition 01 Ready 11 Fire Fault 21 Zone Loss Alarm 02 Alarm 12 Day Zone Fault 22 Bell Trigger 03 Set 13 Fault 23 Strobe Trigger 04 Burglary 14 Part Set 24 Fail To Set 05 Fire 15 Tamper 25 Confirmed Alarm 06 Panic 16 Unset 26 Duress 07 Special Emergency 17 Bell 08 Buzzer 18 Bell Part Set Off 09 Chime 19 Zone Omit 10 Exit Entry 20 Auto Set Alarm 3 Follow Zone 1 Zone Follow 3 Set Follow 2 Alarm Follow ...

Страница 218: ...M 1 Timers 1 GSM Lost 2 GSM Net Loss 2 GPRS 1 APN Code 2 APN User Name 3 APN Password 3 Email 1 Mail Host 2 SMTP Port 3 Email Address 4 SMTP User name 5 SMTP Password 4 Controls 1 Caller ID 5 Parameters 1 PIN Code 2 SIM Number 3 SMS Center Phone 4 GSM RSSI 6 Pre Pay SIM 1 Get Credit by 2 Phone To Send 3 Phone To Receive 4 SMS Message 3 IP 1 IP Configuration 1 Obtain IP 2 Panel Port 3 Panel IP 4 Su...

Страница 219: ...ble Low Battery 2 Alarm Receiving Centre 1 Report Type 1 Voice 1 PSTN GSM 2 GSM PSTN 3 PSTN Only 4 GSM Only 2 IP 1 IP GPRS 2 GPRS IP 3 IP Only 4 GPRS Only 3 SMS 4 Radio 2 Accounts 3 Comm Format 1 Contact ID 2 SIA 4 Controls 1 Call Save 2 Show Kissoff 3 Show Handshake 4 Audible Kissoff 5 SIA Text 6 Random Periodic test 5 Parameters 1 ARC Retries 2 Alarm Restore 1 On Bell Time out 2 Follow Zone 3 At...

Страница 220: ... 2 Call Back Phones 3 Control 1 Call Back 2 User Initiate Call 4 IP Gateway 1 IP Address 2 IP Port 4 Follow Me 1 Define 1 Report Type 1 Voice 2 Email 3 SMS 2 Partition 3 Events 4 Restore Events 5 Remote Control 1 Remote Listen 2 Remote Program 2 Controls 1 Unset Stop FM 2 Disable report at Part Set 3 Parameters 1 FM Retries 2 Voice Msg Recurrence 3 Periodic Test 6 Audio 1 Messages 1 Common 4 Outpu...

Страница 221: ...tition 3 Masking 4 Controls 1 Emergency 2 Multi view 3 Exit beeps 2 Keyfob 0 None 1 Set 2 Unset 3 Part Set 4 Group 5 PO 6 Panic 3 Sounder 1 Parameter 83101 Label 83102 Strobe 1 Control 2 Blink 3 Set Squawk 83103 Sounder LED 1 Always On 3 Follow Set 2 Always Off 4 Follow Alarm 83104 Battery Load Test 1 Never 2 Every 24 hours 83105 Proximity Level Response 83106 Volume 83107 Lamp 831071 Type 1 Alway...

Страница 222: ...re complying with the following standards EN50136 1 1 EN50136 1 1 A2 EN50136 2 1 EN50136 2 1 A1 EN50136 2 2 1998 PSTN complies with the following standards EN50136 1 2 1998 EN50136 1 3 1998 EN50136 2 2 1998 EN50136 2 3 1998 EN50136 1 4 1998 EN50136 2 4 1998 PSTN can be connected to Alarm Receiving Centre via any EN50136 compliant receiver which shall meet all requirements of securing messages When...

Страница 223: ...ter is automatically applied Code is rejected when trying to create a non existing code Possible physical keys calculations Physical keys are implemented in the Wireless Keyfobs It is assumed that only a user possesses a Keyfobs therefore a physical key is considered as access Level 2 Each Keyfob has 24 bit identification code comprising 2 24 options A Keyfob has to be recognized and registered by...

Страница 224: ...Report Codes Feature EN 50131 Compliance Timers Quick Key Required Value Phone Line cut delay Immediate 0 minutes Entry Delay 45 seconds maximum allowed AC Delay Immediate 0 minutes Jamming Time 0 minutes RX Supervision 2 hours System Controls Quick Key Quick Set Set to NO False Code Fault Set to Yes Forced Arming Set to NO Authorize engineer Set to YES Override Fault Set to NO Restore Alarm Set t...

Страница 225: ...htSYS See page 126 Step 2 Enter the location of the upgrade file 1 In the System menu Firmware Upgrade submenu enter the relevant information regarding the location of the upgrade file Server IP Enter the IP address of the router gateway where the upgrade file is located Default firmware riscogroup com Port Enter the port on the router gateway where the upgrade file is located Default 00080 File N...

Страница 226: ...40 minutes to complete This will vary according to whether the procedure is performed via GPRS or IP Once the files are downloaded the panel automatically starts with the upgrade procedure of the units connected to the system Note 1 During the upgrade process of the panel firmware there will be no display on the keypad 2 While downloading the files for the upgrade procedure the STATUS green LED on...

Страница 227: ...tion charges or costs of installation or any liability for direct indirect or consequential damages or delay Seller does not represent that its product may not be compromised or circumvented that the product will prevent any personal injury or property loss by burglary robbery fire or otherwise or that the product will in all cases provide adequate warning or protection Seller in no event shall be...

Страница 228: ...upport cn riscogroup com Spain Tel 34 91 490 2133 E mail support es riscogroup com China Shenzhen Tel 86 755 82789285 E mail support cn riscogroup com France Tel 33 164 73 28 50 E mail support fr riscogroup com Poland Tel 48 22 500 28 40 E mail support pl riscogroup com Belgium Benelux Tel 32 2522 7622 E mail support be riscogroup com Israel Tel 972 3 963 7777 E mail support riscogroup com USA Tel...

Отзывы: