Engineer Programming
Page
109
Quick Keys
Parameter
Default
Range
6.
Enter the time slot, meaning the maximum amount of time allowed
between the triggering events for them to be considered a valid
violation (
XX,YY
indicate the crossed zones).
Default:
1 min
Range:
1 to 9 minutes
Repeat the entire process, as required, for any additional zone links
(up to 10).
Alarm confirm
The Alarm Confirmation menu enables to define protection against false alarms and can be
used for alarm verification
Quick Keys
Parameter
Default
Range
Alarm confirm
Confirm partition
Defines which partitions are to be defined for alarm sequential
confirmation.
Each confirmed partition has a separate timer, which is equivalent to the
confirmation time defined in “Confirmation Time Window”.
A confirmed intruder alarm will be reported if two separate alarm
conditions are detected in the same confirmed partition, during the
confirmation time.
Cycle through the four partitions and press
to toggle
Y/N
Confirm zones
Define which zones are to be defined for alarm sequential confirmation.
When the first zone goes into alarm the system transmits the first zone
alarm. When the second zone goes into alarm, during the confirmation
time, the panel transmits the zone alarm and the police code.
Notes:
A confirmed zone will be part of the sequential confirmation only if the
partition in which the alarm occurs is defined as confirmed partition as well.
Any Code can reset a confirmed alarm.
If the first zone is violated and not restored until the end of the
confirmation time (no second zone alarm), than this zone will be excluded
from the confirmation process until the next setting.
Cycle through the eight zones and
to toggle
Y/N