05   Air Filter Error

Follow the procedure in the “Air Screen” section of the owner’s manual.

If the error code continues to flash after cleaning the air filter, review 

the items in “Code 10” or contact a qualified service technician.

07   Circulation Flow Rate has dropped below 2.1 gpm

Check water filter for blockage
Check pump operation and wiring
Clean Heat Exchanger

10   Air Supply or Exhaust Blockage

Ensure listed 4" b-vent is used and there are no reductions in the vent 

system

Check that nothing is blocking the vent, inlet screen or “Combustion Air 

Assembly”

Check all vent components for proper connections.
Check fan for blockage
Ensure vent length, vent size and combustion air comply with the 

requirements stated in the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54

or the 

Natural Gas and Propane Installation Code, CSA B149.1

.

11   No Ignition

Check that the gas is turned on at the water heater, gas meter, or cylinder.
Ensure gas type and pressure is correct.
Ensure gas line, meter, and/or regulator is sized properly.
Bleed all air from gas lines.
Verify dip switches are set properly.
Ensure appliance is properly grounded.
Ensure igniter is operational.
Check igniter wiring harness for damage.
Check gas solenoid valves for open or short circuits.
Remove burner cover and ensure all burners are properly seated.
Remove burner plate and inspect burner surface for condensation or debris.

12   Flame Failure

Check that the gas is turned on at the water heater and gas meter. Check for 

obstructions in the flue outlet.
Ensure gas line, meter, and/or regulator is sized properly.
Ensure gas type and pressure is correct.
Bleed all air from gas lines.
Ensure vent length, vent size and combustion air comply with the 

requirements stated in the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54

or the 

Natural Gas and Propane Installation Code, CSA B149.1

.

Verify dip switches are set properly.
Ensure appliance is properly grounded.
Check power supply for loose connections.
Check power supply for proper voltage and voltage drops.
Ensure flame rod wire is connected.
Check flame rod for carbon build-up.
Disconnect and reconnect all wiring harnesses on unit and PC board.
Check for DC shorts at components.
Check gas solenoid valves for open or short circuits.
Remove burner plate and inspect burner surface for condensation or debris.

13   Combustion Error

Review items listed under codes “05” and “10”

FE   Flammable Vapors Detected

Leave the area immediately, leaving the exit point open to allow 

ventilation

Do not touch any electric device (including phone or light switch)

Call emergency personnel from a neighbors phone

Do not try to reset the water heater or light the pilot to any other 

appliance

When safety personnel have identified the area as safe and all flammable 

vapors have been evacuated the units can be rest by unplugging the unit 

then plugging back in.
If “FE” continues to flash after area is determined safe, contact a qualified 

service technician.

16   Over Temperature Warning

Check gas type of unit and ensure it matches gas type being used.
Check for restrictions in air flow around unit 
Check for foreign materials in combustion chamber and/or exhaust piping.
Check for clogged heat exchanger.

30   FV Sensor Error

Check sensor wiring for damage.
Measure resistance of sensor.
Replace sensor.

31   Burner Sensor Error

Measure resistance of sensor.
Replace sensor.

32   Heat Exchanger Outgoing Temperature Sensor Fault

Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build-up.
Replace sensor.

35   Tank Temperature Sensor Fault

Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build-up.

Replace sensor.

38   CO or FV Sensor Error

Check sensor wiring for damage.
Measure resistance of sensor.
Replace PCB and sensors.

52   Modulating Solenoid Valve Signal Abnormal

Check modulating gas solenoid valve wiring harness for loose or damaged 

terminals.

Measure resistance of valve coil.

61   Combustion Fan Failure

Ensure fan will turn freely.
Check wiring harness to motor for damaged and/or loose connections.
Measure resistance of motor winding.

63   Circulation Flow Rate has dropped below 1.2 gpm

Check water filter for blockage
Check pump operation and wiring
Clean Heat Exchanger

71   SV0, SV1, SV2, and SV3 Solenoid Valve Circuit Fault

Check wiring harness to all solenoids for damage and/or loose connections.
Measure resistance of each solenoid valve coil.

72   Flame Sensing Device Fault

Ensure flame rod is touching flame when unit fires.
Check all wiring to flame rod for damage.
Remove flame rod and check for carbon build-up; clean with sand paper.
Check inside burner chamber for any foreign material blocking flame at flame 

rod.

Measure micro amp output of sensor circuit with flame present.
Replace flame rod.

73   Burner Sensor Circuit Error

Check sensor wiring and PCB for damage.
Replace sensor.

NO CODE   No hot water

Confirm the water heater is plugged in  and 120 volts is available.

14   Thermal Fuse

Check gas type of unit and ensure it matches gas type being used.
Check for restrictions in air flow around unit and vent terminal.
Check for low water flow in a circulating system causing short-cycling.
Ensure dip switches are set to the proper position.
Check for foreign materials in combustion chamber and/or exhaust piping.
Check heat exchanger for cracks and/or separations.
Check heat exchanger surface for hot spots which indicate blockage due to 

scale build-up.  Refer to instructions in manual for flushing heat exchanger.

Measure resistance of safety circuit.
Ensure high fire and low fire manifold pressure is correct.
Check for improper conversion of product.

Содержание REU-VA1320WF-US

Страница 1: ...d High combustion by setting both No 7 and No 8 dip switches to ON Fig 5 Ensure maximum water flow 13 Check the burner test point pressure 14 Adjust the high pressure potentiometer POT on the PC board as required to the pressure shown in Table 1 15 Return the unit to normal operation by setting dip switches 7 and 8 back to OFF Fig 6 Close all water taps 16 Turn OFF the gas supply and 120 V power s...

Страница 2: ...fuse Remove the fuse and check continuity through it If you have continuity through the fuseB then it is good Otherwise the fuse is blown and Wire Color Voltage Resistance Connector Pin s Tank Temperature Thermistor White Yellow at the PCB White White N A See Chart Above A2 A 3 A 4 Heat Exchanger Temperature Thermistor Brown Yellow at the PCB White White N A See Chart Above A3 A 7 A 8 Burner Senso...

Страница 3: ...SMALL LARGE MODUL ATING SOLENOID VALVE FLAME ROD POV F3 O O Y THERMALFUSES W W F1 OVERHEAT SWITCH A6 R R R BL P GY BR O Y W P BL R BK W AC120V AC120V HOT NEUTRAL HOT GROUND FUSE 5A SURGE PROTECTOR 3 1 G Y 1 3 I 1 GND I 2 W BK BR BL GND G Y IG ELECTRODE SPARK IGNITER G Y BK W W BK G Y GND 1 3 1 2 1 2 6 1 4 14 P PUMP COS CO SENSOR OPERATION UNIT P GY R W Y BK R W Y BK R R BK Y W BL BK R P Y Y OO O O...

Страница 4: ... identified the area as safe and all flammable vapors have been evacuated the units can be rest by unplugging the unit then plugging back in If FE continues to flash after area is determined safe contact a qualified service technician 16 Over Temperature Warning Check gas type of unit and ensure it matches gas type being used Check for restrictions in air flow around unit Check for foreign materia...

Страница 5: ...05 801 006 015 802 801 017 016 001 002 010 011 012 013 014 003 004 A A B B C C 725 120 125 132 131 121 727 127 726 827 828 111 110 113 114 116 103 803 115 112 117 130 133 750 825 730 804 126 134 135 123 122 724 ...

Страница 6: ...D D 405 406 751 806 703 704 805 102 101 701 705 700 402 401 404 824 101 100 821 708 702 823 400 408 409 826 410 822 124 723 722 714 712 711 729 715 716 807 825 728 713 720 721 710 ...

Страница 7: ...034 035 037 038 039 040 041 042 033 044 048 047 049 050 051 046 045 046 052 055 055 052 Pump Configurations 043 ...

Страница 8: ... Tank Thermistor 105000089 1 037 Drain Valve 107000118 1 132 Fan Casing Assembly 108000033 1 1 4 0 1 1 D 8 M r o s n e S R M 9 2 7 038 Diptube 107000119 1 133 Fan Motor Packing 109000106 1 730 Easy Connection 105000090 1 039 Thermistor Bracket 109000368 1 134 Fan Motor Bracket 109000107 1 750 CO Sensor 105000091 1 040 Shoe Horse Grommet 109000369 1 135 Noise Filter Ass y 109000108 1 751 FV Sensor ...

Отзывы: