Extended and Direct Flueing with Wall and Room Terminals
Condensate Drain
The condensate trap will collect condensate from the flue system. This condensate must be drained to the
outside of the building via a condensate drain pipe. In accordance with the installation instructions supplied
with the flue terminal.
The Direct flueing wall terminal can be extended using the methods as shown in
(Fig.5)
The total flue length should not exceed 9m and the number of 90° bends should not exceed 3.
When total vertical rise of flue exceeds 2 m a Condensation Trap / Drainage
MUST BE
fitted
(Fig.5, Method 4.)
.
Note: The through wall terminal is equivalent to a 1m length and counts as one 90° bend, these factors must be
taken into account when sizing a through wall installation.
1
100
2
000
195
155
500
150mm ceiling
ring supplied
with roof
terminal
Combustible
clearance
110mm
350
Where the total vertical flue height does not exceed 2 metres,
the fitting of a Condensation Trap / Drainage is not required.
As vertical height of flue installation is in excess of 2 metres,
a Condensation Trap / Drainage
MUST BE
fitted.
Use combinations of
fixed and adjustable
flue lengths to position
the installation, as flue
components can
NOT
be cut to size.
Use combinations of
fixed and adjustable
flue lengths to position
the installation, as flue
components can
NOT
be cut to size.
Method 1.
Method 3.
Method 2.
Flue Terminal
Flue Terminal
F
lue
T
e
rminal
Ensure a 3° fall to
the flue terminal.
Ensure a 3° fall to
the flue terminal.
Total vertical rise
not in excess of 2m
Method 4.
F
lu
e
T
e
rminal
Ensure a 3° fall to the
Condensate Trap.
The terminal clearances in AS5601 / AG601 do not apply to the Infinity REU V1616WF Water Heaters installed
side by side. The appliances are AGA certified to be installed side by side as shown in
(Fig.6)
, allowing for a
horizontal distance of 155mm between flues.
The minimum distance of 500mm between the underside of the cowl and the nearest part of the roof must still be
met.
(Fig.
4
)
(Fig.
5
)
Содержание REU-V1616WF
Страница 19: ...Infinity REU V1616WF 14 Issue 1 21 11 03 Rinnai 7 Cutaway Diagram ...
Страница 20: ...Infinity REU V1616WF 15 Issue 1 21 11 03 Rinnai 8 Operational Flow Chart ...
Страница 25: ...Infinity REU V1616WF 20 Issue 1 21 11 03 Rinnai 12 Wiring Diagram ...
Страница 47: ...Infinity REU V1616WF 42 Issue 1 21 11 03 Rinnai 20 Exploded Diagram ...
Страница 48: ...Infinity REU V1616WF 43 Issue 1 21 11 03 Rinnai ...
Страница 49: ...Infinity REU V1616WF 44 Issue 1 21 11 03 Rinnai ...
Страница 50: ...Infinity REU V1616WF 45 Issue 1 21 11 03 Rinnai ...
Страница 54: ...Infinity REU V1616WF Issue 1 21 11 03 Rinnai Notes ...