If refrigerant piping is already embedded in
the wall, do the following:
Hook the indoor unit on the mounting plate:
Prepare refrigerant piping:
Fig. 4.6
Move to left or right
30-50mm
(1.2-1.95in)
30-50mm
(1.2-1.95in)
Keep in mind that the hooks on the mounting plate
are smaller than the holes on the back of the unit.
If you find that you don’t have ample room to connect
embedded pipes to the indoor unit, the unit can be
adjusted left or right by about 30-50mm (1.25-1.95in),
depending on the model. (See Fig.4.5)
Page 14
CAUTION
Be extremely careful not to dent or damage the
piping while bending them away from the unit.
Any dents in the piping will affect the unit’s
performance.
Step 4: Prepare refrigerant piping
The refrigerant piping is inside an insulating
sleeve attached to the back of the unit. You must
prepare the piping before passing it through the
hole in the wall. Refer to the
Refrigerant Piping
Connection
section of this manual for detailed
instructions on pipe flaring and fla
re torque
requirements, technique, etc.
NOTE ON PIPING ANGLE
Refrigerant piping can exit the indoor unit from
four different angles:
• Left-hand side
• Left rear
• Right-hand side
• Right rear
Refer to
Fig. 4.4
for details.
Fig. 4.4
Indoor Unit
Installation
Fig. 4.5
Disassemble the louver:
Open and fix the position of the panel
Firstly, unscrew the two screws showed
in the picture below, then open the panel,
and fix the position of the panel by the
latch (see Fig.4.7).
1.
2.