Ember Installation Guide: 12890-B 02-18 

  |   

9

 

 8

  

 |   

Ember Installation Guide: 12890-B 02-18

Gas supply

Gas pipe sizing must consider the gas input to this appliance, as well as other gas 
appliances in the premises. The gas supply termination is inside the heater, and 
enters from the lower right hand side of the appliance.

Purging the gas supply

Foreign materials and debris such as swarf, 
filings etc. must be purged from the gas 
supply. Failure to do so may cause damage to 
the control valve causing it to malfunction.

Gas connection

A small spanner has been provided, located 
in the commissioning pouch on top of the 
PCB cover, to help with the gas connection as 
space is quite tight. Please return the spanner 
to the pouch when finished.

The use of a rubber hose for any gas 
connection to a fixed appliance is not 
authorised by the manufacturer.

Electrical supply

The Ember is fitted with a 1.5 m power cord and 3-pin plug. 
The power cord passes through a slot in the back left hand 
corner of the appliance.

The connection is either direct wired* or connected to a 
power point within the cavity. This must be connected to 
a dedicated earthed power point. The electric isolation 
switch must be accessible after the appliance has been 
installed. 

The fire must not be located immediately below a socket 
outlet (potential fire hazard). 

If the supply cord is damaged, it must be replaced by a licensed tradesperson. This must be a 
genuine replacement part available from Rinnai. 

* Consult a qualified electrician if direct wiring is required as it must comply with AS/NZS 5601 and AS/NZS 3000 and other 

relevant local regulations

Enclosure dimensions

Masonry

Mock chimney

600

700

W-width

700 mm

800 mm

H-height 

700 mm

700 mm

D-depth

400 mm min. 400 mm min.

Framing dimensions above are before the zero clearance 

frame is fitted.

For mock chimney installations the Ember MUST BE 

installed with the Ember Zero Clearance frame, which 

gives the required clearances to combustibles.

Actual chimney size needs to be at least 200 x 200 mm 

for the two flexi flues to fit down the chimney.

Corner installations

The Ember must be positioned within the enclosure on a flat level surface that 

allows free movement of the appliance. The enclosure must be capable of 

supporting 1.5 times the weight of the Ember.

approx. 320 mm

702 min.

 1404 

 25 

 993 

752 min.

 1504 

 25 

 1063 

Ember 600

Ember 700

600

700

W-width

Infill panel*
Masonry frame*

600 mm
600-750 mm
N/A

700 mm
700-850 mm
700-785 mm

H-height 

Infill panel*
Masonry frame*

600 mm
600-675 mm
N/A

600 mm
600-675 mm
600-638 mm

D-depth

400 mm min. 400 mm min.

* Enclosure dimensions can be larger if using an infill 

panel or a masonry frame.

Содержание Ember Series

Страница 1: ...Ember Installation guide Models RDV600N RDV600L RDV700N RDV700L ...

Страница 2: ...ai co nz www youtube com rinnainz www facebook com rinnainz Important Before you start 4 Ember specification 5 Dimensions 6 Gas and electrical supply 8 Enclosure dimensions 9 Clearances from combustibles 10 TV installation 12 Ember masonry installation overview 14 Ember mock chimney installation overview 16 Installing the zero clearance frame 18 Attaching the flexi flues to the spigot plate 19 Bur...

Страница 3: ... unit is installed higher up the wall the movement of air from the convection fan depending on the room configuration could create draughts Noise level 37 45 dB A Flueing Masonry Colinear flexi flue air intake Ø 75 mm exhaust Ø 100 mm Appliance must be installed with a Rinnai Ember flue system Flueing Mock chimney Colinear air intake Ø 75 mm exhaust Ø 100 mm to coaxial direct vent flueing inner Ø ...

Страница 4: ...ations Ember 700 with 4 sided frame mock chimney installations 580 640 644 380 590 26 18 287 618 740 380 590 680 18 312 740 644 380 590 26 680 18 312 695 790 95 95 600 658 825 92 5 92 5 700 695 890 95 95 Ember 700 with 3 sided frame masonry installations or mock chimney installations with a hearth 540 mm 500 mm Viewable glass dimensions same for both 600 models 640 mm 500 mm Viewable glass dimensi...

Страница 5: ...lled The fire must not be located immediately below a socket outlet potential fire hazard If the supply cord is damaged it must be replaced by a licensed tradesperson This must be a genuine replacement part available from Rinnai Consult a qualified electrician if direct wiring is required as it must comply with AS NZS 5601 and AS NZS 3000 and other relevant local regulations Enclosure dimensions M...

Страница 6: ...e the front of the fire or obstruct the fire in any way including the frame around the fire Wall surface above the fire The temperature of the wall surface directly above the fire may get warm and distort paint finishes or distort vinyl wall coverings For durability of surfaces please contact the manufacturer for their specification The below diagrams are to assist people in determining the cleara...

Страница 7: ...ension is the minimum clearance required to a mantel The image adjacent shows the dimension from the edge of the frame in the case of the Ember the 400 mm dimension is to be taken from the edge of the glass Always check with the TV manufacturer It is up to the owner to check the TV installation with the TV manufacturer some have warranty conditions that state a TV is not to be installed above a fi...

Страница 8: ...r engine with screws using the top and bottom fixings Slide the Ember in place and secure the side brackets to the enclosure using the three outer screw positions on each bracket to the brickwork using suitable fixings not provided Provided with the infill panel or masonry frame 9 Complete the gas connection Make the gas connection 10 Install the burn media and commission Install the glass granule...

Страница 9: ...s provided This frame is critical and must be installed as it automatically gives the required clearances to combustibles Refer p 18 for installation details 4 Flue system installed Install the coaxial to colinear adaptor Ensure it is self supported with the frame and screwed in place Attach the intake and exhaust flexi flues to the adaptor clamp and screw into place check clearances are maintaine...

Страница 10: ...round the fire 2 Keeps the enclosure square and provides rigidity above the fireplace 3 Allows for a thin profile frame and for the engine to slip easily in and out of the enclosure Attaching the flexi flues to the spigot plate The flexi flues need to be securely fixed to the engine spigot plate using the clamps provided To do this the spigot plate needs to be temporarily removed from the engine u...

Страница 11: ...starting Ember 600 stone set laid out in the correct order Adding the glass and vermiculite This step is common to both models and both types of burn media It requires removing the upper burn media tray to access the mesh holding tray 1 Unscrew the left and right tray screws to lift off the upper mesh holding tray 2 Carefully empty the bags of vermiculite and glass into the mesh tray blend togethe...

Страница 12: ...the back log onto the two log location brackets at the back of the burner The charred side faces to the front Step 2 Adding the granules and rockwool Place DO NOT POUR the granules ensuring even coverage around the burner ports so as not to cause blockages For the 700 you will need both granule packs for the 600 it s about a bag and three quarters Pinch and roll the rockwool into pea sized balls 6...

Страница 13: ...cket back into the burner 1 2 3 4 Step 1 Back row of stones Place the back row of stones as shown Step 2 Middle row of stones Place the middle row of stones BETWEEN the burner ports as shown Step 3 Front row of stones Add the front row of stones inside the grill A few of these will be angled slightly to cover the front of the burner bed Step 4 Adding the granules and rockwool Place DO NOT POUR the...

Страница 14: ...ch will be the same regardless of frame type for example 3 sided frame 4 sided frame or the 700 masonry frame 1 Position the frame assembly in front of the engine and connect the CAT5 cable to the frame This connects the push button control panel to the engine s box 2 Slide the two top frame hangers into the corresponding frame slots on the Ember engine and push the lower section into the recess o...

Страница 15: ...ity of the installer to check that under normal conditions of the appliance all flue gases are exhausted to the outside atmosphere and that there is no spillage of combustion gases into the room If the appliance cannot be made to perform correctly please contact Rinnai Normal flame pattern Abnormal flame pattern Installation checklist and customer handover Complete the installation checklist in th...

Страница 16: ...mm clearance to a combustible surface the underside of the adaptor has zero clearance and can be installed straight into wooden support joists Ø 100 mm exhaust flexi flue Requires a 50 mm clearance to combustibles Ø 75 mm intake flexi flue Requires a 50 mm clearance to combustibles Flue terminal locations Flue terminals must be compliant with the flue terminal locations shown in AS NZS 5601 1 The ...

Страница 17: ...er than the vertical 245 410 Flue cowl slides depending on wall thickness 590 Unit height Flue components 1 Ember adaptor R3653 Refer p 30 for clearance to combustible information for the Ember adaptor 2 Mock chimney horizontal flue kit R3654 3 Flue pipe s 150 1000 mm 4 Flue elbow 90 R3643 Max number of 90 bends one 5 Horizontal flashing kit R3646 6 Horizontal wall terminal R3650 Vertical terminat...

Страница 18: ...aptor Kit includes high wind roof cowl flue pipes 1200 mm x 3 wall straps x 3 If longer flueing is required order additional flue pipes Masonry chimney flexi vertical flue kit Code R3652 For installation into a masonry fireplace Allows the fire to perform more effectively by achieving a better draw Extends out to 8 m Kit includes flue cowl chimney flashing plate intake flexi Ø 75 mm LHS exhaust fl...

Страница 19: ...00 mm R3635 737 mm 953 mm 1200 mm R3636 949 mm 1165 mm Rise Offset Flue kits and components Ember flue adaptor Code R3653 Colinear to coaxial adaptor Contains adaptor locating plate 455 x 455 mm Ø 75 mm and Ø 100 mm flexi flues and four flue clamps Stretches out to 1 2 m Flue elbow 90 Code R3643 Used to facilitate between vertical and horizontal flueing Elbow swivels 360 at base Once joined effect...

Страница 20: ......

Страница 21: ...Rinnai co nz Experience our innovation 0800 746 624 http www youtube com rinnainz http www facebook com rinnainz Ember Installation Guide 12890 B 02 18 ...

Отзывы: