Rinnai Circ-Logic RU80i Скачать руководство пользователя страница 21

 

 

21 

      

Multiple Water Heater Installation – Through the 
Roof 

Locate the vent and intake air termination using the 
following guidelines: 

1.  For installations with multiple Tankless Water 

Heaters, refer to Figure 16 for proper exhaust and 
combustion air piping placement. 

2.  Roof penetration of the vent and intake air piping 

should be such that the combustion air intake is a 
minimum 12” (30.5 cm) from the adjacent vent pipe 
of the other water heater. For installations in the 
U.S. refer to Figure 16. For installations in Canada, 
refer to clearances required by CAN/CSA B149.1. 

Figure 15: Vertical Termination of U-Vent and        

Combustion Air Pipe 

PVC/CPVC Roof (Tee and upside down “U”)                   
Terminations:

 

Locate the vent and intake air termination using the 
following guidelines: 

1.  The total length of the vent or intake air piping 

must not exceed the limits given in Table 4-7 (this                         
document).  The equivalent length for 90° elbows 
and termination associated with the respective vent 
and intake air piping arrangement MUST be                       
subtracted from total length listed in Tables 4-7. 

2.  For roof terminations installed as shown in Figure 

15, the intake air piping must terminate using a tee 
or combination of elbows per figures 14 and 15. 
The termination must be installed 12” (30.5 cm), 
above roof or the highest anticipated snow level. 

3.  The vent must terminate vertically with a coupling 

to facilitate the bird screen and must be located 
12” (30.5 cm) minimum above the combustion air 
inlet as shown in Figures 14 and 15. 

4.  The vent and intake air terminations must be               

located a radial distance of 12” minimum (30.5 cm) 
from outer wall of vent termination to outer wall of 
combustion air intake termination; refer to Figures 
14 and 15. 

Figure 14: Vertical Termination of Tee-Vent 

and Combustion Air Pipe 

Figure 16: Vertical Termination of Multiple   

Water Heaters

 

 
 
All figures shown in this section is in reference to flat 
roofs.  For heights of venting passing through a 
pitched roof, refer to NFPA 54/ANSI Z223.1-09 (table 
and figure 12.7.2) and/or CSA B149.1-10 (figure 8.1) 

NOTE

 

Certified PVC/CPVC Vent Termination Options (continued) 

12” min 
above air     
intake                   
opening 

12” above 
anticipated 
snow level 
or grade 

Exhaust Vent Termination 

Combustion air termination 

12” min  

12” min 
above 
air     
intake                   

12” above 
anticipated 
snow level 
or grade 

Vent Termination 

Combustion air termination 

12” min  

12” min  

12” min 
above air     
intake                   
opening 

12” min  

12” above 
anticipated 
snow level 
or grade 

Vent Termination 

Combustion air termination 

Содержание Circ-Logic RU80i

Страница 1: ...TWIN PIPE PVC CPVC VENTING GUIDE FOR CONDENSING TANKLESS WATER HEATERS...

Страница 2: ...Multiple Water Heaters 22 17 Vertical Termination of U Vent and Combustion Air Pipe on a Pitched Roof 22 18 Ubbink Concentric to Twin Pipe Adaptor 23 Tables 1 Vent and Air Piping Materials 5 2 Recomm...

Страница 3: ...ERNATIVE TWIN PIPE PVC CPVC VENTING SYSTEM The newly certified vent system is comprised of a Concentric to Twin Pipe Adaptor adaptable to 3 and 4 inch sizes PVC CPVC pipes fittings and either the IPEX...

Страница 4: ...ection of this document Contaminated intake air will damage the water heater resulting in possible severe personal injury death or substantial property damage Exhaust Provide exhaust vent piping to Wa...

Страница 5: ...primer PVC ANSI ASTM D2564 CPVC ANSI ASTM F493 IPEX bird screens purchase separately Termination Vent Screens Polyethylene 3 Vent screen IPEX part 196051 4 Vent screen part 196052 Screens are frictio...

Страница 6: ...ls Before installation consider where air has the ability to travel within the building to the water heater Where possible install the water heater in a sealed closet so that it is protected from the...

Страница 7: ...snow level in your area Ref Description Canadian Installations US Installations A Clearance above grade veranda porch deck or balcony 12 inches 30 cm 12 inches 30 cm B Clearance to window or door tha...

Страница 8: ...at same level 0 30 m to an inside corner 0 30 m between terminals at same level 24 V 0 61 m to wall or parapet 12 V V 60 V V 1 52 m between terminals at different levels Figure 2 Required Clearances...

Страница 9: ...A blank copy of the Vent Length Calculation Sheet is located at the end of this guide Ensure switch 1 in the bank of eight tan dip switches is in OFF position if vent length is greater than 21ft 6 4m...

Страница 10: ...ed into the straight pipe lengths below 20 6 1 10 3 0 5 1 5 5 1 5 of 90 Elbows each 5 equivalent feet Max straight pipe vent length in feet meters 0 45 13 7 55 16 8 60 18 3 60 18 3 1 40 12 2 50 15 2 5...

Страница 11: ...ach 5 equivalent feet Max straight pipe vent length in feet meters 0 21 6 4 31 9 4 36 11 0 36 11 0 1 16 4 9 26 7 9 31 9 4 31 9 4 2 11 3 4 21 6 4 26 7 9 26 7 9 3 6 1 8 16 4 9 21 6 4 21 6 4 4 11 3 4 16...

Страница 12: ...stems ULC S636 Components of any certified system CANNOT be substituted with any other vent system s or unlisted pipes and or fittings All listed components primers and glues are part of the certified...

Страница 13: ...or other type of reducing fittings is required to transition to 4 pipe STEP 5 Apply lubricant to the gasket surface and coupling with finger prior to component attachment refer to installation exampl...

Страница 14: ...mbly Configuration The adaptor as supplied requires no additional parts to be used with standard 3 3rd party solid core PVC CPVC pipes refer to Figure 6 below for required parts for 3 PVC CPVC assembl...

Страница 15: ...ng material contact PVC CPVC manufacturer for a complete list IPEX Concentric Vent Kit CVK Installation For installations with multiple terminations maintain appropriate clearances between terminals r...

Страница 16: ...been determined cut a hole in the roof or wall large enough to accommodate the outer pipe The size of the hole can vary greatly depending on the roof pitch 2 As per the procedures outlined solvent ce...

Страница 17: ...o IPEX PVC CPVC FGV Concentric Vent Kit ONLY for required spacing for all other termination types refer to Figures 12 thru 16 NOTE Reference General Clearance Requirements section of this guide for im...

Страница 18: ...C Low Profile Termination Configuration VENTING INSTALLATION SEQUENCE 1 Install the water heater 2 Determine the termination method sidewall or vertical concentric or separate pipes etc 3 Determine pr...

Страница 19: ...kit Be sure to follow guidelines for solvent cementing as described in the System 696 Installation Guide 3 Use the supplied screws and anchors to secure the base to the wall a drilled 3 16 hole 1 3 16...

Страница 20: ...nd as shown in Figures 12 and 13 If the vent is terminated on a sidewall which is subject to high winds it is recommended to terminate the vent using a tee A tee provides the best protection against w...

Страница 21: ...terminate using a tee or combination of elbows per figures 14 and 15 The termination must be installed 12 30 5 cm above roof or the highest anticipated snow level 3 The vent must terminate vertically...

Страница 22: ...E DO NOT use lubricant between two PVC CPVC components Refer to cement manufacturer instruction for specific instructions and handling NOTICE Certified PVC CPVC Vent Termination Options continued Pitc...

Страница 23: ...cable WARNING Improper installation of vent system and components or failure to follow all installation instructions can result in property damage or serious injury Lubricant can be applied on the sea...

Страница 24: ...10 Approved PVC CPVC Termination Components OEM OEM orCert Product Description Diagram Equivalent Length Ft IPEX Purchased separately 196006 197009 3 Inch 196021 197021 4 Inch System 636 PVC CPVC FGV...

Страница 25: ...mber of fittings Equivalent Vent Length Total Equivalent Length 1 90 elbow x 5 2 45 elbow x 2 5 3 IPEX Low Profile Termination x 5 4 IPEX 4 Concentric Termination x 20 5 IPEX 3 Concentric Termination...

Страница 26: ...26 NOTES...

Страница 27: ...27 NOTES...

Страница 28: ...100000357 01 3 2014...