Rinnai 44
Ducted Gas Heater IM
No.
DISPLAY
DESCRIPTION
7
H01 ID07: 0
ZONE/REFRIGERATION /HUMIDIFIER MODE
Value
System
Configuration
Zone
Connection
Add-On
Connection
Humidifier
Connection
0
Heating
N/A
N/A
N/A
1
Heating
Heater PCB – up to 4
N/A
N/A
2
H Add-On Heater PCB – up to 4
Heater PCB
‘ADD-ON’ terminal
N/A
3
H
Humidification
Heater PCB – up to 4
N/A
Heater PCB ‘ADD-
ON’ terminal
4
H
Humidifi
Add-On
Heater PCB – up to 3
(A,B,C)
Zone Module – 1
only (D)
Heater PCB
‘ADD-ON’ terminal
N/A
5
Heating
Zone Module – up
to 4
N/A
N/A
6
H
Add-On
Zone Module – up
to 4
Heater PCB
‘ADD-ON’ terminal
N/A
7
H
Add-On
Zone Module – up
to 3
Zone Module
‘ADD-ON’ terminal
N/A
8
H01 ID08: 1000
COOLING: ZONING MINIMUM FAN SPEED SETTING
The minimum RPM to which the fan will operate with the maximum number of outlets closed,
with the networker zoning in heating mode.
DO NOT SET BELOW 1000
9
H01 ID09: 0
DO NOT ADJUST
10
H01 ID10: 30
Damper motor Open/Close time can be adjusted between 5 and 240 seconds - factory default
30 seconds
Adjust Networker Parameters
Adjust heater parameters via a networker, as follows:
a.
Press Key 5. 'Clock setting mode' displays. Confirm that the clock display is flashing.
b.
Press and hold Key 2 and Key 4 until 'Installer parameter access' displays.
c.
After the message clears, press the mode key (M) to toggle between networker parameters (n01), and heater
parameters (H01). If more than one networker or heater unit is configured in the system, repeatedly press the
mode key until the desired heater unit is selected, e.g.
H01
ID01: 1.
d.
Press Key 1 or Key 2 to scroll through, and select, the required parameter ID, e.g. H01
ID01
: 1 (refer to Table
10). (Key 1 = next ID, Key 2 = previous ID.)
e.
Turn the rotary dial to adjust the parameter value, e.g. H01 ID01:
1
.
f.
Press the on/off button to save and exit.
Note:
All settings are saved automatically when the on/off button is pressed to exit networker set-up mode.