Rinnai Brivis CC315 Series Скачать руководство пользователя страница 20

Brivis 20 

Ducted Gas Heater IM

6.  COMMISSIONING AND CONTROL SETTINGS

All of these heaters have been factory tested, but should be commissioned and adjusted in accordance with the 

following instructions to ensure efficient and optimal heating performance. Remember:
•  Mains power must be switched OFF before any wiring is touched.
•  Commissioning must be carried out by a qualified trades person.
•  If the heater cannot be adjusted to operate in accordance with these instructions, contact the Customer Service 

Centre (refer to the back cover).

6.1  COMMISSIONING INSTRUCTIONS

6.1.1  Initial Damper Settings

Generally, a correctly designed and installed ducted system should have the following initial damper settings:
•  Living areas: 100% open
•  Bedrooms: 50% open
•  Bathrooms, ensuite and laundry: 25% open.

6.1.2  Initial Ignition and Gas Inlet Pressure Check
a. 

Turn OFF the 240 Volt AC power supply at the fixed switched socket outlet adjacent to the unit.

b. 

Ensure the gas cock adjacent to the heater is in the OFF position.

c. 

Locate gas valve inlet pressure test point, remove the grub screw and insert your test point fitting (hose tail 1/8” 

NPT).

d. 

Attach a manometer to the test point.

e. 

Ensure that all air has been purged from the gas piping and then turn ON the gas cock adjacent to the unit.

f. 

Turn on the 240 Volt AC power supply adjacent to the unit.

g. 

Go to the Thermostat, turn it ON and increase the temperature setting so that it calls for heat 

h. 

The unit will now attempt to ignite.  If the ignition attempt fails the heater will cycle through five ignition attempts 

before locking out.

i. 

Once the ignition is successful allow the unit to run for one minute, ensuring the gas supply pressure does not 

fall to below 1.1 kPa for natural gas and 2.7 kPa for LPG heaters. 

This should be done with all other gas 

appliances operating at their full capacity.

j. 

If the reading is below the minimum requirement and cannot be adjusted any higher, this indicates the incoming 

gas supply is inadequate (check supply pipe for blockage, check pipe sizing and gas meter size).

k. 

Turn the unit OFF at the thermostat, isolate the gas and the 240 Volt power supply adjacent to the unit.

l. 

Remove and replace test point with the grub screw.

Note: 

If there is air in the gas line, the heater may not ignite on the first attempt. Ignition attempts will occur automatically. Allow time 

for the heater to rectify itself as it may simply be purging air.

If the heater does not attempt pilot ignition at all: 
•  Check the Lighting Procedure again and if it still fails to light, by-pass the Thermostat by removing cables from 

the terminal block at the unit and link (bridge) terminals “R” and “W”. If it then lights, there is a fault with the 

wires to the Thermostat or in the Thermostat itself. If it does not light, check the overheat switch has not tripped 

or the 2 amp fuse has not blown.

6.1.3  Start & Check Burner Pressure

•  Repeat steps 'a' to 'g' in Section 6.1.2.  For step 'c' relocate the test point fitting from the inlet pressure test point 

location to the burner pressure test point location, either on the gas valve or the manifold.

•  Take a manometer reading of the test point pressure and confirm it is equal to the figure shown on the appliance 

data label. If the pressure reading is not correct adjust the gas valve pressure regulator either up or down to 

match the required test point pressure. If the pressure is lower than the required amount and cannot be adjusted 

any higher, this indicates that the incoming supply pressure is not sufficient (check supply pipe for blockage, 

pipe and gas meter sizing).

Содержание Brivis CC315 Series

Страница 1: ...Compact Classic Ducted Gas Heater Installation Manual Brivis Models CC315 CC320 CC325 CC330 by...

Страница 2: ...B 276 2004 Local Regulations and Municipal Building Codes including local OH S requirements This appliance must be installed maintained and removed only by an Authorised Person For continued safety of...

Страница 3: ...lations 10 3 Heater Dimensions and Clearances 11 3 1 Compact Classic 11 3 2 Service Clearances 12 3 3 Splitting Compact Classic Heaters 13 3 4 Duct Connection 13 3 5 Flue Instructions 15 3 5 1 General...

Страница 4: ...ing and cooling systems Local Gas and Electricity Authorities SuperSizeGuide Building Code of Australia BCA including local OH S requirements Environment Authorities This appliance must be installed m...

Страница 5: ...ions 1 2 INSTALLER DUE DILIGENCE FOR CHANGEOVERS Modern ducted gas heaters even those that are physically like for like typically have different technical specifications and control systems from exist...

Страница 6: ...uctions may preclude company service personnel from being able to service the unit DISCLAIMER IMPORTANT This document is a guide only Laws regulations and industry standards can vary between States an...

Страница 7: ...g and cooling systems Local Gas and Electricity Authority Codes Product Sizing Guide Local Building Regulations Environment Authorities National Construction Code of Australia NCC Note The manufacture...

Страница 8: ...g to local regulations IMPORTANT Switch OFF the power and unplug the heater before touching any wiring If any electrical wiring is damaged it must be replaced by the manufacturer its service agents or...

Страница 9: ...om the controls access panel side and fan motor access panel side s for the entire length of the heater The air gap created between the base of the heater and the platform by the heater s supports mus...

Страница 10: ...ree ventilation area using A T x F where A minimum free ventilation area mm2 T total gas consumption of all gas appliances MJ hr e g CC320I V2 90MJ hr F factor detailed in the table below Table 1 Vent...

Страница 11: ...24 168 244 407 385 615 338 386 236 485 300 300 CC320IXA V2 215 553 183 724 168 244 407 385 615 338 386 236 485 350 350 CC325I V2 215 553 183 724 168 244 407 385 615 338 386 236 485 300 300 CC325IXA V2...

Страница 12: ...vertical clearance Controls Tray Position Note Heater shall be positioned in the above orientation only for service access Method 2 In Ceiling and Under Floor Diagram 5 Internal Clearances Note All m...

Страница 13: ...rder 3 4 DUCT CONNECTION There are two options available for the Return Air Please refer to Diagram 7 for configuration of the unit 1 Preferred Option is Return Air on fan housing side ex factory 2 Al...

Страница 14: ...he Blank Panel 2 Remove Blank Panel from the appliance 3 Insert two screws removed in Step 1 to the bottom of the Side Pop panel Blank panel Blank panel Insert screws 4 Remove the two bottom screws fr...

Страница 15: ...e Flue Terminal In specific installations for example under the floor it is recommended that a remote terminal be used to terminate a horizontal flue on the outside wall of the building Please refer t...

Страница 16: ...d To facilitate Add On Cooling or Fan Only operation an additional accessory ACC LOOM ADD ON RELAY CLASSIC Brivis Part No B063283 must be fitted To configure a Compact Classic heater for Add On coolin...

Страница 17: ...gulations Requires Brivis programmable Thermostat Contact Brivis Technical Support for information on superseded Brivis Heaters Relay Wires PCB Wires Field Supplied Wires To Add On Cooling Unit For co...

Страница 18: ...g ceiling diffusers then the return air inlet should be at a low level Ceiling systems with a high level return air may result in reduced performance Note It is important that the ducting should be w...

Страница 19: ...operate efficiently with more ceiling outlets fully open if properly balanced There is not a limit maximum number of floor outlets so Table 4 lists the typical number for each heater model The outlet...

Страница 20: ...e does not fall to below 1 1 kPa for natural gas and 2 7 kPa for LPG heaters This should be done with all other gas appliances operating at their full capacity j If the reading is below the minimum re...

Страница 21: ...the warm air at any outlet is not more than 45 C above the return air temperature The fan continues to run while the burners are operating Once Confirmed Turn the heater OFF at the thermostat Ensure t...

Страница 22: ...300 0 21 0 30 540 520 500 480 52 250 1 8 4 10 CC320I V2 90 90 19 19 300 0 21 0 30 540 520 500 480 53 315 2 5 4 10 CC320IXA V2 90 90 19 19 350 0 24 0 35 625 596 570 545 53 315 2 5 4 10 CC325I V2 107 10...

Страница 23: ...Brivis 23 Ducted Gas Heater IM NOTES...

Страница 24: ...ormation visit www rinnai com au or email enquiry rinnai com au Rinnai has a Service and Spare Parts network with personnel who are fully trained and equipped to give the best service on your Rinnai a...

Отзывы: