15. EXHAUST AND VENTILATION
IMPORTANT
Exhaust fans may be required if insufficient free exhaust area exists. If the exhaust fan is the only
exhaust or ventilation outlet, then its capacity should be at least equal to the Cooler’s air output.
Door = 1�6m²
Hinged Window = 0�3m²
Sliding Window = 0�7m²
Average ventilation area provided by various openings when fully opened�
Brivis Models
Number of average size windows
& doors
(suggestions only)
Highest
Fan
Setting
Lowest
Fan
Setting
Contour
Series
Promina
Series
Advance
Series
AD Series
L37
P36
F36DS
One door and a hinged window
1�9 m
2
1�1 m
2
L47
P46
P56
F46DS
F56DS
AD56D BAL
Three sliding windows or one door &
two hinged windows
2�3 m
2
1�4 m
2
L57
P66
F66DS
AD66D / BAL
Four sliding windows or one door
and four hinged windows
2�8 m
2
1�7 m
2
L67
P76
F76DS
Five sliding windows or one door
and five hinged windows
3�1 m
2
1�9 m
2
L77
F86DS
AD86D
Six sliding windows or one door and
six hinged windows
3�4 m
2
2�1 m
2