10 Product Specifications

 

10-1. List of specifications 

 

 

- 51 - 

 

 
 
 
 
 

10 

Product Specifications 

 
 

10-1. List of specifications 

 
<ATEX/IECEx Specifications> 

Detection principle 

Non-dispersive infrared absorption type 

Detectable gas 

Combustible gas / Toxic gas 

Applicable gas detector head 

SD-1DRI 

Concentration display 

Seven-segment LED (four-digit) 

Detection range 

Depend on Detectable gas 

Display resolution 

Depend on Detectable gas   

Detection method 

Aspirator suction type 

Sampling condition 

Equivalent to atmospheric pressure (compressed air: 0.1 - 0.7 MPa, maximum use amount: 3 
L/min <converted into atmospheric pressure>) 

Flow rate 

1.5 ± 0.1 L/min 

Alarm setpoint 

Depend on Detectable gas   

Power display 

POWER lamp on (green) 

External output 

Gas concentration signal/alarm contact (gas alarm or fault alarm, gas/fault common alarm) 

Alarm accuracy 
(under the same conditions) 

Within ±25% to the alarm setpoint value (Combustible gas) 
Within ±30% to the alarm setpoint value (Toxic gas) 

Alarm delay time 
(under the same conditions) 

Within 30sec or 60sec 
(when introducing 1.6 times thicker gas than alarm setpoint value) 
(Depend on gas, without piping delay time and communication delay time) 

Gas alarm type 

One-step alarm (H) 

Gas alarm display 

ALM lamp on (red) 

Gas alarm pattern 

Non latching (auto-reset) 

Fault alarm/self diagnosis 

System abnormalities/sensor abnormalities 

Fault alarm display 

FAULT lamp on (yellow)/detail display 

Fault alarm pattern 

Non latching (auto-reset) 

Alarm contact 

No-voltage contact 1a, de-energized (energized in response to an alarm) or energized 
(de-energized in response to an alarm) 

Contact capacity 

250 VAC - 0.5 A/30 VDC - 0.5 A (resistance load) 

Transmission system 

3-wire type analog transmission (common cable for power and signal <power, signal, common>) 

Transmission specifications 

4 - 20 mA DC (linear/load resistance under 300 

, resolution divided into 200) 

Transmission cable 

CVVS1.25mm

2

 or 2.0mm

2

 - 3-core (when the contact is not used) 

CVVS1.25mm

2

 or 2.0mm

2

 - 5-core (when the contact is used) 

Transmission distance 

Below 1.25 km 

Various functions 

Alarm delay/suppression 

Power supply 

24 VDC (17 

 26.4 VDC) 

Power consumption 

Maximum 2 W 

Cable connecting port 

Pressure proof packing gland 
(Cable gland<G3/4> or Adapter A<NPT1/2> or Adapter B<NPT3/4>) 

Tube connecting port 

Gas IN: Rc1/4 (O.D 

Φ

6-1t, half-union for Cu or SUS tube <Bs or SUS> supplied) 

OUT: O.D 

Φ

8-1t, flare union for Cu or SUS tube (Bs or SUS) 

Compressed air IN: O.D 

Φ

8-1t, flare union for Cu tube 

Initial clear 

Approx. 25 seconds 

Operating temperatures 

-20 - +60 C (at a constant condition) 

Operating humidities 

Below 95% RH (Non-condensing) 

Structure 

Wall mounting sampling unit (Cu or SUS type) 

Explosion-proof structure 

Flame-proof enclosures 

Explosion-proof class 

2G Ex db 

C T6 Gb(ATEX) / Ex db 

C T6 Gb(IECEx) 

External dimensions 

Approx. 400 (W) x 265 (H) x 102 (D) mm 

Weight 

Approx. 5.6 kg 

Outer color 

Munsell 7.5BG5/2 

* When a half-union for gas IN side is changed, check also the external filter (IN/OUT diameter) carefully.

 

Содержание SD-1DRI-AS

Страница 1: ...PT2E 2117 Smart transmitter Gas Detector Head SD 1DRI AS Operating Manual PT2E 196 PT2 196 ...

Страница 2: ... where the performance of the detector can be ensured In facilities compliant with the High Pressure Gas Safety Act an alarm setting below our standard alarm setpoint may trigger a false alarm 3 This is a safety unit not a control unit The alarm contact output of the detector must be used for an external alarm lamp buzzer while the alarm signal output must be used for an indicator or external reco...

Страница 3: ...8 4 6 How to tube 23 5 How to Operate 24 5 1 Preparation for start up 24 5 2 Basic operating procedures 24 5 3 How to start the detector 25 5 4 Modes 26 5 5 User mode 27 5 6 Flow Rate Adjustment 30 5 7 How to exit 30 6 Operations and Functions 31 6 1 Gas alarm activation 31 6 2 Fault alarm activation 32 6 3 External output operation 33 6 4 Other functions 34 7 Maintenance 35 7 1 Maintenance interv...

Страница 4: ...s such as examples of LED display 1 2 Purpose of use The detector is a fixed type gas detector head that detects leak of combustible gases toxic gases and that performs the alarm activation when the gas concentration is over the setting value This detector is a safety unit not an analyzer or densitometer which performs quantitative qualitative analysis measurement for gases Please fully understand...

Страница 5: ......

Страница 6: ......

Страница 7: ......

Страница 8: ......

Страница 9: ......

Страница 10: ......

Страница 11: ......

Страница 12: ......

Страница 13: ...compressed air 8 Compressed air inlet An inlet for compressed air 1 MENU ESC key Used to enter the maintenance mode It is also used to cancel in a specific mode 2 SET key It is used for value confirmation and so on in a specific mode 3 key Used to switch menus or change a value UP 4 key Used to switch menus or change a value DOWN 5 Power lamp Power lamp Detection mode It lights up in green Mainten...

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ...Φ14 0 When the four hexagon socket head bolts of the gas detector head SD 1DRI are loosened and the lid is opened the following terminal plate appears Grounding terminals are provided one inside and the other one outside Figure of Terminal Plate 24 VDC DC 1 Common 2 4 20 mA Sig 3 Contact 4 Contact 5 Specifications of Terminal Plate Specifications of terminal plate Rated voltage 250 VAC Rated curre...

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ......

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ......

Страница 33: ...ration Display In case of over the detection range Over Scale is displayed on the LED Power Indicator Lamp POWER Green During operation this lights up continuously Alarm Indicator Lamp ALM Red It lights up when the alarm setpoint value is reached to or exceeded Contact Activation The contact is activated when the gas concentration reaches or exceeds the alarm setpoint value only when the alarm is ...

Страница 34: ... check that the gas concentration reading dropped Equipped with a protective gear to avoid dangers caused by possibly remaining gases before accessing the gas leak point and then check that gases remain by using a portable gas detector Determine that the point is free from dangers and take actions to fix the gas leak 6 2 Fault alarm activation A fault alarm is triggered when the detector detects a...

Страница 35: ......

Страница 36: ......

Страница 37: ...m the zero adjustment after ensuring that no other gases exist around it Flow rate check Check the flow rate to find abnormalities Filter check Check the dust filter for dust or clogging Alarm Test Inspect the alarm circuit by using the alarm test function Span Adjustment Perform the sensitivity calibration by using the calibration gas Gas Alarm Check Check the gas alarm by using the calibration g...

Страница 38: ...ter Alarm Test Inspects the alarm circuit by using the alarm test function Checks the alarm lamps Check each activation of ALM Checks the external alarm Checks the activation of the external alarm such as a buzzer Span Adjustment Performs the sensitivity calibration by using the calibration gas Gas Alarm Check Checks the gas alarm by using the calibration gas Checks the alarm Checks the alarm acti...

Страница 39: ......

Страница 40: ......

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ......

Страница 49: ...commended regular replacement parts No Item Maintenance intervals Replacement intervals year Quantity pieces unit Remarks 1 Guard assembly 6 months 3 8 years 1 2 Aspirator cap 6 months 3 8 years 1 After replacements having need of operation check by professional service engineers To maintain the safety operation of the detector please use our maintenance service Request RIKEN KEIKI for it NOTE The...

Страница 50: ......

Страница 51: ...additional measures Cable abnormalities open circuit not connected short circuit Check the wiring of detector and related devices around it Abnormal operations Disturbances by sudden surge noise etc Turn off and restart the detector If such a symptom is observed frequently take appropriate measures to eliminate the noise Sensor abnormalities E 1 The sensor is not connected or improperly connected ...

Страница 52: ...pletely For information on actions such as removal filter please contact RIKEN KEIKI Disturbance by noise Turn off and restart the detector If such a symptom is observed frequently take appropriate measures to eliminate the noise Sudden change in the environment When the environment temperature etc changes suddenly the detector cannot adjust to it and is affected by it In some cases the detector t...

Страница 53: ...ellow detail display Fault alarm pattern Non latching auto reset Alarm contact No voltage contact 1a de energized energized in response to an alarm or energized de energized in response to an alarm Contact capacity 250 VAC 0 5 A 30 VDC 0 5 A resistance load Transmission system 3 wire type analog transmission common cable for power and signal power signal common Transmission specifications 4 20 mA ...

Страница 54: ...10 Product Specifications 10 1 List of specifications 52 Outline Drawings Cable gland G3 4 Adapter A NPT1 2 ...

Страница 55: ...10 Product Specifications 10 1 List of specifications 53 Outline Drawings Adapter B NPT3 4 ...

Страница 56: ...amp on yellow detail display Fault alarm pattern Non latching auto reset Alarm contact No voltage contact 1a de energized energized in response to an alarm or energized de energized in response to an alarm Contact capacity 250 VAC 0 5 A 30 VDC 0 5 A resistance load Transmission system 3 wire type analog transmission common cable for power and signal power signal common Transmission specifications ...

Страница 57: ...10 Product Specifications 10 1 List of specifications 55 Outline Drawings ...

Страница 58: ......

Страница 59: ...ection range LEL A unit which the lower explosive limit LEL of the combustible gas to be detected is set to 100 Calibration Adjusts the readings to the calibration gas concentration value by using the calibration gas Zero suppression A function to cut off the specific drifting that the sensor has Alarm delay time A function which temporarily suspends activation to prevent a false alarm caused by n...

Страница 60: ......

Отзывы: