Table 3, continuation
The Detector Mode
Indication
Note
Radio communication
quality appraisal
See sect. «Radio communication quality appraisal»
«Failure in channel 1»
«Failure in channel 2»
Orange LED indication dual
blinking with 12 sec period *
State indication
is on and
«Identification»
indication is off
«Normal»
Indication is off
*) – LED indication of the Detector state
**) – Sound indication of the Detector state
6 Binding with the CP
«Binding» mode is used for logging the Detector in the CP and service
information exchange.
6.1 Prepare the CP in accordance with CP reference guide.
6.2 If it is necessary to log the Detector in double-channel mode, hook up TS
to the Detector as shown in Figure or short-circuit the terminals of the Detector
«-» and «Channel 2». For the single-channel mode neither hooking on, no short-
circuit is required.
6.3 Set the backup power supply battery to the holder plate on the PCB
other side.
6.4 Set the main power supply battery to the holder plate (6).
6.5 Periodical LED indicator blinking green is evidence of binding process.
6.6 In case of mentioned above LED indication absence,
short-circuit
«RESET» terminals for 2 – 3 sec.
6.7 Successful binding procedure complying is indicated by LED indicator
lighting red for 2 – 3 sec.
6.8 The time limit for the binding process of the Detector is 100 sec. To
restart the binding procedure, short-circuit «RESET» terminals for 2 – 3 sec.
7
«
Stand Alone
»
mode
7.1 The Detector changes to stand alone mode upon the expiry of 100 sec
binding procedure.
7.2 During operation in the stand alone mode the Detector has no
communication with CP and it’s state is displayed only by means of LED and
sound indication (see Table 3).
7.3 During operation in the stand alone mode LED and sound indication is
always ON under condition of «Tamper» message absence.
8 Communication Quality Appraisal
8.1 For radio communication quality appraisal it is necessary to:
- place initially backup and then main power supply batteries to the
correspondent holder plates;
- set the Detector on the assumed place of installation;
- push and then release case tamper.
8.2 After case tamper releasing the Detector generates case tamper
alarm message, transmits it via radio communication channel and represents
communication quality with CP by LED indication in accordance with the Table 4.
Table 4
LED Indication
Radio
communication
quality appraisal
Recommendations
Color
Mode
Green
Three
blinks
Excellent
Install the Detector on
this place
Green
Two blinks
Good
Green
One blink
Communication
established
Choose another place
for installation or use a
repeater*)
Red
Four blinks
No communication
*)
–
«
Ladoga BRSS-RK-RTR
»
or
«
Ladoga BRSS-RK-RTR
»
ver. 1
9 Installation
9.1 Drill holes for fastening the Detector elements. You may use the FD and
the SPM base without the PCB for marking out the holes.
The FS should be located in the place, where the water spilled in the
detection zone close the sensor contacts. The FS installation with the terminals
downwards ensures generation of alarm signal over appearance the liquid sheet
with a thickness exceeding 1 mm. The FS installation with the terminals sidewise
provides easy access to the sensor terminals for removal of a liquid from the FS
surface between the terminals after the leakage elimination.
9.2 Fasten the FS on the mounting surface with screws or a water-resistant
glue. Fasten the SPM base on the mounting surface with screws. For the wall-
tamper monitoring, the second screw must be screwed in a hole under the wall
tamper. Install the PCB, connect the FSs to the loop terminals (the red wire to
the «+» terminal). Install the cover.
«RIELA» JSC, www.rielta.ru,
17 Chapayeva St., Saint Petersburg, Russia, 197101, [email protected],
tel./fax: +7 (812) 233-0302, 703-1360,
Technical support: tel.: +7 (812) 233-29-53, 703-13-57, [email protected]
Made in Russia
Mod. 3 dd. 09.11.15
№ 00175
10 Troubleshooting
Table 5
CP Message
Elimination Procedure
«Tamper»
Check the security of the SPM fastening, close
it’s cover
«Alarm in Loop 1»
«Alarm in Loop 2»
In case there is no liquid (moisture) between the
FS contacts, check the absence of a short circuit
between the wires
«Failure in Loop 1»
«Failure in Loop 2»
Check the integrity of the wires connecting the
FS and the SPM and their fastening to the SPM
terminals
«Main power supply
battery fault»
Replace the main power supply battery and the
backup one
«Backup power supply
battery fault»
Replace the backup power supply battery
11 Manufacturer’s Guarantees
11.1 The manufacturer guarantees conformity of the Detector to the
requirements of technical conditions provided the transportation, storage,
installation and operation conditions are observed.
11.2 The guaranteed shelf life of the Detector is 63 months since the date of
manufacture. The guaranteed useful life is 60 months since the day of putting
into operation within the limits of the guaranteed shelf life.
11.3 The detectors that are found non-conforming to the requirements of the
specifications will be repaired by the manufacturer, provided the installation and
operation rules have been observed.
Note
– Warranty obligations do not apply to batteries.
12 Storage and Transportation
12.1 Factory-packed detectors can be shipped by any transport means
in covered vehicles (in railway, cars, trucks, sealed heated compartments of
aircraft, holds etc). The Detector is resistant to:
a) transport pounding with the acceleration 30 m/sec
2
with impact frequency
from 10 to 120 impacts/sec or 15000 impacts with the same acceleration;
b) the ambient temperature minus
50 … +50 °С;
c) relative air humidity (95 ± 3) % at the ambient tempe35 °С.
12.2 The uptime of the Detector after transportation under the conditions
different to exploitation conditions – not more than 6 hours.
12.3 The storage room shall be free from current-conducting dust, acid
vapors, alkali and gases that cause corrosion and destroy insulation.
12.4 The uptime of the Detector after transportation under the conditions
different to exploitation conditions – not more than 6 hours.
13 Acceptance and Packing Certificate
Wireless flood sensor «STZ-RK»,
batch number _________________,
has been manufactured in compliance with the existing technical
documentation, considered fit for operation and packed by the «RIELTA» JSC.
Person in charge of acceptance and packing
QC representative_________________ __________________.
Date, month, year