6 Switching ON and Setting Up
Generally operational sequence consists of the following steps:
- binding (logging) the Detector with the CP;
- choosing place of installation;
- operability testing;
- installation.
7 Binding with the CP
7.1 Prepare the CP for the new device logging in («Binding» mode) in
accordance with the CP Manual. In the Detector radio-coverage zone only one
CP prepared for binding procedure should be located.
7.2 Remove the Detector from the base rotating it counter clockwise.
7.3 Install first the backup power supply battery, and after the main one into
the holders, located on the PCB (if the battery is installed by manufacturer,
remove an isolator).
7.4 Close «RESET» contacts on the PCB by any metal object and hold it until
«Binding» indication switches on.
7.5 Fulfill binding. After a successful binding with the CP, the red LED
indicator blinks shortly.
Note
– The time during which the Detector operates in the «Binding» mode
is limited to 100 s. To repeat binding procedure, repeat Cls. 7.3 – 7.5.
8 Standalone Mode
To provide the Detector operation independently without CP, act as follows:
- remove the Detector from the base rotating it counter clockwise.
- remove the isolating plates between «+» contacts and battery holders
primarily from backup, and then from main power supply batteries.
- close «RESET» pin contacts on the PCB by any metal object and hold it until
«Binding» indication switches on.
- wait for approximately 100 s till the end of binding mode without binding
with the CP.
9 Installing the Detector
When choosing the place of installation for the Detector, take into account
the fact that the Detector refers to fire Detectors with operability control and
therefore, only a single Detector may be installed in the monitored premise.
All other conditions being equal, the location chosen for the installation of the
Detector should meet the following requirements:
- prevention of water ingress from the front side and the base side;
- minimum vibrations of building structures;
- minimum illumination;
- maximum distance from sources of electromagnetic interference and infrared
radiation (heating units);
- maximum convenience of installation, checking and removal of the Detector.
Transmission quality may differ from premise to premise; therefore, it is
advisable to apprise a communication quality before the Detector is finally
installed.
10 Communication Quality Appraisal
10.1 Bring the Detector to the assumed place of installation.
10.2 Press the arm of sensing element, ensuring control of the Detector
removal from the base.
10.3 The Detector displays the quality of communication by LED indication
as per Table 4.
Table 4 Communication quality appraisal results
LED Indication
Communication
Quality Appraisal
Recommendations
Color
Mode
Green
Three blinks
Excellent
Install the Detector at
this place
Green
Two blinks
Good
Green
One blink
Communication established
Choose another place
for installation or use a
repeater
Red
Series of blinks
No communication
Rev. 3 of 18.04.2018
№ Э00464
v.2
11 Operability Test
Press the operability test button and hold it during not less than 5 s, until the
Detector switches «Fire» LED indication and sound signal. Make sure that «Fire»
alarm message at correspondent zone is received.
Feed testing spray into the optical smoke chamber opening. In case of
operation with the CP in order to restart the Detector, «Arming» command by
the wirelwss two-way communication «Rielta-Contact-R» protocol from the CP
is required.
12 Installation
12.1 Choose the Detector location, where the quality of communication is
appraised «excellent» or «good» and carry out marking for it’s mounting. Use
the base for marking. (See Figure 1).
12.2 Install the base at the chosen place and fasten it by 2 screws.
12.3 Insert the Detector into the base and fix it by turning clockwise.
13 Maintenance
The operability of the Detector should be checked at least annually.
The Detector should be cleaned from dust if the Detector generates «Fault»
or «Optical Smoke Chamber Dustiness» message. For this purpose, sweep the
optical system of the Detector by air under 0.3 – 0.5 kg/cm
2
pressure.
Technical maintenance rate for optical smoke chamber dustiness prevention
depends on the operating conditions and statistical data. It is recommended
to provide services of all detectors logged in the fire alarm system periodically.
In case of any battery discharge, both batteries should be replaced with a
new one.
Attention!
It is forbidden to remove and disassemble optical smoke chamber.
14 Storage and Transportation
14.1 The Detector in original package without power supply batteries is
resistant to:
а) transport jolting with the acceleration of 30 m/sec
2
with impact frequency
rate from 10 to 120 impacts/sec or 15000 impacts with the same acceleration;
b) the ambient temperature from minus 50 … +50 °С;
c) relative air humidity (95 ± 3) % at the ambient tempe35 °С.
14.2 The Detectors in original package may be transported by any transport
facility in closed vehicles over any distances in compliance with the existing
shipping rules concerning the respective means of transport.
14.3 After transportation under the conditions different to exploitation
conditions, the Detector shall be ready to operate after a maximum of six hours.
15 Manufacturer’s Guarantees
15.1 The manufacturer guarantees conformity of the Detector to the Technical
Specifications requirements provided the transportation, storage, installation and
operation conditions are observed.
15.2 The guaranteed shelf life of the Detector is 42 months since the date
of manufacture.
15.3 The guaranteed useful life is 36 months since the day of putting into
operation within the guaranteed shelf life.
15.4 The Detectors that are found non-conforming to the Technical
Specifications requirements shall be repaired by the manufacturer, provided
the installation and operation rules have been complied with.
Note
– Warranty obligations are not applied to the power supply batteries.
16 Packing Certificate
Wireless independent smoke Detector «Ladoga PD-RK-A» has been
manufactured in compliance with the active technical documentation, classified
as fit for operation and packed by «RIELTA» JSC.
Packing date _______________________________
month, year
«RIELTA» JSC, www.rielta.com
Chapaeva Str. 17, Saint Petersburg, Russia, 197101, [email protected]
Tel./fax: +7 (812) 233-0302, 703-1360
Technical support, tel.: +7 (812) 233-29-53, 703-13-57, [email protected]
Made in Russia