![Riello WinDialog 40U Plus Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/riello/windialog-40u-plus/windialog-40u-plus_user-manual_1460127027.webp)
27
TECHNICAL SPECIFICATIONS
MODEL
Series (type code)
Win Dialog 50
USY1…
Win Dialog 40U
Plus USY2…
Win Dialog 60U
Plus USY2…
Win Dialog 80U
Plus USY2…
Capacity
230V +20%/ -25%
Frequency
50 or 60Hz +/-5% (auto sensing)
INPUT
Maximum current
3 A
2.4 A
3.6 A
4.8 A
Voltage
(on battery)
Step wave /-5%
Frequency
(on battery)
50 or 60Hz +/-0.5% (auto sensing )
Voltage Regulator
AVR
AVR automatically increases the output voltage by 17% if the input voltage drops by
-10% to -26% below nominal. AVR decreases the output voltage by 15% if the input
voltage increases by +9% to +20% above nominal.
Transfer time
Typically 6-8 ms
Nominal power VA
500
400
600
800
OUTPUT
Nominal
power
W
300 240 360 480
EMI/RFI Filter
10dB at15MHz, 50dB at 30MHz
PROTECTION AND
FILTERS
Protection against
overload and short
circuits
Mains: Fuse for overload and short circuits
Battery: the UPS shuts down after 30 seconds if the load is between 100 ~ 110% of
the nominal, after 5 seconds if it exceeds 110%, or immediately in the event of a
short circuit.
Type
Lead acid, sealed, maintenance-free
Model
12V 7Ah
12V 4.5Ah
12V 7Ah
12V 9Ah
Typical recharge time
6-8 hours
BATTERY
Protections
Protection against battery failure, battery replacement indicator
Net Weight (Kg)
5.3
4.2
5.5
6.1
Weight with packaging
(Kg)
- - - -
Size (mm) WxDxH
152x110x325 mm
Input plug
IEC 320-10A
PHYSICAL
CHARACTERISTICS
Output plugs
N°3 x IEC 320-10A
Battery Mode
Slow audio signal (approx. 0.20Hz)
Battery failure
Fast audio signal (approx. 1Hz)
Overload <110%
Fast audio signal (approx. 1Hz)
Overload >110%
Continuous beep
ALARMS
Disabling buzzer
-
via software
via software
via software
INTERFACE USB
Interface
-
Bi-directional communication port
ENVIRONMENTAL
CONDITIONS (1)
Environmental
Conditions
max. altitude 6,000 metres, 0-90% non condensing humidity
0-40°C
OTHERS
Noise level
<40dBA (1m from source )
(1)
to prolong battery life, keep it connected to the mains so as to preserve the battery charge and at an
operating/storage temperature of 20-25°C.