107
CONFIGURATION OF CASCADED THERMAL UNITS
4.3.11
System parameters Block diagram 4
9
See section "Commissioning and maintenance" for a de-
tailed description of how the parameters work
MANAGING
Functions:
− Reads system sensor (SS)
− Controls thermal unit two-way valve (V1)
− Controls system pump (PS)
− Controls DHW pump (PB) instead of the LPG gas solenoid
valve (VLPG)
− Reads storage tank sensor (SB)
− Manages control of mixed zone 3 zone management (ZM)
device via bus. Up to a maximum of 16 devices can be
managed.
Programmable outputs and inputs parameter configuration (*)
(If Par. 97 = 11-21-22-23-24-25 - Stand alone configuration)
Par.
No. Description
Parameter setting
Terminals No.
125
Progr.ble
outp. 1
3 = DHW pump (**)
M02
16-17-18
187
Progr.ble
outp. 5
4 = System pump (PS)
M02
9-10-11
128
Progr.ble
outp. 4
1 = General pump (V1)
M02
13-14-15
122 Prog Input 7
3 = System sensor (SS)
M01
9-10
188 Prog Input 9
1 = DHW sensor (SB)
M01
13-14
(*)
Do NOT change the factory setting of parameter 97
(**)
In place of the fuel shut-off valve VPLG
Configuration of parameters for INAIL kit (***)
Par.
No. Description
Parameter setting
Terminals No.
123
Progr.ble
inp. 8
2 = Water pressure switch M01
27-28
117
Progr.ble
inp. 2
3 = Heating flowmeter
M01 21-22-23
(***)
An INAIL kit is required for each thermal unit
Hardware configuration
S1 = OFF (not used)
DIPSWITCH = 10000000
Configuration of boiler parameters
Par.
No.
Description
Parameter setting
73
Boiler Address
- “Managing” (if the
cascade sensor is used SC)
- “Stand-Alone” (if the
cascade sensor is not used
SC)
147
Number of Units
Set the total number of
cascaded units (from 2 to
8)
184
No. Active DHW units
0 to 8 (Number of active
units for DHW production)
7
CH Hysteresis
7°C
35
DHW mode
Choose from:
1 = Water heater with probe
2 = Water heater with
thermostat
135
Mod. Pump Type
2 = Grundfos (choose
according to need)
136
Mod. pump mode
Fixed 90% (according to
need)
140
Minimum Flow
5 l/min
Configuration of cascade parameters
Par.
No.
Description
Parameter setting
148
Power Mode
Choose from:
2 = Maximum number of
burners
3 = Minimum number of
burners
152
PwrMode2 Min Power
4%
153
PwrMode2 Hysteresis
40%
84
Module Rotation Interval
5 days
74
Emergency mode setpoint
50 (according to need)