13
GENERAL INFORMATION
GENERAL INFORMATION
IMPORTANT NOTES FOR BURNER INSTALLATION
Before fixing the burner to the boiler, make sure that:
− The door opens the right way (see the relevant sections
for details on how to reverse the door)
− The length (L) of the burner fixing bolts is less than (S),
i.e. the total depth of the seal, plates and washer.
Longer
bolts can cause the door to warp, compromising its
ability to seal the boiler hermetically and permitting
the release of combustion fumes.
To ensure correct burner installation, also refer to the burner’s
own manual.
L < S
S
L
If you are installing a new boiler but re-using an old burner,
always perform the following checks:
− Make sure that the performance of the old burner is ad-
equate for the requirements of the boiler
− Make sure that the length and diameter of the burner
nozzle are as specified in the following table.
9
When you finish installing the burner in the boiler, fill the
gap between the burner’s blast tube and the refractory ma-
terial in the door with the ceramic insulation (A) supplied
with the boiler.
A
Ø
L
TAU N
115
150
210
270
350
450
Burner head
L min. (mm)
110
110
170
180
180
195
Hole in door
Ø (mm)
162
162
162
180
180
210
TAU N
600
800
1000
1150
1250
1450
Burner head
L min. (mm)
200
200
200
200
200
205
Hole in door
Ø (mm)
210
235
235
230
230
265
0
Do not re-use old burners if their blast tube lengths are be-
low those specified in the table.
1.6
Identification
The products are identified by:
Serial number plate
This is located on the boiler body and specifies the serial num-
ber, model, and furnace power.
Data plate
This lists the technical specifications and performance of the
product. It comes inside the documentation envelope. On com-
pletion of the installation you MUST apply it in a clearly visible
position at the top of one of the side panels. If you damage
or lose this label, order a replacement immediately from
R
's
Technical Assistance Service.
9
If these plates or any other means of clearly identifying the
product are defaced, removed or lost, proper installation
and servicing may be rendered difficult.
23
27
0000581
WEEK OF
MANUFACTURE
CALDAIA IN ACCIAIO
Modello
Matricola
Codice
Code
Anno fabbricazione
Tipo
Type
Portata term.
Pot. utile
Pres. Max esercizio
Aliment. elettrica
kW
T°Max ammessa
Contenuto acqua
°C
l
Combustibile utilizzato : TUTTI I GAS / GASOLIO
max (Hi)
Q
max
60°/80°
P
PMS
Pressione focolare
kW
pn
PER CATEGORIA COMBUSTIBILE
E PAESI DI DESTINAZIONE
VEDI ETICHETTA BRUCIATORE
Portata term.
min (Hi)
Q
kW
Pot. utile
kW
T
max
m²
Superficie di scambio
mbar
RIELLO S.p.A.
Via Ing.Pilade Riello 7
37045 Legnago (VR) - ITALY
066940IE
STEEL BOILER
Model
Serial number
Codice PIN
PIN number
Year of manufacture
Max. heat input
Min. heat input
Furnace pressure
Max. operating
pressure
T°
Max permitted
Max. useful
heat output
60°/80°
P
min
heat output
Min. useful
Water capacity
Heat exchange
surface area
VEDI QUADRO ELETTRICO - SEE ELECTRIC CONTROL PANEL
Collegamento di terra obbligatorio - Obligatory ground connection
Fuel
: GAS / OIL
FOR FUEL TYPE COUNTRY
OF DESTINATION
SEE BURNER DATA PLATE
Power supply
Pa
k
Matricola
Modello
Pres. Max esercizio
Portata term.
Q
max (Hi)
PMS
kW
RIELLO S.p.A.
Via Ing.Pilade Riello 7
37045 Legnago (VR) - ITALY
Serial no.
Model
Max.operating press.
Max. heat inpt
COMBUSTIBILE UTILIZZATO / FUEL: GAS, GASOLIO / GAS, OIL
Pa
k