Riello SDH 3000 Скачать руководство пользователя страница 15

15 

 

 

USE 

 

C

ONNECTIONS AND SWITCHING ON FOR THE FIRST TIME

 

1)  Check that there is a protection device against overcurrents and short circuits in the system upstream from the 

UPS. The recommended protection value is 10A (for the 700VA, 1000VA and 1500VA versions) and 16A (for 
the 2200VA, 3000VA and ER versions) with a B or C trip curve. 

2)  Power the UPS using the input cable provided. 

3)  Press the ON/OFF switch located on the front panel. 

4)  After a few moments, the UPS will switch on, the display will light up, there will be a beep and the 

 icon will 

start to flash. The UPS is in stand-by mode: meaning that it is only consuming a small amount of power. The 
microcontroller supervising the self-diagnoses is powered; the batteries are charging; and everything is ready 
for UPS activation. Battery operation is also in stand-by mode provided that the timer is active. 

5)  Connect the equipment to be powered into the sockets on the back of the UPS, using the cable supplied or a 

cable no longer than 10 metres. 

 

CAUTION: do not connect equipment which absorbs more than 10A to the IEC 10A sockets. For equipment 
which exceeds this level of absorption, use the IEC 16A socket only (available on the 3000VA version). 

6)  Check which operating mode is set on the display and, if necessary, see the “

Configuring operating modes

” 

paragraph to set the required mode. For advanced UPS configurations execute the software UPSTools which 
can be downloaded from the web site 

www.riello-ups.com.

 

 
 

S

WITCHING ON FROM THE MAINS

 

1)  Press the “ON” button for 1 second. After pressing it, all the icons on the display light up for 1 second and the 

UPS beeps. 

2)  Switch on the equipment connected to the UPS. 

When switching on for the first time only:

 after 30 seconds, check that the UPS is operating correctly: 

1)  Simulate a blackout by disconnecting power to the UPS. 

2)  The load must continue to be powered, the 

 icon on the display must light up and there must be a beep 

every 4 seconds. 

3)  When power is reconnected, the UPS must go back to operating from the mains. 

 
 

S

WITCHING ON FROM THE BATTERY

 

1)  Press the ON/OFF switch located on the front panel. 

2)  Hold down the “ON” button for at least 5 seconds. All the icons on the display light up for 1 second. 

3)  Switch on the equipment connected to the UPS. 

 
 

S

WITCHING OFF THE 

UPS 

In order to switch off the UPS, hold down the “STBY” button for at least 2 seconds. The UPS goes back to stand-by 

mode and the 

 icon starts to flash: 

1)  If the mains power is present, the ON/OFF switch must be pressed to completely turn off the UPS. 

2)  During battery mode operation with the timer not set, the UPS automatically switches off after 30 seconds. 

However if, the timer is set, press and hold down the "STBY" key for at least 5 seconds to turn off the UPS. For 
complete shutdown, press the ON/OFF switch. 

 

 

Содержание SDH 3000

Страница 1: ......

Страница 2: ...ing the environmental aspects All our products pursue the objectives defined in the environmental management system developed by the company in compliance with applicable standards No hazardous materi...

Страница 3: ...ON 12 TOWER VERSION WITH BATTERY BOX 13 RACK VERSION 14 USE 15 CONNECTIONS AND SWITCHING ON FOR THE FIRST TIME 15 SWITCHING ON FROM THE MAINS 15 SWITCHING ON FROM THE BATTERY 15 SWITCHING OFF THE UPS...

Страница 4: ...4 COMMUNICATION SLOT 23 BATTERY PACK REPLACEMENT 24 TROUBLESHOOTING 26 ALARM CODES 28 FAULT 28 LOCK 29 TECHNICAL DATA 30...

Страница 5: ...an be installed in the two different positions The UPS is also equipped with a dedicated battery pack that allows for easy battery replacement hot swap in complete safety thanks to the protected conne...

Страница 6: ...6 UPS VIEWS FRONT VIEW Extractable rotatable display plate Removable front panel Release slits Battery pack connector ON OFF Switch Battery pack retention panel...

Страница 7: ...Communication port RS232 Battery expansion connector optional USB communication port IEC 10A output socket IEC 16A output socket IEC 16A input plug Communication Card Slots IEC 10A input plug Cooling...

Страница 8: ...ad level indicator ON button Configuration area STAND BY button Maintenance request Regular operation Timer Mains operation Measurement display area Battery operation Stand by alarm Load powered by by...

Страница 9: ...to the type of UPS for which the BATTERY BOX is intended It is therefore necessary to take great care to ensure that the battery voltage of the BATTERY BOX is the same as the voltage permitted by the...

Страница 10: ...ackage must contain UPS Support feet UK plug Schuko power cable IEC 10A IEC 16A only for models 2200 3000VA 2 IEC 10A connection cables USB cable RS232 cable User manual CD Safety manual Handles for r...

Страница 11: ...can be installed in series for extended runtimes Connect the Battery Boxes in series as shown in the figure below If the UPS is connected to a battery box the maximum active power is derated from PF 0...

Страница 12: ...SURE THAT THE UPS IS COMPLETELY SWITCHED OFF AND NOT CONNECTED TO THE MAINS POWER SUPPLY OR TO ANY LOAD Once removed from the packaging the UPS is already preset for installation in the tower configu...

Страница 13: ...AD THE BATTERY BOX IS DISCONNECTED FROM THE UPS FROM ANY OTHER BATTERY BOXES AND WITH THE BATTERY ISOLATOR OPEN For the battery box version each foot is composed of three parts two supports and an ext...

Страница 14: ...gently pull it away from its position just enough to be able to rotate it ATTENTION The panel must be removed carefully DO NOT ATTEMPT IN ANY WAY TO REMOVE THE PANEL FROM THE UPS 2 Rotate the panel 9...

Страница 15: ...erating modes paragraph to set the required mode For advanced UPS configurations execute the software UPSTools which can be downloaded from the web site www riello ups com SWITCHING ON FROM THE MAINS...

Страница 16: ...connected to the UPS are powered by the bypass Dynamic Indicates the estimated percentage charge of the batteries Dynamic Indicates the percentage of charge applied to the UPS compared with the nomin...

Страница 17: ...examples are shown below GRAPHIC EXAMPLE 1 DESCRIPTION GRAPHIC EXAMPLE 1 DESCRIPTION Mains voltage Battery charge percentage Mains frequency Total battery voltage UPS output voltage Applied load perce...

Страница 18: ...maintaining the output frequency synchronised to the mains within a configurable range Outside this range the UPS output de synchronises from the mains supply moving to the nominal frequency in this...

Страница 19: ...TROL TERMINAL BOARD The remote control terminal allows for implementation of the REPO function Remote Emergency Power Off and to remotely switch on off the UPS The UPS is provided by the manufacturer...

Страница 20: ...full display of the status of the UPS via USB or RS232 For a list of possible configurations available to the user refer to the UPS Configuration paragraph INSTALLATION OPERATIONS 1 Connect one of the...

Страница 21: ...n Disabled without input output synchronisation Power off due to minimum charge Automatic UPS power off in battery operation mode if the charge is lower than 5 Disabled Enabled Disabled Autonomy limit...

Страница 22: ...steps High 250 264 in 1V steps Bypass voltage threshold for ECO Selects the permitted voltage range for operation in ECO mode Low 200V High 253V Low 180 220 in 1V steps High 240 264 in 1V steps Inter...

Страница 23: ...e manual provided 2 TXD 3 RXD 5 GND 6 Power supply DC Imax 20mA 8 Programmable output default low battery pre alarm 9 Programmable output default battery operation COMMUNICATION SLOT The UPS is equipp...

Страница 24: ...ACK IS VERY HEAVY USE EXTREME CAUTION WHEN REPLACING IT 1 Set the UPS to bypass mode manually by pressing the ON SEL buttons for 4 seconds see paragraph entitled USE Configuration of Operating Mode Th...

Страница 25: ...tteries see the label located on the battery pack near the connector 5 Insert the new battery pack into the compartment sliding it into the UPS Put the battery pack retention panel back in position an...

Страница 26: ...STAND BY OFF emergency power supply mode in fact only powers the loads in the event of a blackout NO CONNECTION TO THE LOAD Check the connection to the load THE UPS IS OPERATING FROM THE BATTERY DESP...

Страница 27: ...rs again call the support centre THE BUZZER SOUNDS CONTINUOUSLY AND THE DISPLAY SHOWS ONE OF THE FOLLOWING CODES F04 L04 THE TEMPERATURE OF THE DISSIPATORS INSIDE THE UPS IS TOO HIGH Check that the te...

Страница 28: ...0 C A54 Load percentage greater than the user threshold set A61 Replace batteries A62 Batteries missing or Battery Box missing or not connected A63 Waiting for battery charging Alarms these are more c...

Страница 29: ...ed for locks due to serious persistent overloads and short circuits CODE DESCRIPTION L02 Control card is not inserted correctly L03 Incorrect auxiliary power supply L04 Dissipator over temperature L05...

Страница 30: ...ter 4 seconds Load overload 150 Bypass line available bypass immediately activated blocked after 1 second Bypass line not available blocked after 0 5 second OTHER DATA Leakage current towards ground m...

Страница 31: ...ttery rated voltage Vdc 36Vdc 72Vdc Dimensions W x D x H mm 87 x 425 x 450 87 x 625 x 450 Weight Kg 13 5 20 5 25 38 The symbol replaces an alphanumeric code for internal use If the UPS is connected to...

Страница 32: ...0MNSDH1K0RUENUB...

Отзывы: