Operation
Operating times
Time expressed in seconds
Tab. E
Lockout types and triggering times in case of burner mal-
function
Tab. F
6.9
Recycle function if flame goes out during operation
The control box allows recycling, i.e. the complete repetition of
the start/up program.
If after the safety time since the last recycle the flame does not
appear, the burner carries out a lockout.
6.10 Restart function following firing failure
The control box allows the start-up programme to be repeated,
making up to 3 attempts, if no flame is formed by the end of the
safety time.
If the flame still fails to appear after the fourth ignition attempt, the
burner locks out at the end of the safety time.
6.11
Control of the motor rpm
Check of the motor operation if the rotation number per minimum
minute exceeds (900 rpm).
If the motor does not exceed the number of minimum turns, it
stops after 20 seconds.
6.12 Control box reset (using built-in button)
To carry out the control box reset, proceed as follows:
Press and hold the reset button for 1-2 seconds.
In case the burner does not restart it is necessary to check if
the limit thermostat (
TL
) is closed.
ta
tf
tl
tm
ts
tw
t1
t2
t3
t8
20
1
40
10
5
-
25
3
5
10
ta
Time for checking motor turns:
if the number of turns is lower than 900 rpm, after
ta
will
be carried out a lockout.
tw
Stabilisation time motor turns.
tf
Response time after the flame disappearance.
t1
Pre-purging time:
by the signal of heat request to the end of the ignition.
tl
Flame or flame simulation detected during pre-purging:
immediate lockout.
t2
Transformer pre-ignition time:
ignition before the valve closing.
tm
Stabilisation time:
the modulation occurs after this time.
t3
Transformer ignition time:
the transformer remains on during the safety time.
ts
Safety time:
if at the end of the time
ts
a flame is not present,
tpp
is
carried out. After 3 times follows a lockout.
t8
Post-purging time:
Additional purging when the heat request is completed,
or in case of flame failure during the operation or in
case of ignition failure.
Description of types of faults
Lockout
Presence of flame in pre-purging “t1”
At the end of the time of “t1”
No ignition at end of safety time “ts”
After max. 3 repeats, within 1 second
Flame goes out during operation
After max. 1 repetition, if there is no flame at the end of ts
Not correct No. of turns of the fan motor (< 900 rpm)
After max. 20 seconds
Fault at the valve circuit
At the end of the time of “t1”