Faults - Probable causes - Solutions
If faults arise in ignition or operations, the burner performs a
"safety stop", which is signalled by the red burner lockout LED.
The display of the operator panel visualises alternately the lock-
out code and the relative diagnostic.
To restore start-up conditions, refer to the
page 35.
When the burner starts up again, the red LED goes out.
8.1
Error codes list
8
Faults - Probable causes - Solutions
WARNING
In the event of a burner lockout, more than two
consecutive burner reset operations could cause
damage to the installation. On the third lockout,
contact the Aftersales Service.
DANGER
If further lockouts or burner faults occur, interven-
tions must only be made by qualified, authorised
personnel (as indicated in this manual, and in
compliance with the laws and regulations current-
ly in force).
Error
code
Diagnostic code
Meaning of the REC 27.100A2 system
Recommended measures
No Comm
No communication betweenREC 27.100A2 and
RDI21…
Check the wiring between the control box REC 27.100A2 and
the display RDI21…
2
#
No flame at the end of TSA1
1
No flame at the end of safety time 1 (TSA1)
2
No flame at the end of safety time 2 (TSA2)
4
No flame at the end of safety time 1 (TSA1)
(software version
V02.00)
3
#
Air pressure error
0
Air pressure switch off
1
Air pressure switch on
4
Air pressure on – Lockout alarm at start
20
Air pressure, fuel pressure on - Alarm lock at start
68
Air pressure, POC on – Alarm lockout at start
84
Air pressure, fuel pressure, POC on - Alarm lockout at start
4
#
Extraneous light
0
Extraneous light during start-up
1
Extraneous light during switch-off
2
Extraneous light during start-up – Lockout alarm at start
6
Extraneous light during start-up, air pressure - Alarm
lockout at start
18
Extraneous light during start-up, fuel pressure - Alarm
lockout at start
24
Extraneous light during start-up, air pressure, fuel pressure
- Alarm lockout at start
66
Extraneous light during start-up, POC – Alarm lockout at
start
70
Extraneous light during start-up, air pressure, POC - Alarm
lockout at start
82
Extraneous light during start-up, fuel pressure, POC -
Alarm lockout at start
86
Extraneous light during start-up, air pressure, fuel
pressure, poc - Alarm lockout at start
7
#
Loss of flame
0
Loss of flame
3
Flame loss (software version
V02.00)
3…255
Flame loss during TÜV test (flame loss test)
The diagnostics covers the period of time from the closure of the
fuel valves at the point the flame loss was detected (resolution
0.2 s
value 5 = 1 s).
12
#
Valve leak detection control:
0
V1 leaks
Leak test
Check if the valve on the side of the gas has any leaks.
Check the wiring and check that the circuit is open.
1
V2 leaks
Leak test
Check if the valve on the side of the burner has any leaks.
Check if the pressure switch for the leak test (PGVP) is closed
when gas pressure is not present.
Check the wiring and check if there is any short-circuit.
Содержание RS 34/E MZ
Страница 2: ...Translation of the original instructions ...
Страница 65: ...63 20068131 GB Appendix Electrical panel layout RS 34 E MZ ...
Страница 66: ...20068131 64 GB Appendix Electrical panel layout RS 44 E MZ ...
Страница 67: ...65 20068131 GB Appendix Electrical panel layout RS 44 E MZ 3Ph ...
Страница 68: ...20068131 66 GB Appendix Electrical panel layout RS 34 44 E MZ ...
Страница 69: ...67 20068131 GB Appendix Electrical panel layout RS 44 E MZ 3Ph ...
Страница 70: ...20068131 68 GB Appendix Electrical panel layout ...
Страница 71: ...69 20068131 GB Appendix Electrical panel layout ...
Страница 72: ...20068131 70 GB Appendix Electrical panel layout ...
Страница 73: ...71 20068131 GB Appendix Electrical panel layout ...
Страница 75: ......