20123781
20
GB
Installation
5.9
Electrodes adjustment
5.10
Combustion head adjustment
The air damper servomotor 4)(Fig. 4), beyond varying the air out-
put according to the output demand, through a leverage varies
the combustion head adjustment.
This system allows an optimum adjustment also at the minimum
firing rate. Similarly to servomotor rotation, it is possible to vary
the opening of the combustion head moving the tie-rod on the
holes (5-6-7-8-10)(Fig. 19).
The selection of the hole to be used is determined based on the
maximum output requested, as illustrated in Tab. I.
In the factory, the adjustment is adjusted for the maximum stroke
(hole 10, Fig. 19).
Tab. I
WARNING
Position the electrodes according to the dimen-
sions shown in Fig. 18.
Fig. 18
Diffuser
Electrodes
D11587
Fig. 19
20061124
Leverage hole
Output (kW)
From
A
RS 100
0
5
1100
4000
5
4000
6600
8
6600
8100
10
8100
10100
RS 1
200
5
1500
5500
5
5500
7500
6
7500
9650
10
9650
11100
WARNING
The gas pipes leave the factory calibrated at
notch 1.
The adjustment shown in Fig. 20 allows the gas
pipes to be positioned in the best way for the ap-
plication on which the burner is installed (e.g. boil-
ers with flame inversion chamber).
Fig. 20
20077710
Содержание RS 1000/EV BLU
Страница 2: ...Translation of the original instructions ...
Страница 41: ...39 20123781 GB Appendix Electrical panel layout ...
Страница 43: ...41 20123781 GB Appendix Electrical panel layout 0 1 2 2 2 0 3 4 56 789 ...
Страница 45: ...43 20123781 GB Appendix Electrical panel layout 0 1 0 1 222 3 3 3 4 3 3 3 3 3 3 3 3 3 3 3 4 3 ...
Страница 47: ......