background image

31 

20148124

GB

Start-up, calibration and operation of the burner

6.8

Air / fuel adjustment

During the operations for calibrating the air/fuel ratio for oil
burners, the following adjustments need to be made:

A

Oil pump delivery pressure:

act on the screw 5)(Fig. 22) located on the pump.

B

Air cam:

act on the adjustment screws 2)(Fig. 36) after having

loosened the screws 3)(Fig. 36).

C

Gas cam:

act on the adjustment screws 2)(Fig. 36) after having

loosened the screws 3)(Fig. 36).

D

Oil cam:

modify the eccentricity by acting on the screw 4)(Fig. 37)

after having loosened the screws 7)(Fig. 37). 

By tightening the screw 4)(Fig. 37) the eccentricity

increases, thereby increasing the difference between the

maximum and minimum return pressure returning from the

nozzle.

Key

 (Fig. 37)

1

Maximum oil pressure switch

2

Delivery pressure gauge

3

Return pressure gauge

4

Eccentric adjustment screw

5

Piston stop ring

6

Piston calibration nut and lock nut

7

Eccentric locking screws

8

Variable eccentric 

Burner calibration procedure

Install the nozzle suitable to achieve the maximum desired
output.

Verify that the eccentricity of the oil cam is such to make a
travel of about 8 mm on the shaft of oil modulator. 
Normally, with a shaft stroke of 8 mm, the pressure variation
needed for the modulation of the minimum to maximum
output is obtained. 
To verify this, manually rotate the cam after having released
the servomotor with the lever 7)(Fig. 38), so that the travel of
the shaft is not exaggerated or insufficient. Remember to
block the servomotor after the verification.

Switch on the burner, with the selector on the control panel
on manual 1)(Fig. 34). 
At this point, after the pre-purging phase, the servomotor
stops at about 20°.

Adjust the outlet pressure of the pump as shown in point 

A

(oil pump outlet pressure) 

to obtain an outlet pressure to

the nozzle of 24 - 25 bar.

Adjust the minimum return pressure to approx. 6 bar. 
To do so, the length of the shaft 5)(Fig. 37) must be varied
by means of nut 6)(Fig. 37).

Calibrate the air delivery by adjusting the variable profile
cam with the screws 2)(Fig. 36).

Having performed this first adjustment, increase the output
supplied via the automatic return selector on the control
panel. Pause after a 15° rotation of the servomotor and
perform another adjustment by means of the variable profile
cam of the air.
It is recommended to perform a calibration that will prevent
the formation of a smoky flame and arrive as soon as
possible to the maximum output (maximum stroke of the
servomotor 130°); on the eccentric (screw 4, Fig. 37),
calibrate the pressure on the return line to obtain the output
desired and requested by the nozzle, and then go back to
calibrate the intermediate points.

Then recheck the values  of the combustion parameters at
the various modulation outputs and if necessary make the
necessary adjustments.

At this point shift the selector 3)(Fig. 34), to 

GAS

 and check

that the gas operation is operating correctly at the desired
output. 
If this is not so, calibrate the gas cam as in point 

C (Gas

Cam) 

mentioned above.

With the optimal adjustment achieved, remember to lock the
adjustment screws of the cam profiles by means of screws
3)(Fig. 36).

D8369

Fig. 37

ATTENTION

When calibrating the cams, never go beyond the
travel limits of the servomotor 0° - 130° to avoid
any sticking. Carrying out a manual travel 0 -130°
of the cams, check that there are no mechanical
stops before the micro-switches 1-2 of the
servomotor are activated.

Содержание RLS 800/M MX

Страница 1: ...20148124 2 11 2020 Installation use and maintenance instructions Dual fuel light oil gas burner Progressive two stage or modulating operation CODE MODEL TYPE 20147802 RLS 800 M MX 1301 T GB ...

Страница 2: ...Translation of the original instructions ...

Страница 3: ...12 Control box RFGO A22 13 4 13 Servomotor SQM10 1 14 5 Installation 15 5 1 Notes on safety for the installation 15 5 2 Handling 15 5 3 Preliminary checks 15 5 4 Operating position 16 5 5 Removing the shutter lockout screws 16 5 6 Preparing the boiler 16 5 6 1 Boring the boiler plate 16 5 6 2 Blast tube length 16 5 7 Securing the burner to the boiler 17 5 8 Access to head internal part 17 5 9 Elec...

Страница 4: ...ure switch 33 6 10 3 Minimum gas pressure switch 33 6 11 Operation sequence of the burner 34 6 11 1 Burner start up 34 6 11 2 Steady state operation 34 6 11 3 Burner flame goes out during operation 34 6 11 4 Ignition failure 34 6 12 Final checks with burner operating 35 7 Maintenance 36 7 1 Notes on safety for the maintenance 36 7 2 Maintenance programme 36 7 2 1 Maintenance frequency 36 7 2 2 Saf...

Страница 5: ... 30 EU Electromagnetic Compatibility PED 2014 68 EU FS2 only Pressure Equipment Directive Such products are marked as indicated below The quality is guaranteed by a quality and management system certified in accordance with ISO 9001 2015 Manufacturer s Declaration RIELLO S p A declares that the following products comply with the NOx emission limits specified by German standard 1 BImSchV revision 2...

Страница 6: ...rried out correctly may cause damage to the machine and or injury to people DANGER DANGER LIVE COMPONENTS This symbol indicates operations which if not carried out correctly lead to electric shocks with lethal consequences DANGER FLAMMABLE MATERIAL This symbol indicates the presence of flammable materials DANGER BURNING This symbol indicates the risks of burns due to high temperatures DANGER CRUSH...

Страница 7: ...event of damage to things or injury to people if such damage injury was due to any of the following causes incorrect installation start up use and maintenance of the burner improper incorrect or unreasonable use of the burner intervention of unqualified personnel carrying out of unauthorised modifications on the equipment use of the burner with safety devices that are faulty incorrectly applied an...

Страница 8: ...nance Only those parts envisaged by the manufacturer can be replaced 3 2 Personnel training The user is the person body or company that has acquired the machine and intends to use it for the specific purpose He is responsible for the machine and for the training of the people working around it The user undertakes to entrust the machine exclusively to suitably trained and qualified personnel undert...

Страница 9: ...800 M TC Emission Class 1 EN267 EN676 MY Class 1 EN267 Class 3 EN676 BLU Class 3 EN267 EN676 MX Class 2 EN267 Class 3 EN676 FS1 3 400 50 230 50 BASIC DESIGNATION EXTENDED DESIGNATION MX 3N 400V 50Hz 3 230V 50Hz 230V 50Hz 110V 50 60Hz Heavy oil E Electronic cam EV Electronic cam and variable speed with Inverter P Proportional air gas valve BP Two stage light oil Proportional valve gas M Mechanical ...

Страница 10: ...7 295 674 Fuels LIGHT OIL max viscosity at 20 C 6 mm2 s 1 5 E 6 cSt NATURAL GAS G20 methane gas G21 G22 G23 G25 LPG G31 NCV 26 kWh Nm3 Gas pressure at max output 2 Gas G20 G25 mbar 50 6 75 4 Operation Intermittent min 1 stop in 24 hours Progressive two stage or modulating by kit see accessories Pump Output at 16 5 bar Pressure range Fuel temperature kg h bar c max 560 6 30 140 Nozzles number 1 Sta...

Страница 11: ... head requires the burner to be opened and the rear part turned on the hinge The maximum dimensions of the open burner are indicated by the L and R positions The l position is reference for the refractory thickness of the boiler door Tab E mm A B C D E F G H I L R S RLS 800 M MX 1333 558 173 428 626 DN80 972 988 388 1187 1061 349 I B A D E C F G H L S S R D9251 Fig 1 ...

Страница 12: ...anufacturer The firing rates were obtained in special test boilers according to EN 676 standard In Fig 3 you can see the diameter and length of the test combustion chamber Example Output 7000 kW diameter 120 cm length 6 m MODULATING RATIO The modulating ratio obtained in the test boilers according to the standard EN 676 for gas EN 267 for light oil is 2 5 1 ATTENTION The firing rate value Fig 2 ha...

Страница 13: ...fferential type 19 Combustion head air pressure test point 20 Maximum gas pressure switch with pressure test point 21 Flame sensor 22 Pressure test point for air pressure switch 23 Pump 24 Pump motor 25 Minimum oil pressure switch 26 Maximum oil pressure switch 27 Nozzle return pressure gauge 28 Nozzle delivery pressure gauge 29 Oil modulator 30 Pressure gauge connection 31 Pilot gas train 15 6 19...

Страница 14: ... 18 Auxiliary circuits fuse 19 Plug socket servomotor 20 Plug socket valves motor 21 Fan motor thermal relay 22 Pump motor contactor and thermal relay 23 Oil Gas selection relay 24 Plug socket maximum gas pressure switch 25 Flame sensor plug sensor socket NOTE Two types of burner lockout may occur Control box lockout if the button red LED of control box 11 Fig 5 and signal button 10 Fig 5 light up...

Страница 15: ...ions Do not confuse the powered conductors with the neutral ones Ensure that spliced wires cannot get into contact with neighbouring terminals Use adequate ferrules Arrange the H V ignition cables separately as far as possible from the control box and the other cables When wiring the unit make sure that AC 230 V mains voltage cables are run strictly separate from extra low voltage cables to avoid ...

Страница 16: ...nt national safety standards are respected When assembling the servomotor and connecting the damper the gears can be disengaged by means of a lever allowing the drive shaft to be easily adjusted in both directions of rotation Technical data Tab G ATTENTION To avoid accidents material or environmental damage observe the following instructions Avoid opening modifying or forcing the actuators Operati...

Страница 17: ...on air inside the boiler must be free from hazardous mixes e g chloride fluoride halogen if present it is highly recommended to carry out cleaning and maintenance more frequently ATTENTION Burner handling operations can be highly dangerous if not carried out with the greatest attention distance unauthorised personnel check integrity and suitability of the means available Check also that the area i...

Страница 18: ... screen supplied with the burner 5 6 2 Blast tube length The length of the blast tube must be selected according to the indications provided by the manufacturer of the boiler and in any case it must be greater than the thickness of the boiler door complete with its fettling For boilers with front flue passes 1 Fig 12 or flame inversion chamber a protection in refractory material 5 must be inserted...

Страница 19: ...lated to air damper and head movement undo the 4 fixing screws 1 disconnect the electrode cable 2 disconnect the light oil pipes unscrewing the two pipe fittings 3 Release the ignition pilot retainer remove the gas pressure screw test point 6 of the head disconnect the lower part of the elbow until it is released from its housing remove the internal part of the head 5 5 9 Electrode position ATTENT...

Страница 20: ...00 650 700 750 Normally atomisation angles of 45 are recommended Tab J ATTENTION It is advisable to replace the nozzle once a year during periodical maintenance CAUTION The use of nozzles other than those specified by Riello S p A and inadequate regular maintenance may result into emission limits non conforming to the values set forth by the regulations in force and in extremely serious cases into...

Страница 21: ...put required In the factory the hole is adjusted for the maximum stroke hole 3 Fig 16 If for combustion reasons it is necessary to move the spacer 1 Fig 17 onto the 1st and 2nd hole of the gear while the hinge is positioned to the right the spacers 4 Fig 17 supplied as standard must be mounted Proceed as follows Fig 17 unscrew the nuts 2 and remove the tie rod 3 unscrew the spacer 1 and place it o...

Страница 22: ...mote control Italy only 8 On off solenoid valve Italy only See electrical layout Connections to be carried out by the installer SV 9 Return line 10 Check valve Italy only 5 12 3 Hydraulic connections The pumps are equipped with a by pass that connects return line with suction line They are installed on the burner with the by pass closed by screw 6 Fig 22 It is therefore necessary to connect both h...

Страница 23: ...pressure gauge 3 Fig 20 max pressure on return circuit must be approx 16 5 bar The relevant delivery pressure read on the pressure gauge 2 must be 20 bar see Tab I on page 18 IMPORTANT For a correct calibration the eccentric 8 must operate on the entire range of travel of the servomotor 20 130 a pressure variation must correspond to each servomotor variation Never drive the variator piston fully h...

Страница 24: ...G 1 4 5 Pressure adjuster 6 By pass screw 7 Pressure gauge connection G 1 4 The time required for this operation depends upon the diameter and length of the suction tubing If the pump fails to prime at first start up and the burner locks out wait approx 15 seconds reset the burner and then repeat the start up operation And so on After 5 or 6 starting operations allow 2 or 3 minutes for the transfo...

Страница 25: ...r P3 Pressure upstream of the filter L Gas train supplied separately L1 Responsibility of the installer DANGER Explosion danger due to fuel leaks in the presence of a flammable source Precautions avoid knocking attrition sparks and heat Make sure the fuel shut off valve is closed before performing any operation on the burner ATTENTION The fuel supply line must be installed by qualified personnel i...

Страница 26: ...alve P2 Fig 28 with maximum opening 90 To calculate the approximate output at which the burner operates subtract the pressure in the combustion chamber from the pressure of the gas at test point P1 Fig 28 Find in Tab L related to the burner concerned the pressure value closest to the result of the subtraction Read the corresponding output on the left DANGER Disconnect the power supply using the sy...

Страница 27: ...of 6000 kW 30 2 mbar Pressure in combustion chamber 5 mbar 30 2 5 35 2 mbar pressure required at test point P1 Fig 28 Key Fig 28 P1 Head gas pressure test point P2 Butterfly valve gas pressure test point 2 Manual valve 12 Gas inlet for pilot 13 Pilot line pressure adjuster 14 Safety valve 15 Operating valve 5 13 5 Pilot gas train connection The burner is equipped with a dedicated gas train fixed t...

Страница 28: ...llows to use it for applications requiring a burner operating cycle longer than 24 hours When it is used as a UV control the system is considered as non permanent requiring one burner recycle every 24 hours Normally burner stopping is guaranteed by the boiler s thermostat pressure switch If this is not the case a time switch must be applied to L N in series to stop the burner at least once every 2...

Страница 29: ...it in the arrow direction to the right to carry out the thermal relay test 5 16 Motor rotation As soon as the burner starts place yourself in front of the cooling fan of the fan motor and check that it turns anticlockwise Fig 32 If this is not the case put the switch of the burner to 0 off and wait until the control box carries out the switching off phase Invert the phases on the three phase motor...

Страница 30: ...of the scale Purge the air from the gas line We recommend using a plastic tube routed outside the building and to purge air until gas is smelt Fit a U type pressure gauge or a differential pressure gauge Fig 33 with socket on the gas pressure of the pipe coupling and in the combustion chamber Used to derive the approximate MAX output of the burner using the table on page 24 Connect two lamps or te...

Страница 31: ...en place proceed with burner global calibration operations 6 6 Change of fuel There are two change of fuel options 1 with selector 3 Fig 34 2 with a remote selector connected to the main terminal board Placing the selector 3 Fig 34 on EXT the function for selecting the fuel remotely is active In this position if there is no remote selector the display shows the priority fuel 6 7 Combustion air adj...

Страница 32: ...e servomotor The passage from one position to the next one is obtained by pressing the selector 2 Fig 36 on the symbol or For better adjustment repeatability take care to stop the rotation of the cam unit when the upper bearing that slides on the profile 4 Fig 36 is aligned with one of the adjustment screws 2 Fig 36 Screw or unscrew the pre set screw 2 Fig 36 to increase or decrease the air output...

Страница 33: ... 34 At this point after the pre purging phase the servomotor stops at about 20 Adjust the outlet pressure of the pump as shown in point A oil pump outlet pressure to obtain an outlet pressure to the nozzle of 24 25 bar Adjust the minimum return pressure to approx 6 bar To do so the length of the shaft 5 Fig 37 must be varied by means of nut 6 Fig 37 Calibrate the air delivery by adjusting the vari...

Страница 34: ...tor on position max approx 130 Operating with oil Cam 2 limits the servomotor limit switch at the 0 position With the burner off the air damper is completely closed Operating with oil and gas Cam 3 regulates the minimum modulating output It is factory set at 30 Operating with minimum oil Cam 4 limits the limit switch of the servomotor on position max approx 130 Operating with gas Cam 5 regulates t...

Страница 35: ...ximum gas pressure switch must be regulated to a value no higher than 30 of the measurement read on the gauge when the burner is working at maximum output After making the adjustment remove the pressure gauge and close the tap 6 10 3 Minimum gas pressure switch Adjust the minimum gas pressure switch after performing all the other burner adjustments with the pressure switch set to the start of the ...

Страница 36: ... the boiler point C Fig 42 The electrical control box continues to check the presence of the flame and the correct position of the air and gas maximum pressure switches If the temperature or the pressure is low so the thermostat pressure switch TR is closed the burner progressively increases the output up to the MAX value section C D Then if the temperature or pressure increases until the TR opens...

Страница 37: ...inimum end of scale position Turn the air pressure switch knob to the maximum end of scale position The burner must stop in lockout Turn off the burner and cut off the power Disconnect the minimum gas pressure switch connector The burner must not start Disconnect flame detection sensor electrical connections The burner must stop in lockout due to ignition failure ATTENTION Make sure that the mecha...

Страница 38: ... combustion flue gases Significant differences with respect to the previous measurements indicate the points where most care should be exercised during maintenance Combustion head Open the burner and make sure that all components of the combustion head are in good condition not deformed by the high temperatures free of impurities from the surroundings and correctly positioned Burner Check that the...

Страница 39: ...ed life cycles do not refer to the warranty terms indicated in the delivery or payment conditions Safety component Life cycle Flame control 10 years or 250 000 operation cycles Flame sensor 10 years or 250 000 operation cycles Gas valves solenoid 10 years or 250 000 operation cycles Pressure switches 10 years or 250 000 operation cycles Pressure adjuster 15 years Servomotor electronic cam if any 1...

Страница 40: ...ake sure that the hoses are still in good condition Fuel tank Approximately every 5 years suck any water on the bottom of the tank using a separate pump Combustion If the combustion values measured before starting maintenance do not comply with applicable Standards or do not indicate efficient combustion consult the table below or contact our Technical Support Service to implement the necessary ad...

Страница 41: ... to open the burner on the hinge 7 4 Closing the burner Refit following the steps described but in reverse order refit all burner components as they were originally assembled DANGER Disconnect the electrical supply from the burner by means of the system main switch DANGER Close the fuel shut off valve Wait for the components in contact with heat sources to cool down completely 5 5 1 2 6 5 5 7 3 4 ...

Страница 42: ...LED starting from the flame LED represents 20 of the signal power To exit the check mode function press the reset button the flame control will go back to the normal operating mode 8 3 Flame control lock out or emergency stop condition The RFGO control device can be locked out emergency stop at any time during the operating cycle and unlocked when already locked lock out by simply pressing the key...

Страница 43: ...per open Damper closed Modulation Ignition Flame Status Icon Power OFF ON OFF Not ready Diagnostics Green Standby Green Servomotor movement Note 3 OFF Flashing Flashing OFF Green Waiting for closing Green blinking Green OPEN before ignition Green Minimum before ignition Green Ignition Green PTFI Green blinking Green MTFI Green Active modulation Green Minimum output position Green With flame presen...

Страница 44: ... cause material problems severe injuries or death It is the owner or user s responsibility to make sure that the equipment described is installed used and commissioned in compliance with the requirements provided both by national and local law The lock out condition indicates the presence of a fault which occurred during the operating cycle or during stand by mode Before performing an unlock attem...

Страница 45: ...elay fault Red 19 Combustion airflow switch fault in the rest position Red 20 UV no flame at the end of the 2nd safety time MTFI Red 21 Safety relay fault Red 22 Supervisor processor fault Red 23 Supervisor memory test fault Red 24 Flame loss during the operation AUTO Red 25 Supervisor processor data memory fault Red 26 Supervisor processor internal fault Red 27 Not used 28 Not used 29 Operating t...

Страница 46: ...ingle phase line 50 60Hz 5 FR No flame at the end of the 2nd safety time MTFI No flame at the end of the second safety time Inspect the system check the gas pressure inspect the flame detection electrode check the wiring etc 6 FR internal circuit fault Internal fault Replace the control device 7 Internal communication fault Internal fault Replace the control device 8 Remote reset The user pressed ...

Страница 47: ...rnal fault Replace the control device 41 Internal hardware fault Internal fault Replace the control device 42 Main processor fault Internal fault Replace the control device 43 Supervisor processor fault Internal fault Replace the control device 44 Supervisor processor timeout Internal fault Replace the control device 45 Off specification mains voltage Off specification mains voltage frequency Chec...

Страница 48: ...8 at the wrong moment or there is no voltage when necessary Check the wiring Check the actuator 59 Internal hardware fault Internal fault Replace the control device 60 Local reset fault Local reset button pressed for more than 10 seconds or reset button locked If the problem persists replace the control device 61 Open POC fault The fuel valve is open at the wrong moment Check the wiring 62 UV stro...

Страница 49: ...tentiometer Spacer kit Potentiometer kit for load position indication Soundproofing box kit Kit for the remote selection of the fuel Gas trains in compliance with EN 676 Please refer to manual A Appendix Accessories Parameter to be controlled Probe Output regulator Adjustment field Type Code Type Code Temperature 100 500 C PT 100 3010110 RWF50 2 RWF50 5 20101190 20101191 Pressure 0 2 5 bar 0 16 ba...

Страница 50: ...ut star triangle starter 5 Functional layout RFGO A22 6 Functional layout RFGO A22 7 Functional layout RFGO A22 8 Functional layout RFGO A22 9 Electrical wiring kit RWF50 internal 10 Electrical wiring that is the responsibility of the installer 11 Functional layout for kit RWF50 12 Electrical wiring kit RWF50 external 1 2 Sheet no 1 A1 Coordinates Indication of references ...

Страница 51: ...49 20148124 GB Appendix Electrical panel layout 0 0 1 20 0 0 20 0 1 1 3 3 1 4 4 0 4 0 5 4 6 4 0 4 0 0 4 4 4 4 4 74 7 7 4 4 0 5 4 0 0 0 0 0 ...

Страница 52: ...20148124 50 GB Appendix Electrical panel layout ...

Страница 53: ...51 20148124 GB Appendix Electrical panel layout 0 1 1 1 ...

Страница 54: ...20148124 52 GB Appendix Electrical panel layout 0 0 1 0 1 2 0 3 0 1 0 1 1 0 0 0 0 0 40 4 4 0 0 1 2 0 1 ...

Страница 55: ...53 20148124 GB Appendix Electrical panel layout 0 1 2 2 2 0 ...

Страница 56: ...20148124 54 GB Appendix Electrical panel layout 0 1 1 1 2 3 45678 9 55 ...

Страница 57: ...10 302 6 7 1 0 2 2 310 24 5 2 2 0 8 0219 310 24 5 1 0821 2 5 5 1 0 2 24 5 9 9 9 1 1 1 3 2 3 12 64 2 1 4 A B 2 2 B 20 27 2 2 2 2 2 0 46 1 4610 4 1 2 1 2 2 2 B0 B1 00 B1 0 B1 0 B1 00 21 1 2 21 2 3 2 1 3 2 2 2 2 09 0 2 6 0 29 1 0 29 1 0 231 2 2 0 1 B 2 2 0 1 2 1 B 2 4 2 A B 20 2 22 2 4 22 2 39 3 3 ...

Страница 58: ...20148124 56 GB Appendix Electrical panel layout 0 1 2 1 3 4 56 7 8 7 8 9 1 2 3 0 1 0 0 1 0 0 9 0 9 0 0 0 1 0 2 2 2 ...

Страница 59: ... 4 0 4 5 1 5 6 4 4 9 4 7 A 91 5 9 09 A 7 001B 5 4 1 C 4 7 8 4 D970 4 64 7 47 1 4 E 001 9 F4 94 1 4 1 0 7 94 G 6 1 9 4 4 A H H A A H A H 7 7 7 A 7 A A I 3 I 3 I J I K I I I I I 3I 3 I I 3 I I J I 3 3 3 L L L L A L L A L L A 47 901 9 70 4 94 47 7 4 8 4 4 9 47 7 4 8 4 4 9 7 4 4 8 944 9 09 8 944 9 09 4 8 1 5 9 09 8 1 5 9 09 ...

Страница 60: ...4 5 4 5 46 7 4 8 09 6 4 4 46 4 6 6 8 09 6 4 8 09 446 5 4 8 09 8 09 1 3 2 6 4 6 4 8 A 7 6 68 B 7 7 C 5 7 C 7 5 6 6 5 6 7 6 8 46 8 4 8 67 4 6 6 7 6 7 6 7 C C 6 6 C 6 C 6 C 6 7 7 7 6 7 7 7 6 6 6 75 6 6 76 5 6 76 5 4 6 6 7 6 C 7 7 7 6 C 5 68 7 B C 7 7 6 68 6 7D 7 5 57 D ...

Страница 61: ... contacts K6 Burner ON dry contact output relay KG Gas operation relay KO Light oil operation relay MP Pump motor MV Fan motor PA Air pressure switch PE Burner earth PGM Maximum gas pressure switch PGMin Minimum gas pressure switch PO Oil pressure switch PO1 Maximum oil pressure switch on return line RS Remote burner reset button SV General safety valve S1 Emergency stop button S2 Off automatic ma...

Страница 62: ......

Страница 63: ......

Страница 64: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www riello com ...

Отзывы: