20010309
18
GB
Installation
5.7
Securing the burner to the boiler
Prepare an adequate system of hoisting by hooking onto the
rings 3)(Fig. 12).
Slip the thermal protection (standard equipment) onto the
blast tube 4)(Fig. 12).
Place entire burner on the boiler hole arranged previously,
(see Fig. 11), and fasten with the screws given as standard
equipment.
5.8
Accessibility to the interior of the combustion head
In order to reach inside the combustion head (Fig. 13) proceed as
follows:
disconnect the electrical wiring related to oil pump/servomo-
tor, air servomotor and gas pressure switch;
disconnect the leverages related to air damper and head
movement;
unscrew the 4 x fixing screws 1);
release the cable of the electrode 2);
disconnect the oil pipes by unscrewing the two
connectors 3).
Release the ignition pilot retainer;
remove the screw/gas pressure test point 6) of the combus-
tion head;
unscrew the under part of the elbow until it comes free of its
slot;
extract the internal part 5) of the combustion head.
5.9
Position of electrodes
WARNING
The burner-boiler seal must be airtight.
Fig. 12
D3507
WARNING
While unscrewing, some fuel may leak out.
1
2
2
3
4
7
5
8
6
Fig. 13
D9424
WARNING
Place the electrode on the ignition pilot observing
the dimensions specified in Fig. 14.
Fig. 14
18.5
0
- 2
71.5
± 1
Diffuser
Electrode
D9218
Содержание RLS 800/E MX
Страница 2: ......
Страница 77: ...39 20010309 Electrical panel layout Schéma tableau électrique ...
Страница 78: ...20010309 40 Electrical panel layout Schéma tableau électrique ...
Страница 80: ...20010309 42 Electrical panel layout Schéma tableau électrique ...
Страница 81: ...43 20010309 Electrical panel layout Schéma tableau électrique 0 1 1 1 ...
Страница 82: ...20010309 44 Electrical panel layout Schéma tableau électrique 0 ...
Страница 83: ...45 20010309 Electrical panel layout Schéma tableau électrique 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 ...
Страница 89: ......
Страница 90: ......