21
20027761
GB
Installation
5.12
Light oil supply
5.12.1 Double-pipe circuit
The burner is equipped with a self-priming pump which is capable
of feeding itself within the limits listed in the Tab. J at the side.
The tank higher than the burner A
(Fig. 21)
The distance "P" must not exceed 10 meters in order to avoid
subjecting the pump’s seal to excessive strain; the distance "V"
must not exceed 4 meters in order to permit pump self-priming
even when the tank is almost completely empty.
The tank lower than the burner B
(Fig. 21)
Pump depression values higher than 0.45 bar (35 cm Hg) must
not be exceeded because at higher levels gas is released from
the fuel, the pump starts making noise and its working life-span
decreases.
It is good practice to ensure that the return and suction lines enter
the burner from the same height; in this way it will be less proba-
ble that the suction line fails to prime or stops priming.
5.12.2 The loop circuit
A loop circuit consists of a loop of piping departing from and re-
turning to the tank with an auxiliary pump that circulates the fuel
under pressure.
A branch connection from the loop goes to feed the burner.
This circuit is extremely useful whenever the burner pump does
not succeed in self-priming because the tank distance and/or
height difference are higher than the values listed in the Tab. J.
Tab. J
Key to layout
(Fig. 21)
H = Pump/foot valve height difference
L
= Piping length
Ø = Inside pipe diameter
1
= Burner
2
= Pump
3
= Filter
4
= Manual on/off valve
5
= Suction line
6
= Foot valve
7
= Rapid closing manual valve remote controlled (only Italy)
8
= On/off solenoid valve (only Italy). See layout of electric
panel board. Electrical connections set by installer (SV)
9
= Return line
10 = Check valve (only Italy)
Explosion danger due to fuel leaks in the pres-
ence of a flammable source.
Precautions: avoid knocking, attrition, sparks and
heat.
Make sure the fuel interception tap is closed be-
fore performing any operation on the burner.
WARNING
The fuel supply line must be installed by qualified
personnel, in compliance with current standards
and laws.
H (m)
L (m)
Ø (mm)
10
12
14
16
4
14
30
55
95
3,5
13
28
52
89
3
12
26
48
82
2.5
11
24
44
76
2
10
22
41
70
1.5
9
20
37
63
1
8
18
33
57
0,5
7
16
29
51
0
6
14
26
44
-0,5
5
12
22
38
-1
4
10
18
32
-1,5
3
8
15
25
-2
6
11
19
-2,5
4
7
13
-3
4
7
V
H+
H-
P
10
c
m
Fig. 21
D3513
Содержание RLS 650/M MX
Страница 2: ...Translation of the original instructions ...
Страница 50: ...20027761 48 GB Appendix Electrical panel layout ...
Страница 51: ...49 20027761 GB Appendix Electrical panel layout 0 1 1 1 ...
Страница 52: ...20027761 50 GB Appendix Electrical panel layout 0 0 1 0 1 2 0 3 0 1 0 1 1 0 0 0 0 0 40 4 4 0 0 1 2 0 1 ...
Страница 53: ...51 20027761 GB Appendix Electrical panel layout 0 0 0 ...
Страница 54: ...20027761 52 GB Appendix Electrical panel layout 0 1 1 1 2 3 45678 9 55 ...