Start-up, calibration and operation of the burner
6.9.0.2 CALC function
The diagram (Fig. 52) shows how the fuel modulation curve is
modified if the values of point “P5” are changed.
By keeping the “+” key pressed for more than 3 s, the points
from “P6” to “P8” are recalculated.
By keeping the “-” key pressed for more than 3 s, the points
from “P4” to “P2” are recalculated.
The diagram of (Fig. 53) shows the fuel modulation curve when,
after the modification of point “P5”, the recalculation of all the oth-
er points is not carried out.
Fig. 52
P0
P1
P2
P3
P4
P5
P6
P7
P8
P9
0
10
20
30
40
50
60
70
80
90
100
An
g
le
(
d
e
g
re
e
s
)
Point of the curve
Original
curve
Fu
el
CALC-
CALC+
D7908
Recalculation
Fig. 53
P0
P1
P2
P3
P4
P5
P6
P7
P8
P9
0
10
20
30
40
50
60
70
80
90
100
Point of the curve
An
g
le
(
d
e
g
re
e
s
)
D7909
Fu
el