2613
8
GB
4.5
COMBUSTION HEAD SETTING
(see fig. 11, page 7)
It depends on the output of the burner and is carried out by rotating clockwise or counterclockwise the setting
screw (5) until the set-point marked on the regulating rod (9) is level with the outside plane of the nozzle-holder
assembly (1).
In the sketch the combustion head is set for an output of 1.50 GPH at 12 bar.
The set-point
3
of the regulating rod (9) is at the same level with the outside plane of the nozzle-holder as-
sembly (1) as shown in the schedule.
4.6AIR DAMPER ADJUSTMENT
(see fig. 11, page 7)
To vary the setting adjust the screw (7) after loosing the nut (8).
When burner shuts down the air damper automatically closes till a
max. chimney depressure of 0.5 mbar.
4.7
BURNER START-UP CYCLE
Lock out is indicated by a lamp on the control box (3, fig. 1, page 1).
5.
MAINTENANCE
The burner requires periodic maintenance carried out by a qualified and authorised technician
in conformity
with legislation and local standards.
Maintenance is essential for the reliability of the burner, avoiding the excessive consumption of fuel and conse-
quent pollution.
Before carrying out any cleaning or control always first switch off the electrical supply to the burner
acting on the main switch of the system.
THE BASIC CHECKS ARE:
Check that there are not obstructions or dents in the supply or return oil pipes.
Clean the filter in the oil suction line and in the pump.
Clean the photoresistance, (7, fig. 1, page 1).
Check for correct fuel consumption.
Replace the nozzle (see fig. 10, page 6) and check the correct position of electrodes (fig. 12, page 7).
Clean the combustion head in the fuel exit area, on the diffuser disc.
Leave the burner working without interruptions for 10 min. and set rightly all the components stated in this
manual.
Then carry out a combustion check verifying:
Smoke temperature at the chimney;
Content of CO
2
(%);
Content of CO (ppm);
Smoke value according to opacity smokes index according to Bacharach scale.
Lock-out due to failure to light
C
Normal
D5029
~
12s
Thermostat
Motor
Ignition transformer
Oil valve
Flame
Lock-out lamp
~
12s
5 s
C