Installation
5.6
Burner assembly
CF Application
In case of
CF
applications, the burner shall not operate without
protection
(A)
of the suction inlet (Fig. 7).
BF Application
In case of
BF
applications an optional snorkel and gasket are
available replacing
(A)
with
(B)
(Fig. 8)
This item can be supplied separately.
The combustion air supply is through a flexible or rigid pipe con-
nected to the air intake.
Consequently, you must comply with the following requirements
and instructions:
The combustion air intake tube must be:
- fastened securely to the burner;
- made of a suitable material, with temperature characteris-
tics in the range - 30 °C to 80 °C;
- in compliance with all requirements of applicable regula-
tions in force in the country of destination.
The intake-tube / burner system must not allow a loss of
over 2 m
3
/h at 0.5 mbar:
for instance, the above requirements will be met if you use flues
for pressure exhaust of flue gases (the condensation kind).
Make sure the air intake tube’s inlet is positioned so that it is
not likely to be obstructed by foreign matter and, where nec-
essary, use suitable screens.
The inside diameter of the hose must be at least 80 mm.
The intake tube can be up to 6 metres in length.
NOTE:
Burner installation must in any case comply with the flue
systems included within the boiler approved configuration.
CAUTION
The temperature of the incoming air must not
exceed 70 °C.
WARNING
For correct BF application, the burner must be in-
stalled on an appropriate BF boiler.
D5884
A
Fig. 7
B
D5883
Fig. 8
WARNING
Length is reduced if there are bends in the intake
section.
For instance, using a tube with a smooth inside
surface, you must allow for the following losses:
– for each 45° bend, tube length is reduced by
0.5 m;
– for each 90° bend, tube length is reduced by
0.8 m.
WARNING
Under no circumstances should the air’s
entry in the hose intake area be obstructed.
The hose must not be blocked in any way or
feature a shutting device (valves, membranes
etc.).